Generated by COMcheck-Web Software
Envelope Compliance Certificate 2006 IECC Section 1: Project Information Project Type: New Construction Project Title : University of Kentucky Funkhouser Bldg. 105 Renovation Construction Site:
Owner/Agent:
Lexington, Kentucky 40506
Designer/Contractor:
Katie Bluhm University of Kentucky Lexington, Kentucky 40506
Katie Bluhm Lexington, Kentucky 40506
[email protected]
Section 2: General Information Building Location (for weather data): Climate Zone: Heating Degree Days (base 65 degrees F): Cooling Degree Days (base 50 degrees F):
Lexington-Fayette, Kentucky 4a 4783 3754
Activity Type(s) School/University
Floor Area 1400
Section 3: Requirements Checklist Envelope TBD: No envelope assemblies specified
Climate-Specific Requirements: Component Name/Description
Gross Area Cavity or Perimeter R-Value
Cont. R-Value
Proposed U-Factor
Budget U-Factor
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
Air Leakage, Component Certification, and Vapor Retarder Requirements:
❑
1. All joints and penetrations are caulked, gasketed or covered with a moisture vapor-permeable wrapping material installed in accordance with the manufacturer's installation instructions.
❑ ❑ ❑
2. Windows, doors, and skylights certified as meeting leakage requirements.
❑ ❑
5. No roof insulation is installed on a suspended ceiling with removable ceiling panels.
❑ ❑
7. Cargo doors and loading dock doors are weather sealed.
❑
9. Building entrance doors have a vestibule equipped with closing devices. Exceptions:
3. Component R-values & U-factors labeled as certified. 4. Insulation installed according to manufacturer's instructions, in substantial contact with the surface being insulated, and in a manner that achieves the rated R-value without compressing the insulation. 6. Stair, elevator shaft vents, and other outdoor air intake and exhaust openings in the building envelope are equipped with motorized dampers. 8. Recessed lighting fixtures are: (i) Type IC rated and sealed or gasketed; or (ii) installed inside an appropriate air-tight assembly with a 0.5 inch clearance from combustible materials and with 3 inches clearance from insulation material.
Building entrances with revolving doors. Doors that open directly from a space less than 3000 sq. ft. in area.
❑
10.Vapor retarder installed.
Project Title: University of Kentucky Funkhouser Bldg. 105 Renovation Data filename:
Report date: 10/05/09 Page 1 of 7
Generated by COMcheck-Web Software
Interior Lighting Compliance Certificate 2006 IECC Section 1: Project Information Project Type: New Construction Project Title : University of Kentucky Funkhouser Bldg. 105 Renovation Construction Site:
Owner/Agent:
Lexington, Kentucky 40506
Designer/Contractor:
Katie Bluhm University of Kentucky Lexington, Kentucky 40506
Katie Bluhm Lexington, Kentucky 40506
[email protected]
Section 2: General Information Building Use Description by:
Activity Type
Activity Type(s) School/University
Floor Area 1400
Section 3: Requirements Checklist Interior Lighting:
❑
1. Total proposed watts must be less than or equal to total allowed watts. Allowed Watts 1680
Proposed Watts 1272
Complies YES
Controls, Switching, and Wiring:
❑
2. Independent controls for each space (switch/occupancy sensor). Exceptions: Areas designated as security or emergency areas that must be continuously illuminated.
❑ ❑ ❑
Lighting in stairways or corridors that are elements of the means of egress. 3. Master switch at entry to hotel/motel guest room. 4. Individual dwelling units separately metered. 5. Each space provided with a manual control to provide uniform light reduction by at least 50%. Exceptions: Only one luminaire in space; An occupant-sensing device controls the area; The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
❑
Areas that use less than 0.6 Watts/sq.ft. 6. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft. Exceptions:
❑
Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security. 7. Photocell/astronomical time switch on exterior lights. Exceptions:
❑
Lighting intended for 24 hour use. 8. Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts). Exceptions: Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 4: Compliance Statement
Project Title: University of Kentucky Funkhouser Bldg. 105 Renovation Data filename:
Report date: 10/05/09 Page 2 of 7
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2006 IECC requirements in COMcheck-Web and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title
Signature
Project Title: University of Kentucky Funkhouser Bldg. 105 Renovation Data filename:
Date
Report date: 10/05/09 Page 3 of 7
Generated by COMcheck-Web Software
Interior Lighting Application Worksheet 2006 IECC Section 1: Allowed Lighting Power Calculation A Area Category School/University
B Floor Area (ft2)
C Allowed Watts / ft2
1400
D Allowed Watts (B x C)
1.2
1680
Total Allowed Watts =
1680
Section 2: Proposed Lighting Power Calculation A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast School/University (1400 sq.ft.) Linear Fluorescent: A: Parabolic Louver / 48in. T8 32W / Electronic
B C D Lamps/ # of Fixture Fixture Fixtures Watt. 3
12
106
E (C X D)
1272
Total Proposed Watts =
1272
Section 3: Compliance Calculation If the Total Allowed Watts minus the Total Proposed Watts is greater than or equal to zero, the building complies. Total Allowed Watts = Total Proposed Watts = Project Compliance =
1680 1272 408
Interior Lighting PASSES: Design 24% better than code.
Project Title: University of Kentucky Funkhouser Bldg. 105 Renovation Data filename:
Report date: 10/05/09 Page 4 of 7
Generated by COMcheck-Web Software
Exterior Lighting Compliance Certificate 2006 IECC Section 1: Project Information Project Type: New Construction Project Title : University of Kentucky Funkhouser Bldg. 105 Renovation Construction Site: Lexington, Kentucky 40506
Owner/Agent:
Designer/Contractor:
Katie Bluhm University of Kentucky Lexington, Kentucky 40506
Katie Bluhm Lexington, Kentucky 40506
[email protected]
Section 2: Exterior Lighting Area/Surface Power Calculation A Exterior Area/Surface
B Quantity
C Allowed Watts / Unit
D Tradable Wattage
E F Allowed Proposed Watts Watts (C x D)
Total Tradable Watts* = 0 0 Total Allowed Watts = 0 Total Allowed Supplemental Watts** = 0 * Wattage tradeoffs are only allowed between tradable areas/surfaces. ** A supplemental allowance equal to 5% of total allowed wattage may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B C D Lamps/ # of Fixture Fixture Fixtures Watt.
E (C X D)
Total Tradable Proposed Watts =
0
Section 4: Requirements Checklist Lighting Wattage:
❑
1. Within each non-tradable area/surface, total proposed watts must be less than or equal to total allowed watts. Across all tradable areas/surfaces, total proposed watts must be less than or equal to total allowed watts. Compliance: No exterior fixtures are defined.
Controls, Switching, and Wiring:
❑ ❑
2. All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting. 3. All lighting fixtures are controlled by a photosensor or astronomical time switch that is capable of automatically turning off the fixture when sufficient daylight is available or the lighting is not required. Exceptions: Covered vehicle entrance/exit areas requiring lighting for safety, security and eye adaptation.
Exterior Lighting Efficacy:
❑
4. All exterior building grounds luminaires that operate at greater than 100W have minimum efficacy of 60 lumen/watt. Exceptions: Controlled by motion sensor or exempt from consideration under the provisions of Section 505.6.2.
Exterior Lighting TBD: No exterior lighting fixtures specified
Project Title: University of Kentucky Funkhouser Bldg. 105 Renovation Data filename:
Report date: 10/05/09 Page 5 of 7
Generated by COMcheck-Web Software
Mechanical Compliance Certificate 2006 IECC Section 1: Project Information Project Type: New Construction Project Title : University of Kentucky Funkhouser Bldg. 105 Renovation Construction Site: Lexington, Kentucky 40506
Owner/Agent: Katie Bluhm University of Kentucky Lexington, Kentucky 40506
Designer/Contractor: Katie Bluhm Lexington, Kentucky 40506
[email protected]
Section 2: General Information Building Location (for weather data): Climate Zone: Heating Degree Days (base 65 degrees F): Cooling Degree Days (base 50 degrees F):
Lexington-Fayette, Kentucky 4a 4783 3754
Section 3: Mechanical Systems List Quantity System Type & Description
Section 4: Requirements Checklist
Project Title: University of Kentucky Funkhouser Bldg. 105 Renovation Data filename:
Report date: 10/05/09 Page 6 of 7
Generated by COMcheck-Web Software
Mechanical Requirements Description 2006 IECC
Project Title: University of Kentucky Funkhouser Bldg. 105 Renovation Data filename:
Report date: 10/05/09 Page 7 of 7