Boise Data Center Guarantees 100 Percent Uptime All-Copper Grounding Systems Ensure Reliability, Lower Maintenance Costs Among Involta’s newest-generation data centers is this 31,400 square feet facility in Boise, Idaho. The colocation center targets clients who opt to outsource mission-critical services, along with IT consulting and management, in order to concentrate on their core businesses. The center initially comprises two 100-cabinet data halls but was built for a several-fold increase in capacity. Like other Involta data centers, the facility features a robust all-copper grounding system coupled with a full-area lightning protection system. And, like a growing number of mid-sized data centers, it was designed and built to maximize electrical energy efficiency.

Involta is a Cedar Rapids, Iowa-based company that designs, builds and operates mission-critical-class data centers. Founded in 2007, the company operates 11 centers in six states1. It targets clients looking for the flexibility, security and economy of a full-service colocation center including IT consulting and management. Among Involta’s latest-generation centers is a 31,400 square foot facility located in Boise, Idaho (Cover Photo). Commissioned in December 2014, the center was built with an initial capacity for approximately 150 cabinets drawing 2.5 MW at full load. It can expand to nearly four times its current size and data capacity as business grows. It has two data halls, one of which is now operational (Figure 1). Involta creates and maintains the highest practical level of reliability at its centers to guarantee 100 percent uptime for its tenants. In data center terms, reliability means having lots of built-in redundancy, at least duplicate equipment and/or systems for any mission-critical need. Redundancy can be seen wherever one looks at Involta-Boise, and most of it involves copper. Iowa, Ohio, Idaho, Minnesota, Arizona, Pennsylvania

1

COPPER ELECTRICAL APPLICATION - POWER QUALITY | WWW.COPPER.ORG

FIGURE 1. A portion of data hall No. 1 at the Involta-Boise data center shown shortly after the center’s commissioning in late 2014. Most tenants prefer to cage their cabinets for additional security beyond that offered by the extensive systems in place at the center.

FIGURE 2.

FIGURE 3.

The Boise center is supplied with two 2.5-MW/12.7-kV feeds. Power is fed to the center via two independent, redundant feeds labeled “Blue” and “Red”.

One of two 2500-kW, 13.5-kV/480-V utility transformers serving distribution switchgear in one of the Boise center’s data rooms.

Redundant Power System

equipment quickly without relying on traditional connections. All-copper conductors in the busways supply three-phase power to customers at 208V/225A, which is sufficient for any expected requirements. We try to split the load evenly and never get above 50 percent on either of the dual circuits, so in the event that there is a failure in one of those feeds, the alternate busway can support the IT load on that particular rack or row of racks.”

Jeremiah Hinkle has managed Involta’s Boise data center since it opened. He can point out redundant equipment and systems literally from top to bottom. “I should start by explaining that we have independent dual power feed systems that extend all the way from the Idaho Power substation (Figure 2) to the customers’ racks,” Hinkle said. “We chose to label them ‘Red’ and ‘Blue’ feeds and color-code them accordingly. Most other centers use ‘A’ and ‘B’ terminology. The substation supplies the center with up to 2.5 MW at 12.7 kV. Power is fed to two step-down utility transformers (Figure 3) that are individually dedicated to one power room apiece, supplying 480 V to our main distribution switchgear. The facility has additional transformers inside the power room to step power down to 208 V for distribution to the data hall and 120 V for the office.

Starline busways are also used in the carrier room, which houses servers for outside vendors such as internet service providers, telephone and communications networks, etc. Racked equipment is bonded to traditional copper busbars installed on a portion of the racks overhead (Figure 5). Double-screw lugs ensure the long-term reliability of equipment bonding connections. Where Starline or conventional connections are used, the racks themselves are also robustly bonded (Figure 6)

Power enters the facility as the two Red and Blue feeds. In the event that we do experience a utility failure, we’ve implemented and installed a tie-breaker system in our power rooms so that if we happen to lose our Red utility feed, for example, that tie will close and the Red bus will be fed through the Blue switchgear. It works well.” Hinkle explained that distribution from the power rooms to the customer occurs through two power modules that Involta provides. “Customers provide their own dual power distribution units to support their IT equipment,” Hinkle said. “We use Starline™ busways (Figure 4) which enable technicians to add or change

FIGURE 4. Red and Blue power feeding equipment via Starline busways. The compact busways enable rapid connection of attached IT equipment. The busways shown are rated at 208V/255A.

COPPER ELECTRICAL APPLICATION - POWER QUALITY | WWW.COPPER.ORG

Cooling System Saves Energy

FIGURE 5A.

FIGURE 5B.

Equipment racks in the relatively small (compared with data rooms) carrier rooms are also connected via busway (Figure 5a). Grounding connections are made to a copper grounding bus located above the stack of cabinets in the racks (Figure 5b).

Involta has refined its data center designs over the years. “This is what we do as a company,” Hinkle said. “At Involta-Boise, we decided to design our air returns a bit differently than those in our other data centers. At Boise, we actually built a four-foot-wide gap, or mixing chamber, between the data hall and the mechanical spine where the four, 25-ton Liebert DSE units reside (Figure 8).2 Cold output air from the Lieberts feeds into the mixing chamber. We placed return grates in the data hall up high near the ceiling so that the Lieberts constantly create a negative pressure — a vacuum effect — pulling the hot air in up high before injecting it into the four-foot mixing chamber. There, output from the Lieberts cools it and sends it back into the data hall to cool the customers’ IT equipment.” The center utilizes a number of other energyefficient practices, including LED lighting, motionsensing light switches and efficient mechanical equipment, plus the ability to incorporate free-air cooling when outdoor temperatures permit.

Does it work? FIGURE 6. Equipment mounted in racks. Green wires are routed to the left of the figure and up to the Starline buses. Insert shows green wire with double-screw attachment lug.

Back-Ups The center is equipped with two, 1-MW emergency generators serving the Red and Blue power feeds, respectively (Figure 7). The generators are load-tested monthly and no-load tested weekly, with results carefully documented. Should there be a utility failure and one generator simultaneously goes down, the second backup generator can support the critical load. Backing up the power feeds to the data halls are two 500 kW-UPS units equipped with sufficient battery capacity to keep the critical load operating for 50 minutes based on the current critical load. One beneficial feature of the dual “Red” and “Blue” system is that it enables personnel to shutdown either feed if the other one requires maintenance or repair. Equipment on the system then remains completely operational and the center’s 100 percent uptime is preserved.

Absolutely. Hinkle proudly notes that the center’s power utilization efficiency (PUE) is between 1.4 and 1.6, which is remarkably low for a center like Involta-Boise.

PUE is the ratio of a facility’s total energy consumption to the amount of energy sent to IT equipment. Total energy includes such functions as heating and cooling, lighting and office. A “perfect” PUE rating, obviously unobtainable, would be 1.0.

PUE

Total Facility Energy IT Equipment Energy

While PUE has several shortcomings as an energy-efficiency metric, it is still widely used in the data center industry. “This facility really has exceeded my expectations,” Hinkle said. “In the beginning, my goal was to operate at 1.5 PUE. Typically, at older data centers, you see a 2.0 PUE. To be lower than that is good, but in my opinion to be at a 1.5 to 1.2 is incredible.”

Placing mechanical equipment outside the data rooms contributes to the center’s overall security since it restricts access to the data floor by mechanical tradesmen and others who might not fully appreciate the sensitive nature of the IT environment.

2

COPPER ELECTRICAL APPLICATION - POWER QUALITY | WWW.COPPER.ORG

FIGURE 7. Involta – Boise is equipped with two 1 MW emergency generators, either of which can supply the critical loads in the entire center.

“Textbook” Grounding and Lightning Protection

FIGURE 8. Three of four 25-ton Liebert units supplying cold air for the center. Air is then mixed in a mixing chamber (insert) located behind the units (insert).

Unfortunately, even in modern data centers, electrical grounding and lightning protection are too often treated as afterthoughts. That’s not so at Involta centers, and certainly not at Involta-Boise, where grounding is especially robust throughout the facility. • There is one grounding system with uninterrupted electrical continuity throughout the entire center. All of the center’s electrical equipment, including IT equipment, therefore operates at a single, uniform ground potential. That very important feature is surprisingly easy to overlook. • An AWG 2/0 buried bare copper ring ground completely surrounds the facility (Figure 10). Bonded to the ring at periodic intervals are 10-feet X ¾-inch copper-clad grounding electrodes. Access ports along the ring allow for inspection of such items as lug tightness and ground resistance. All electrical and lightning systems are connected to this ring.

FIGURE 9. Equipment racks themselves are bonded to copper busbars which serve the equipment cabinets and are then connected to the overhead busways.

• Mechanical equipment, water, gas and telephone systems are properly grounded per National Electrical Code requirements. Mechanical equipment and IT systems do not share branch circuits. • IT equipment grounding begins at the cabinets, where #6 AWG or larger green wires are firmly bonded to equipment cases using double-screw lugs (Figure 6). Green wires are bundled and routed upward to Starline buses. • Starline buses are used in the center’s carrier rooms, where servers for internet service providers, networking and other communications companies are installed. Bonnding conductors are routed to traditional copper grounding bars attached to rack frames. The racks themselves are bonded to the copper bus with heavy-gage copper cables (Figure 9). • Heavy gage grounding conductors connect Starline systems with copper grounding bars placed at convenient locations in the data rooms and mechanical spine. • Also bonded to the ring are copper down-conductors from the rooftop lightning protection system. It consists of interconnected, regularly spaced surge termination devices (lightning rods) mounted along the roof’s periphery.

FIGURE 10. A 2/0 buried copper ground ring completely surrounds the structure, with 10 feet X ¾ inch tinned copper-clad vertical electrodes placed at periodic intervals. Note the inspection box to allow maintenance and testing.

COPPER ELECTRICAL APPLICATION - POWER QUALITY | WWW.COPPER.ORG

That’s a Lot of Copper! Is Copper Cost-Competitive? The initial cost of copper cable is normally higher than aluminum cable of equivalent ampacity. But what seem to be simple economics in aluminum’s favor, is strongly mitigated by the fact that electrical grounding conductors usually comprise less than one percent of a major technical construction project such as a data center. In addition, copper grounding conductors require far less maintenance (and lower labor costs) than aluminum systems. The red metal doesn’t “creep” like the softer aluminum does; meaning that connections remain tight and don’t require frequent torqueing to keep systems intact. Copper is also naturally corrosion resistant and represents a far less

long-term deterioration. Taken together, those factors easily make copper the cost-comparative. All this means it’s more reliable, a vital consideration at data centers. “It may be cheaper up front to use aluminum, but it’s going to be more expensive to maintain,” Hinkle said. Inside plant at Involta-Boise, from downstream of the distribution switchgear to all the way out to the customer, our systems are all copper.” For more information about grounding and lightning protection systems, visit www.copper.org

COPPER ELECTRICAL APPLICATION - POWER QUALITY | WWW.COPPER.ORG

A6185 - XX/16

copper.org

Boise Data Center Guarantees 100 Percent Uptime - EC Mag

Involta is a Cedar Rapids, Iowa-based company that designs, builds and operates ... services, along with IT consulting and management, in order to concentrate ...

6MB Sizes 6 Downloads 182 Views

Recommend Documents

Boise Data Center Guarantees 100 Percent Uptime - EC Mag
Insert shows green wire with double-screw attachment lug. COPPER ... The center utilizes a number of other energy- ... PUE is the ratio of a facility's total energy.

Boise Data Center Guarantees 100 Percent Uptime
close and the Red bus will be fed through the Blue switchgear. It works well.” Hinkle explained that distribution from the power rooms to the customer occurs ...

Probabilistic-Bandwidth Guarantees with Pricing in Data-Center ...
Abstract—Bandwidth-sharing in data-center networks is an important problem that .... 2; and we call this dynamically-allocated bandwidth. ..... 904–911, Sep. 2009.

The 1 Percent Solution - Mercatus Center
Budget of the United States Government, Fiscal Year 2012. 3 CBO ...... The New York Times published an online, interactive tool to .... Create a non-open-.

The 1 Percent Solution - Mercatus Center
high of $2.568 trillion (18.5 percent of GDP) in 2007 (a difference of $786 billion, or 44 ... income and product account data from the Bureau of Economic Analysis. .... the federal budget would balance in 2016 under a 1 percent reduction and by ...

CCNA Data Center- Introducing Cisco Data Center Technologies ...
Retrying... CCNA Data Center- Introducing Cisco Data Center Technologies Study Guide- Exam 640-916.pdf. CCNA Data Center- Introducing Cisco Data Center ...

Expedited Processing of Veteran's 100 Percent ... - Social Security
There are three ways in which you can apply. • Apply online at ... Call or visit your local Social Security office. ... The most convenient way to contact us anytime,.

Snell & Wilmer Earns 100 percent on Human Rights Campaign ...
Dec 5, 2016 - inclusive health care benefits, competency programs and public ... designation as a Best Place to Work for LGBTQ Equality. ... Founded in 1938, Snell & Wilmer is a full-service business law firm with more than 400 attorneys.

Snell & Wilmer Earns 100 percent on Human Rights Campaign ...
Dec 5, 2016 - Founded in 1938, Snell & Wilmer is a full-service business law firm with more than 400 attorneys practicing in nine locations throughout the ...

GNDEC M.Tech EC 2009 Data Communication Networks.pdf ...
(b) Discuss the CSMA/CD MAC layer protocol in detail. Q5) (a) Differentiate between packet..switching, message switching and circuit. ~witching in detail. . . . (b) What are the advantages ofFDDI over a basic Token ring? Q6) (a) What are functions of

Data Center Ethernet
Fibre Channel is the technology of choice for Storage Area Networks (SANs). It provides the ..... (http://www.t11.org/ftp/t11/pub/fc/sw-2/01-365v0.pdf). 16.

Boise State University
Deployed Google Apps for Education to students, staff ... Technology, “from a technical standpoint, we were falling behind the curve because we were tied to a ...

Chiropractic Boise Id.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. Chiropractic ...

man-100\ally-financial-payment-processing-center-address.pdf ...
Page 2 of 5. ALLY FINANCIAL PAYMENT PROCESSING CENTER. ADDRESS PDF. Ally Financial Payment Processing Center Address. Offer us 5 mins and also we will certainly. reveal you the very best book to check out today. This is it, the Ally Financial Payment

man-100\canon-customer-support-center-uk.pdf
man-100\canon-customer-support-center-uk.pdf. man-100\canon-customer-support-center-uk.pdf. Open. Extract. Open with. Sign In. Main menu.

Percent
Yea, The 8-10 Reps. Seems To Work Best For Me As WellTo Build Mass. . I'M WithDave 100 Percent.. Arnold Schwarzenegger'S Blueprint To Cut:Nutritionthe.

data center design guide pdf
Loading… Page 1. Whoops! There was a problem loading more pages. data center design guide pdf. data center design guide pdf. Open. Extract. Open with.

40 plus mag ...
... kertas soalan lain di : Page 1 of 15. Page 2 of 15. Page 3 of 15. 40 plus mag milfs_____________________________________________________.pdf.

astuce criminal law Boise, Idaho.pdf
Page 3 of 10. Page 3 Mark Scheme Syllabus Paper. Cambridge IGCSE – October/November 2014 0606 23. © Cambridge International Examinations 2014. 4 (i) 2000 1000e ln 2 a b a b + = → += B1. (ii) 2 3297 1000e 2. ln 3.297 oe. a b a b − = →+. = M1.

data center proposal pdf
data center proposal pdf. data center proposal pdf. Open. Extract. Open with. Sign In. Main menu. Displaying data center proposal pdf.

Cheap 100% Original Xiaomi Wireless Switch House Control Center ...
Cheap 100% Original Xiaomi Wireless Switch House Co ... ice Accessories Free Shipping & Wholesale Price.pdf. Cheap 100% Original Xiaomi Wireless Switch ...

pdf-1476\data-center-fundamentals.pdf
Connect more apps... Try one of the apps below to open or edit this item. pdf-1476\data-center-fundamentals.pdf. pdf-1476\data-center-fundamentals.pdf. Open.