Technical Data October 2011
Lister-Petter LPW 3-27
CGT Stamford PI 044
50 Hz
Generator Model:
BCL 13-50
Power Factor
3-Phase
Cos Φ = 0.8
PRIME POWER (PRP)
RATINGS
STANDBY POWER (LTP)
Voltage
kVA
kWe
kVA
kWe
Amps
440/254
12
10
12
10
16
415/240
13
10
13
10
17
400/230
13
10
13
10
18
380/220
13
10
13
10
19
Definition of Ratings & Reference Conditions Prime Power (PRP) is the nominal output continuously available, where the average load (variable) does not exceed 70% of the prime power rating. No overload is available. Standby Power (LTP) is the maximum output available (at variable load), for up to 500 hours per year. No overload is available. Standard Reference Conditions: air inlet temperature 25°C (77°F), 150m (500ft) above sea level and 60% relative humidity. Note: The above ratings may be subject to derate at different operating conditions. Please see the Derate Guidelines on the Broadcrown Website. All power ratings and reference conditions in accordance with ISO 8528-1 and ISO 3046-1.
Key Features: ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Efficient water cooled diesel engine. Single bearing CGT Stamford alternator Radiator with pressure cap and drain point Fully guarded engine-driven fan Fabricated steel skid base with fork lift pockets Moulded polypropylene fuel tank with filler cap Heavy duty rubber anti-vibration mountings 12V starter battery and connecting cables Separate engine-driven battery charging alternator Spin on oil and fuel filters and dry type air filter element Industrial silencer (15dBA reduction) supplied loose BC 701E-M Key Start control system Main line circuit breaker Factory Test Certificate Operation & Maintenance Manual Wide range of optional extra features available
Overall Dimensions & Weights - Open Set Length (L) = 1310mm Width (W) = 540mm Height (H) = 1290mm
H
L
Dry Weight (inc oil) = 420kg Operating Weight = 480kg
W
Typical Open Generator Sound Pressure Level at 1m, Free Field (dB) Overall dBA
63 Hz
125 Hz
250 Hz
500 Hz
84
74
76
77
79
1000 Hz
2000 Hz
4000 Hz
8000 Hz
80
76
70
70
All designs and specifications subject to change without notice
BCL 13-50 October 2011
LISTER-PETTER LPW 3-27
ENGINE & COOLING SYSTEM
Engine Speed Gross Power Fan Power Net Power Emissions Certification Altitude Capability
PRIME
STANDBY 1500
r/min kWm kWm kWm
13 0.5 12.4
m
TBA
13 0.5 12.4 ―
litres/h litres/h litres/h litres/h litres
2.8 2.2 1.5
2.8 2.2 1.5
Air
Engine Air Flow Maximum Air Intake Restriction (used filter)
m³/s kPa
TBA
Exhaust
Exhaust Gas Flow Exhaust Gas Temperature Maximum Exhaust Back Pressure Typical Exhaust Pipe Diameter
m³/s °C kPa mm
TBA TBA
Radiator Cooling Air Flow Max Restriction to Cooling Air Flow Max Radiator Air-On Temperature Maximum Coolant Temperature Coolant Capacity - Engine Only Total Coolant Capacity
m³/s Pa °C °C litres litres
TBA TBA TBA 105 TBA 6.5
Total Oil Capacity incl Filters Typical Oil Pressure at Rated Speed Typical Oil Consumption (>250hrs Operation)
litres kPa litres/h
4 200 0.007
Heat Rejection to Engine Cooling Water Heat Rejection to Charge Cooler Heat Radiated From Engine (Typical)
kW kW kW
Electrical System Voltage Battery Type Battery Capacity SAE CCA
Fuel
740
Cooling
Fuel Consumption at 100% Power Fuel Consumption at 75% Power Fuel Consumption at 50% Power Total fuel flow Standard Fuel Tank Capacity
740
Oil
mm litres kPa
3 cyl / inline / 4-stroke Natural / None Mechanical Governor 86 / 80 1.395
Thermal
Cylinders / Type Aspiration / Charge Cooling Governing / Engine Management Bore / Stroke Cubic Capacity BMEP
TBA
Elec
General
Performance
SI Units
TBA TBA 7.5 TBA
TBA
TBA n/a
1.6
1.6 12 1 X 069 520
V A
CGT STAMFORD PI 044 SI Units
General Data
TBA 2.5
ALTERNATOR
Manufacturer Model (may vary with voltage) Operating Temperature Coupling / No. of Bearings Phase / Poles / Winding Type Power Factor Excitation Insulation System AVR Type Voltage Regulation
TBA 55
°C
PRIME
STANDBY
Cummins Generator Technologies - STAMFORD PI 044 F PI 044 F 40 27 Direct / Single Bearing 3-Phase / 4-Pole / Winding 311 Cos Φ = 0.8 Self Excited Class H SX 460 ± 1.0% All designs and specifications subject to change without notice
BCL 13-50 October 2011
BC 7210E-M Automatic Remote Start
STANDARD CONTROL SYSTEM The standard control system for the Midi Range is the BC 7210E-M Auto Start system, based on the DSE 7210 control module, which provides : ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Automatic remote start Overspeed protection Underspeed protection Low oil Pressure protection High coolant temperature protection Fail to Start indication Automatic cool-down timer function Optional - Common Alarm & System In Auto volt-free contacts
Together with digital displays for : ▪ Volts, Amps and Frequency ▪ Engine operating hours This system also has an increased digital input/output count for external options and, being cost effective in comparison with the optional analogue system, is the preferred choice for most customers. With a modest cost increase, the BC 7210-M is similar to the BC 7210E-M but comes with digital indications for Oil Pressure and Coolant Temperature.
CONTROL SYSTEM OPTIONS BC 7310 & BC 7320 control systems (Control Modules illustrated) provide complete power monitoring and protection facilities. Compared to BC 7210, additional features include : ▪ ▪ ▪ ▪ ▪
Pre-alarms for Low Oil Pressure and High Coolant Temperature Digital display of kW, kVA and Power Factor Under/Over Volts protection Over Current Protection Full RS485 Telemetry and SAE J1939 CANBus implementation. All generating sets driven by engines with onboard ECU/CANBus come with the BC 7310 as standard.
Note: The BC 7320 provides full AMF functionality with integrated mains monitoring and generator/mains contactor control.
The optional control system for the Midi Range is BC 701E-M (photo), based on the Deep Sea Electronics DSE701 Key Start controller. This provides for the manual control of the generator via a two-position key switch and membrane push button for Start, together with Overspeed, Low Oil Pressure and High Coolant Temperature protection. ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
LED indications for protection operation LED indication for charge alternator fail Membrane push button for engine preheat (where applicable) Analogue voltmeter with 4-position selector switch Analogue ammeter with 4-position selector switch Engine hours counter Emergency Stop button One auxiliary input for optional features Optional - Generator Running volt-free output
The panel is constructed in 1.5mm steel, powder coated to RAL9001 for a high quality, durable finish with the hinge points of the cover located at the bottom edge for improved maintenance access.
The BC 701-M control system (not illustrated) is similar to the BC 701E-M unit but benefits from the addition of : ▪ Analogue frequency meter ▪ Analogue gauges for Oil Pressure, Coolant Temperature & Battery Charge Amps ▪ 7-Position voltmeter selector switch All designs and specifications subject to change without notice
BCL 13-50 October 2011
OPTIONAL ACOUSTIC ENCLOSURE
Midi Canopy M1
The optional acoustic enclosure for this model is the Midi 1 Canopy, suitable for operation in harsh outdoor environmments whilst providing excellent security and acoustic performance. All steel canopy components are pre-treated and polyester powder coated (to a typical thickness of 70-80μm) in RAL9001 white and the baseframe is finished in RAL9005 black. Acoustically, the canopy is designed to meet the requirements of EU Legislation 2000/14/EC, achieved by extensive use of fire-retardant polyurethane foam together with efficient management of cooling air. Exhaust noise is minimised by internally mounted high performance exhaust silencers. A compact fuel tank moulded in tough polypropylene, with visual level indication, is mounted within the baseframe.
Other key features include : -
Gull-wing doors with gas struts for good service access Panel viewing window in main door Heavy duty locks on all doors for total security Weather cap on exhaust discharge Emergency Stop button relocated to canopy exterior Lifting and holding down points Fork Lift pockets Single roof lifting point.
Dimensions (mm) L
x
1810 x
W
950
x
H
x 1120
Additional Weight (kg) [
Typical Sound Pressure Level at 75% of Prime Power
Fuel Tank Capacity (Litres)
dB(A) at 1m
dB(A) at 7m
Integral
Bunded
Single Point Lift
73
63
52
-
Standard
125
[ Indicative weight of canopy additional to open set Typical SPL is a mean level, measured in free field conditions, with no contributory background noise.
KEY MECHANICAL OPTIONS (Open Set) Engine & Cooling :
Fuel System :
- Electronic governor - Oil and coolants drains extended to edge of baseframe - Coolant heater
- Low fuel level switch (single point) - Fuel level switch (four point)
Alternator : - Anti-condensation heater - Quadrature droop kit - Alternative AVR Please refer to Broadcrown Sales Department for full details of these and other options
All designs and specifications subject to change without notice