MEASUREMENT OF GROUNDING RESISTANCE IN TOWER LINES Favio Casas Ospina Electrical Engineer Seguridad Eléctrica

Alejandro Vargas Avila Electrical Engineer

Abstract – This article exposes the methodologies for the resistance measurements of grounding systems in transmission lines, it summarizes the implemented procedures, describes the earth tester used and exposes a statistical analysis of results in the measurements of more than three thousand towers of high voltage.

1 - INTRODUCTION A project of earth resistance measurement was led in 3025 towers of transmission, with voltages of 115 kV to 2500 m.o.s.l. (meter over sea level), as part of a maintenance program, it was necessary to determine the percentage of towers that were above 30 ohms (Design value), and to look for a correlation with the towers with more lightning activity.

Gloria Maria Acero Electrical Engineer ICONTEC

observer. Although not all the measurements systems are the same, some qualities can be named, that can affect the development of the measurement system. Such qualities can be systemic as the environmental effects, the error is the uncertainty and that they can be static as the calibration. 3 - STANDARDS The guide IEEE 81 - 1983 in their numeral 12,6 suggests that the transmission lines measurement should be implemented with a high - frequency ground resistance meter, which operates to 25 kHz 4 - MEASUREMENT METHODS A

The measurement system, the necessary personnel and the earth tester were determined keeping in mind: • • • • • •

The scarce documentation and standards about the topic. Condition physical - environmental unfavorable. Instruments not well employed or without the appropriate characteristics for this kind of measurements. Parallel connections among grounding systems due to overhead ground wire. Bad implementation of the different ground resistance measurement techniques. Uncertainty in obtained data.

With the previous aspects tests were carried out, these tests determined that field measurements should be made under the following conditions:

G I E V

S

RE

RS

H

RH

B A Ov erhead ground B i - frequency V High G i I Measuring H t S E Tow er difussion RPE b i t difussion R S probe it earth rod diffusion R H Auxiliary i t

Remote th Hig-frequency t Auxiliary earth d Tow er ti

Fig. 1

• • • • •

With one or two overhead ground wire connected or disconnected. With energized or de-energized lines. With earth testers with frequencies from 111Hz to 25 kHz in order to compare their results and possible coincidences. To implement the recommendations given by the guide IEEE - 81 of 1983 in relation with the earth tester and measurement method. To implement earth testers with different techniques and methodologies of application.

2 - SYSTEM OF MEASUREMENT In a simple way, the objective of a measurement system is to present a qualitative or quantitative result of a measured variable. However, in a specific relation with the numbers, the measured value is not specifically similar to the true value, this in reason of all the elements that involves a measurement system. A measurement system is conformed basically by four elements: the object to measure, the measurement earth tester, the measurement method and finally the

The fig. 1 shows the method suggested by the IEEE 81 1983 with a high frequency ground resistance meter (25 kHz) and the application of the rule of 61,8%. This method requires two auxiliary electrodes that have to be placed and buried at 90º of the overhead wires. This recommendation is given in order to avoid a coupling with the grounding system under test. The earth tester injects current in one of the electrodes, it is considered as "current electrode", that electrode is placed far from the grounding system, the intermediate electrode is placed at 61.8% of the distance between the grounding system and the current electrode, this electrode measures the potential elevation and its named "probe electrode". The precision is given by the non interaction of both electrodes (guaranteed using a far earth) and the place of the intermediate electrode in the valley of the curve, the number of measures (minimum three) and the characteristics of the earth tester. Other measurements were made with a low frequency earth tester, using the fall-of-potential method and with the overhead earth wires connected or disconnected.

An alternating measurement method, suggested by LEM, was rehearsed and it is denominated "Selective". For its application the fall-of-potential method should be implemented with the application of the rule of 61,8% and the utilization of a clamp-on current transformer for the measurement of the current in each one of the four legs of the tower. The total resistance of an individual tower is the parallel sum of all grounds resistance values. 5 - PREVIOUS REHEARSALS In the measurements group was necessary to carry out activities to ensure and trust the observers, earth testers and measurements methods. The results of the measurements and the realization conditions are presented: Date Dispositive Voltage Frequency (Hz) 1470 160 800 111

Date Dispositive Voltage Frequency (Hz)

1470

111

111

Method

Characteristics

Fall of potential Fall of potential Fall of potential Fall of potential

Without overhead ground wire Without overhead ground wire Without overhead ground wire Without overhead ground wire

No. of Measu. 1 1 1 1

Place of current electrode (m)

Resistance (Ω )

100

324.00

100

330.00

100

340.00

100

343.00

Characteristics

No. of Measu.

With overhead ground wire Rule of 61,8% Without overhead ground wire With overhead ground Rule of wire 61,8% Without overhead ground wire With overhead ground wire Selective Without overhead ground wire

1 2 1 2 1 2

Place of current electrode (m)

Resistance (Ω )

100

2.52

100

7.80

100

1.43

100

7.90

100

13.00

100

8.10

Date: 07.02.00 Dispositive: Tower 100 Voltage 230 kV Method

25000

Rule of 61,8%

1470

111

111

Rule of 61,8%

Rule of 61,8%

Rule of 61,8%

1470 25000 111 111 111

• •



No. of Measu.

1 overhead ground wire

1

Without overhead ground wire

2

1 overhead ground wire

1

Without overhead ground wire

2

1 overhead ground wire

1

Place of current electrode (m)

Resistance (Ω)

100

5,70

100

6,00

100

1,50

100

7,30

100

0,88

100

7,50

Without overhead ground wire

2

1 overhead ground wire

1

100

8,20

Without overhead ground wire

2

100

7,80

No. of Measu.

Place of current electrode (m)

Resistance (Ω)

100

11,39

100

27,00

100

9,93

Method

Characteristics

Fall of potential Fall of potential Fall of potential Fall of potential Fall of potential

1 overhead ground wire 1 overhead ground wire 2 overhead ground wire Without overhead ground wire Without overhead ground wire

1 1 1 1 1

100

34,50

150

32,60

From the analysis of the results without overhead ground wire and with a frequency of 111 Hz, and combining the

To use the high frequency-meter (25 kHz), in measurements with overhead ground wire connected. To use low-frequency meters (111 Hz or 1470 Hz) with the overhead ground wire disconnected Not to use the low-frequency meter specifically of 800 Hz, in this kind of measurements. To implement the fall-of-potential method with the application of the rule of 61,8% as measurement method.

Keeping in mind that when measurements of this kind are carried out not only the obtained data is important, but it is necessary to mention that the personnel's security is also important. Among all the security recommendations, for this kind of case is important to remark that: •

Characteristics

Date: 23.02.00 Dispositive: Tower 105 Voltage 230 kV Frequency (Hz)

Based on the previous data, it was determined:



31.01.00 Tower100 230 kV

Frequency (Hz)

In the case of the tower 100, with overhead ground wire, to 111 Hz and combining the results of the 2 rehearsal methods, it gives a value of half 5.88 ohms, but a deviation of 5,02 that shows the great dispersion of the results, so the methods for this case are not comparable. When they are analysed individually its found that with the rule of 61.8% the half result is 1.1, the deviation is 0,2 and for the "selective" method 10,6 and deviation of 2,4. Keeping in mind that with the rule of 61.8% the deviation is lower, this method is the most reliable.

6 - IMPLEMENTED METHODOLOGIES

05.08.99 Tower 14 115 kV

Method

results for the two rehearsal methods we obtained a standard deviation, this indicates that the dispersion among the values is small and therefore the half value can be accepted with a high grade of trust from the statistical point of view, and also the data of high frequency tester is 20% lower.

• • •

• • •

Before proceeding to the resistance measurement, its necessary the measurement of the voltage originated by spurious currents. If that voltage overcomes the 25 volts, do not practice any measure and determine the origin of the problem. Field measurements should not be scheduled during periods of storms or lightning activity. Connections or disconnections of transmission lines during a period of electric storms should not be done. In the event that an electric storm suddenly appears on the tested area, work must be stopped, disconnecting all connections among the measurement earth testers and the tested ground, isolating temporarily the connectors. Any bridge or continuity between the body between and the measurement earth tester or among the measurement implements must be avoided. The cable rolls that are used during the measurement are isolated or at least mounted on a clean or insulating platform. The grounding systems must be connected (determine in case of fall) to every metallic frame of the earth testers.

7 - RESULTS

to a measurement with a low frequency earth tester with the overhead ground wires disconnected and be carried out by two people, while with low frequency earth tester frequency 6 people are necessary.

1 ,3 3 % 7 ,8 4 %

5 ,3 2 %

R <1

7 ,9 1 %

1
10
2 2 ,4 1 %

100
2 3 ,5 3 %

Fig. 2. 1428 Towers measured with earth tester of 111 Hz

1 ,8 8 % 1 5 ,4 0 %

8 ,0 2 %

9.7 - All measurements will be in perpendicular way to the line. 9.8 - The results of the project showed that due to the training of the people and the clarification of the all procedure, the percentage of accidents and loss of information was 0%. 9.9 – with the expressed reference to the measurement of grounding systems, the calibration presents the difficulty of emulating the real conditions of operation easily so that the variables can be really analyzed.

0 ,5 6 % 4 ,7 0 %

9.5 - The measurements with low frequency tester will be with the over head ground wire disconnected.

R <1 1
4 0 ,5 1 %

Fig. 3. 1597 Towers measured with high-frequency earth tester (25 kHz)

9.10 - In these cases, an alternative option can be the realization of a repetitive analysis that would allow to trust in the earth tester, however, earth resistance measurements are influenced by environmental changes, mainly in the moisture of the land, so that an analysis should be executed under very planned conditions in order to consider the test as applicable. 10 - REFERENCES • •

45%

25000 Hz 111 Hz

40%

• •

35% 30%

• • •

25% 20% 15%

Casas, Favio. Tierras soporte de la seguridad eléctrica. 1988. Segelectrica IEEE 81 – 1983. Guide for measuring earth resistivity, ground impedance, and earth surface potentials of a ground system. ABB, HW2A, Earth resistance measuring instrument. Vargas, Avila Alejandro. Manual de técnicas en medición de sistemas de puesta a tierra. 2000. Transmission line grounding reference book. EPRI. 1980 LEM, Electrical grounding techniques. 1998. www.lem.com

10% 5%

Authors:

0% R<1

1
5


Fig. 4. Comparison between both earth testers •

9 - CONCLUSIONS 9.1 - 168 (5%) of the 3025 transmission towers measured, need a corrective maintenance of their grounding system. Only 60 (2%) of towers need an urgent maintenance keeping in mind the high incidence of lightning. 9.2 - The sample measured was of 100% of the towers, its considered that the results are 100% reliable. 9.3 - All the activities were made in order to trust in the earth tester and the method of measurement, however and being strict, the results do not correspond with a calibration and a properly uncertainty analysis. 9.4 - Measurements with a high frequency tester gives 20% lower than the other measurements, its equivalent

Eng.

Favio

Casas

Ospina,

e-mail:

[email protected] Eng.

Alejandro

Vargas

Avila,

e-mail:

[email protected]

Eng. Gloria Maria Acero, e-mail: [email protected]

measurement of grounding resistance in tower lines - Elistas

Guide for measuring earth resistivity, ground impedance, and earth surface potentials of a ground system. •. ABB, HW2A, Earth resistance measuring instrument.

71KB Sizes 0 Downloads 170 Views

Recommend Documents

The measurement of lactate threshold in resistance exercise - cefema
Resistance incremental tests (IT) make it possible to determine critical metabolic and cardiovascular changes, such as the lactate threshold (LT). Different methods are frequently used to improve the exactness of LT identification. The objective of t

In situ resistance measurement of the p-type contact in ...
Feb 18, 2005 - tionally, minority electrons from vertical current leakage may influence the total resistivity in a real diode laser. 9. Hence, conventional methods ...

Grounding stress in expiratory activity
folds appear to lack the essential biomechanical properties that would permit modulation of… intensity using adult-like strategies.' So to increase the loudness of ...

Grounding language in action
using abstract, amodal, and arbitrary symbols (i.e., words) combined by syntactic rules (e.g., Burgess & Lund, 1997;. Chomsky, 1980 ... meaningful to an animal.

Grounding of Textual Phrases in Images by ...
or phrases, they typically do not provide the spatial local- ization of the phrases. Consequently, being able to learn from this data without grounding supervision ...

Resistance of double haploid rice lines to brown plant ...
iron trays filled with water after germination of seedlings. Seven days after sowing, seedlings were infested with first instar nymphs @ 10-. 15 per seedling. After insect release the seed box was covered with mosquito net wire mesh cage. The lines w

The symbol-grounding problem in numerical cognition A review of ...
The symbol-grounding problem in numerical cognition A review of theory evidence and outstanding questions.pdf. The symbol-grounding problem in numerical ...

Grounding and Supplementation
Jun 28, 2015 - It is typically understood to require, among other things, that the facts .... Since grounding is not reflexive, the definition of groverlap must be ...

Rightful Resistance in Rural China.pdf
structure which village activists can exploit in resisting the mis-implementation of central policies by. cadres at the local level. In other words, since state power is ...

improvements in impact resistance property of metal ...
This paper covers impact testing of ABS and Nylon6 thermoplastics under three different conditions ... to resist the fracture under stress applied at high speed [1].

The Influence of Trial in Consumer Resistance to Switching from ...
The Influence of Trial in Consumer Resistance to Switching from ATM to Internet.pdf. The Influence of Trial in Consumer Resistance to Switching from ATM to ...

Coercion Resistance in Authentication Responsibility ...
with two laptop computers for Alice and Harry to use. Al- though Harry was .... The system is trained with 10 out of 26 SC samples (ran- domly chosen with a ...

improvements in impact resistance property of metal ...
The Automotive, Aerospace ... 1JNTU College of Engineering, Anantapur, AP ... 3Department of Mechanical Engineering,JNTU College of Engineering, ...

In re Sea Star Lines - notice of settlement.pdf
Deborah Roberts as Personal Representative of the Estate of Michael. Lee Holland has reached a full and final settlement of all claims filed in this action (Docket. No.249) in the amount of FIVE HUNDRED THOUSAND DOLLARS ($500,000.00) for all. non-pec

What Is the Well-Foundedness of Grounding?1,2
Nov 28, 2014 - In effect, this story leaves open the explanatory task of telling us how the instantiation of F by a ... have its source in, or acquire its being from, the non-derivative. ..... This principle is attractive because it is a straightforw

Simultaneous measurement of in-plane and out-of ...
wrapping or differentiation operations. The method relies on multidirectional illumination of the object with lasers of different wavelengths and digital recording of holograms using a three CCD sensor camera, i.e., three-color CCD with red, green, a

Language grounding in robots for natural Human
using the teaching protocol. Conclusions. - We have developed a physically embodied robot with language grounding capabilities. - During the course of the research several online, incremental and open-ended learning architectures with many innovation

Measurement of Small Variations in Optical Properties ...
in Optical Properties of Turbid Inclusions ... Special optical system for non-invasive determination of small variations in the optical properties of homoge- .... water. Fig. 3. Total scattered optical power as a function of the relative Intralipid c

Measurement of Temperature and Reaction Species in ...
Cathode Diffusion Layer of a Free-Convection Fuel Cell. Tibor Fabian,a,z ... monitor spatial and temporal distributions of temperature and spe- cies within an .... reflects light in a narrow bandwidth determined by the total length of the grating ...