1. BRUSHLESS SYNCHRONOUS MOTOR/GENERATOR Type AMS 900L6L BST     

13700kW / 11688kVA, PF=1 / 0.8 12470V 60 Hz, 1200 rpm Designed for generator starting Designed according to NEMA MG1

2. MOTOR CONTROL PANEL 3. MAIN TERMINAL CONNECTION BOX

SEC.1   

1.

BRUSHLESS SYNCHRONOUS MOTOR/GENERATOR 

Technical Specification

Type AMS 900L6L BST   ‐ brushless synchronous Motor/Generator   ‐ 13700kW/11688kVA, PF=1/0.8  ‐ 12470V   ‐ 60 Hz, 1200 rpm   ‐ installation in safe area   ‐ Designed for generator starting  ‐ Designed according to NEMA MG1  Description

Eng. Units

Total output Output DE Output NDE Input DE at P.F 0.8 Input NDE at P.F 0.8 Power factor (overexcited) Voltage Frequency Speed Current Exciter type Exciter output Excitation Applicable standards Insulation class stator and exciter Insulation class main rotor Temperature rise, stator within class Temperature rise, rotor within class Efficiency at P.F. 1 and 100 % load 75 % load 50 % load 25 % load Efficiency at P.F.0.8 and 100 % load 75 % load 50 % load 25 % load

 



kW kW kW kW kW

Motor

Generator

13700 6850 6850 1.00 12470 60 1200 643 GLB 600B 33 78 / 8.2 NEMA F H B B

11688 (kVA) 4770 4770 0.8 12470 60 1200 541 GLB 600B 46 93 / 9.9 NEMA F H B B

% % % %

98.57 98.50 98.18 96.92

98.56 98.42 97.99 96.46

% % % %

-

98.00 97.83 97.30 95.43

V (±10) Hz (±5) rpm A kVA V/A

SEC.1   

BRUSHLESS SYNCHRONOUS MOTOR/GENERATOR 

 

2.

Included accessories

2.1   ‐   2.2   ‐ ‐ ‐ ‐   2.3   ‐

Main Electrical Data  Guaranteed efficiency 

‐   2.4   ‐ ‐ ‐ ‐ ‐ ‐     2.5   ‐ ‐ ‐

‐      

Main Mechanical Data  Cooling arrangement: IC8 A6W7. Separate motor driven fans air/water cooled machine.  Counter clockwise direction of rotation at drive end, facing shaft end.  Protection of machine IP54  Temperature rise, stator within class B  Excitation  Main brushless exciter type GLB for DC excitation complete with diode bridge, thyristors, RC‐ circuits and control box.  MCP530, UL Certified  Cooling System  Air‐to‐water single tube cooler with ANSI flanges (Design/Test pressure 0.6/0.9MPa)  Ethylene glycol as water cooler anti‐freeze (20 %).    External fans redundancy. Normally 2 out of 4 fans in service  Two water coolers in series on air side (2x70%)  Water cooler connection at left side of machine facing DE  Water cooler material: Tubes: Cu 90%/Ni 10%, Tube end plates: Naval brass, Water box:  Rilsan coated steel, Plate fins: Aluminum 

Shaft Extensions  Cylindrical shaft end in DE    Cylindrical shaft end in NDE  Coupling: two (2) piece coupling half by MAYR Corp ROBA‐DS 7300/956.060‐S  o Alternating/Rated/Shock Torque: 48.7 / 73 / 146 kNm  o Max speed 1200rpm  o 220 mm H7 bore with shrink disc  o Sleeve for HBM T40FM‐60kNm transducer flange  Material of rotor body and shaft: 34CrNiMo6+QT (2541) 

 

SEC.1      2.6   ‐ ‐ ‐ ‐ ‐ ‐

‐ ‐ ‐ ‐ ‐ ‐ ‐   2.7   ‐ ‐   2.8   ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐   2.9   ‐ ‐ ‐   2.10   ‐ ‐    

BRUSHLESS SYNCHRONOUS MOTOR/GENERATOR 

Bearings  Both DE and NDE bearings insulated, DE grounded with cable.  Complete bearing oil connection system to common point, stainless in‐ and outlet, ANSI  Flow sight glass in oil outlet, stainless steel  Forced lubricated sleeve bearing. Bearing provided with loose oil ring.  Orifice    Mineral oil, quality ISO VG 46. Oil inlet temp min 40degC, max 65degC. Degree of purity for  oil: 17/15/12 acc. to ISO 4406:1999. (ISO VG 100 requires an oil inlet temperature min 40  degC, max 70degC)  Oil connection at left side of machine seen from DE, located in the center of the machine.     Oil flow meter in stainless steel with contact, safe area  Oil inlet flange: 3/4 Cl 150  Oil inlet pressure 2.5 bar (g), ABB standard.  Oil outlet flange: ANSI 3 Cl 150  Rotor axial end play +/‐6 mm.  The lube oil drain pressure must be less than or equal to the machine ambient pressure. An  oil drain pressure of 200‐1000 Pa lower than the bearing ambient is recommended.  Main Terminal Boxes and Related Accessories  Stator winding terminated with busbars and a flange adapted for special terminal box,  terminal box supplied by ABB USA.   Stator winding termination on the right side, seen from DE  Monitoring and Protection Accessories  1x RTD in warm exciter air, duplex (Pt100), 3 wire, unshielded.  1x RTD in warm machine air, duplex (Pt100), 3 wire, unshielded.  1x RTD per Bearing Shell, duplex (Pt100), 3 wire, unshielded  2x RTD in cold machine air, duplex (Pt100), 3 wire, unshielded (mounted at NDE + DE)  6x RTD's in stator windings, single (Pt100), 3 wire, unshielded, safe and hazardous area  Heaters in both main machine and exciter, safe area, 480 VAC 3 phase supply. The heaters  should always be connected during stand still to avoid condensation.  Painted carbon steel junction boxes located at left side of machine facing DE.  Water leakage detector, float switch, Safe area.  Foundation and Installation  Long sole plate (ABB std) including anchor bolts, leveling screws etc.  Mounting kit including fastening screws, jacking screws and dowel pins.  Stainless steel mounting and alignment shim pack  Special Design and Accessories  Premium efficiency electrical steel sheets.  Silver solder in rotor coils. 

SEC.1    2.11   ‐ ‐   2.12   ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐

BRUSHLESS SYNCHRONOUS MOTOR/GENERATOR  Painting and corrosion protection  ABB blue color (NCS 4822‐B05G)  Standard industrial coating acc. to ISO 12944 C3  Spare parts  1 x Control pulse unit  6 x Diode  2 x Thyristor  1 x Bearing shell DE  1 x Bearing shell NDE  2 x Oil ring  4 x Labyrinth seal  2 x Seal ring  M/GCP spare parts acc. to Technical specification M/GCP, 3BSY 200439‐GHT. 

2.13    Packing and Transportation  ‐ Seaworthy wooden case packing, long time storage. 

3.

Documentation ‐ ‐ ‐ ‐

Material Certificates, according to ITP  Standard documents for Machine according to List of documents, 3BSY 200027‐GHT  Test procedures, according to ITP, 3BSY 2000003‐GHT  User's manual on CD: 1 copies 

4. Workshop tests ABB Machines standard procedure is to perform a type test for a single machine order. If two or  more identical machines are ordered, then a type test is performed on the first machine and routine  tests on the remaining machines.  Proposed workshop tests according to enclosed Inspection plan, 3BSY200003‐GHT are part of our  manufacturing program and are part of the quoted price of the machine.  Witness tested by General Compression engineers 

SEC.1   

BRUSHLESS SYNCHRONOUS MOTOR/GENERATOR 

SEC.2   

MOTOR CONTROL PANEL

 

1. ACCESSORIES The Motor Control Panel includes following accessories:   ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐

MCB for short circuit protection of auxiliary circuits  Single phase thyristor converter  Exciter field breaker  Transducers for Motor or bus voltage, Active power, Reactive power, Stator current  Transducers for Excitation current and Diode supervision  Power supply units for 24VDC from AC and DC supply  Set of auxiliary relays for operation  Synchronizer  Synch‐check relay  Emergency stop button  Single phase power supply transformer of dry‐insulated type. The transformer is installed  inside the Motor Control Panel. 

2. POWER SUPPLY Main excitation power supply ‐ ‐

Voltage supply, single phase   480 V, 60 Hz   Power demand     3000 VA  

Auxiliary power DC Separate auxiliary power supply for the electronics, protection and back‐up excitation is  recommended.  ‐ ‐

Voltage     Power demand  

   

110 V DC   1500 W  

Auxiliary power AC Separate auxiliary power supply for light and socket outlet  ‐ ‐

Voltage  Power   

   

   

120V, 60 Hz  300 VA  

Thyristor converter output Supplied from internal transformer  ‐ ‐ ‐

Excitation supply voltage, single phase    Maximum continuous excitation current   Maximum boosting excitation current    

Measuring circuits ‐ ‐ ‐ ‐ ‐

Voltage three phase   Power consumption   Current single phase   Power consumption   Frequency    

         

100‐120 V   <2 VA / phase   1 or 5 A   <1 VA   50 Hz  

180 V DC   20 A DC   30 A DC for 10 sec  

SEC.2   

MOTOR CONTROL PANEL

3. PANEL Main features  The motor control with accessories is mounted in a freestanding control panel. The regulator with  accessories is mounted in the rear plane of the cubicle. Terminals for external wiring are located at  the rear plane of the panel. The panel is intended for cable connections from bottom. Access is from  the front.   ‐ Dimensions L x W x H     800 x 500 x 2100 mm   ‐ Weight        250 kg  ‐ Degree of protection     IP 41   ‐ Ambient temperature     0 ‐ +40 C   ‐ Standard color       RAL 7035   Standards  ‐ The Motor Control Panel is designed to meet following standards:   ‐ UL for panels 508  ‐ EMC Directive 2004 / 108 / EC   ‐ Low Voltage directive 2006 / 95 / EC  

4. DOCUMENTATION Following documentation is included with the delivery:   ‐ Circuit diagram   ‐ Panel layout drawing   ‐ Single line diagram   ‐ List of apparatus   ‐ Signal transfer list   ‐ Internal wiring table   ‐ Setting list for the protections and for the regulators   ‐ Instruction manual for each major component  

5. WORKSHOP TESTING ABB’s standard procedure is to perform a test for every Control Panel. Proposed workshop tests  according to enclosed INSPECTION PLAN are part of our manufacturing program and are part of the  quoted price of the panel.  Witness tested by General Compression engineers 

6. PACKING The Motor Control Panel is put in an impregnated wooden crate. 

SEC.2   

MOTOR CONTROL PANEL

SEC.3   

MAIN TERMINAL CONNECTION BOX

ABB Motor_Gen_12470_V 13700kW_f.pdf

Rilsan coated steel, Plate fins: Aluminum. 2.5 Shaft Extensions. ‐ Cylindrical shaft end in DE. ‐ Cylindrical shaft end in NDE. ‐ Coupling: two (2) piece coupling ...

893KB Sizes 46 Downloads 254 Views

Recommend Documents

ABB SACE - ABB Group
1999. Plugs, socket-outlets and couplers for industrial purposes - Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories. IEC 61008-1. 1996. Residual current operated circuit-breakers without integral overcurrent pr

ABB SACE - ABB Group
the main parameters of the components of an electrical plant and for the selection of the protection devices for a wide range of installations. Some application examples ...... time switches. IEC 60364-1. 2001. Electrical installations of buildings -

147454490757e3c50b7757a.Workspot 2016 - PAPER ABB Ltda.pdf ...
147454490757e3c50b7757a.Workspot 2016 - PAPER ABB Ltda.pdf. 147454490757e3c50b7757a.Workspot 2016 - PAPER ABB Ltda.pdf. Open. Extract.

abb transformer handbook pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. abb transformer ...

abb electric motor catalogue pdf
abb electric motor catalogue pdf. abb electric motor catalogue pdf. Open. Extract. Open with. Sign In. Main menu. Displaying abb electric motor catalogue pdf.

ABB-ACS55-Users-Guide.pdf
Page 2 of 19. EN 7. Safety instructions. Read the following instructions carefully before proceeding with the. installation. Warning! Dangerous voltage! Only a competent electrician may install ACS55. Never work on the drive, the motor cable or the m

ABB-ACS850-04-Firmware-Manual.pdf
Table of contents. Page 3 of 296. ABB-ACS850-04-Firmware-Manual.pdf. ABB-ACS850-04-Firmware-Manual.pdf. Open. Extract. Open with. Sign In. Main menu.

ABB-depression-Protocol-09052016.pdf
There was a problem loading this page. Retrying... ABB-depression-Protocol-09052016.pdf. ABB-depression-Protocol-09052016.pdf. Open. Extract. Open with.

MCCB ABB TMax Lamha.vn.pdf
Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. MCCB ABB TMax Lamha.vn.pdf. MCCB ABB TMax Lamha.vn.pdf.

TU-RMU-ABB-24KV.pdf
Page 1 of 88. ABB AS, Power Products Division. SF6-insulated Ring Main Unit type SafeRing 12 - 24 kV and. SF6-insulated Compact Switchgear type SafePlus 12 - 24 kV. Product catalogue. Page 1 of 88 ...

Environmental and financial performances of ABB ...
results show a high correlation between the covariates where the signs are ...... aspects and how those are affected by the firm or how those – visa versa ...... order, Deutsche Bank, Citigroup, Credit Suisse, ABN AMRO, UBS Warburg, HSBC, ...

ABB Calor Emag Taschenbuch – Schaltanlagen, 10 ... -
The civil engineering consultant must determine a large quantity of ... If, however, necessary, structural measures for protection of the electrical installations.

A Comparison of WirelessHART and ZigBee for Industrial ... - ABB Group
tion between a host application and smart field instru- ments, providing access to diagnostics, configuration and process data [1]. Traditionally, HART specified a ...

Bang-gia-bien-tan-abb-2016.pdf
Page 1 of 17. Page 1 of 17. Page 2 of 17. Page 2 of 17. Page 3 of 17. Page 3 of 17. Bang-gia-bien-tan-abb-2016.pdf. Bang-gia-bien-tan-abb-2016.pdf. Open.

ABB-Low Voltage Capacitors-Power Factor Correction Solutions.pdf ...
Page 1 of 20. Low Voltage Capacitors. Power Factor Correction Solutions. Low Voltage Products. www.dienhathe.info. www.dienhathe.org. Page 1 of 20 ...

MCCB ABB Tmax T6-T7-T8 Lamha.vn.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. MCCB ABB ...