Model UC625 (P874) IEEE C37.90.1

RTK EMC TEST REPORT PRODUCT CHARACTERISTICS AND PERFORMANCE DURING THE APPLICATION OF SURGE WITHSTAND CAPABILITY (SWC) FOR PROTECTIVE RELAYS AND RELAY SYSTEMS BASED ON IEEE C37.90.1

PRODUCT

Model UC625 (P874) Alarm System

COMPILED BY

Tim McLeman

SIGNED

DATE

10th June 2009

EMC Test Report P874-IEEE C37.90.1 Page 1 of 9

Model UC625 (P874) IEEE C37.90.1

EFT TEST RESULTS AND REPORT Product

Model UC625 (P874)

Tested by

Tester 3

S/No N/A

Date 10th June 2009

This report details the results of the tests performed on the above product. It serves as evidence towards the demonstration of compliance with the standard. The results shown in this report represent the levels and types of disturbance to the function of this product likely to be observed if this product is subjected to a similar stimulus in its intended operating environment. The tests were conducted in accordance with the RTK Test Procedure for Surge Withstand Capability (SWC). The results and figures given show the typical disturbance observed during the tests. TEST SET-UP Several typical samples of the product were stimulated during the tests using the UC625 (P874) Functional Test Specification/Procedure. The test severity levels and performance criteria used are those defined in the standard for surge withstand capability (SWC) IEEE C37.90.1-1989. The following ports were tested: 1. Alarm ports set to normally open and normally closed. 2. Relay ports set to normally open. 3. Power ports. The following climatic conditions were observed: Temperature 20°C

Relative Humidity 49%

Test Equipment for surge withstand capability test Item

Manufacturer

Type

Serial No.

Next Cal. Due

Surge generator Capacitive Coupler Digital Multimeter Oscilloscope Power Supply

Schaffner RTK Hewlett Packard Tektronix Thurlby Thandar

NG505AC CC100NF 34401A TDS2022 Pl320QMD

23 CCN1 62 C01008 175339

14th April 2003 Not required th 04 July 2002 12th July 2002 Not Required

EMC Test Report P874-IEEE C37.90.1 Page 2 of 9

Model UC625 (P874) IEEE C37.90.1 TEST RESULTS Alarm ports – Oscillatory waveform - Common Mode Test Voltage: 2.5 to 3KV, Repetition rate: 50/sec, Duration 2sec, Source impedance 150 to 200 Ohms Observations No effect was observed during or after the test. Alarm ports – Oscillatory waveform - Transverse Mode Test Voltage: 2.5 to 3KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 150 to 200 Ohms Observations No effect was observed during or after the test. Alarm ports – Fast Transient waveform - Common Mode Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration 2sec, Source impedance: 80 Ohms or less, polarity: +ve Observations Momentary flicker on some display LED’s. No other effects were observed during or after the test. Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration 2sec, Source impedance: 80 Ohms or less, polarity: -ve Observations Momentary flicker on some display LED’s. No other effects were observed during or after the test. Alarm ports – Fast Transient waveform -Transverse Mode Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 80 Ohms or less, Polarity: +ve Observations No effect was observed during or after the test. Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 80 Ohms or less, Polarity: -ve Observations No effect was observed during or after the test.

EMC Test Report P874-IEEE C37.90.1 Page 3 of 9

Model UC625 (P874) IEEE C37.90.1

Relay ports – Oscillatory waveform - Common Mode Test Voltage: 2.5 to 3KV, Repetition rate: 50/sec, Duration 2sec, Source impedance 150 to 200 Ohms Observations No effect was observed during or after the test. Relay ports – Oscillatory waveform - Transverse Mode Test Voltage: 2.5 to 3KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 150 to 200 Ohms Observations No effect was observed during or after the test. Relay ports – Fast Transient waveform - Common Mode Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration 2sec, Source impedance: 80 Ohms or less, polarity: +ve Observations No effect was observed during or after the test. Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration 2sec, Source impedance: 80 Ohms or less, polarity: -ve Observations No effect was observed during or after the test. Relay ports – Fast Transient waveform -Transverse Mode Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 80 Ohms or less, Polarity: +ve Observations No effect was observed during or after the test. Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 80 Ohms or less, Polarity: -ve Observations Momentary flicker on some display LED’s. No other effects were observed during or after the test. Power ports – Oscillatory waveform - Common Mode EMC Test Report P874-IEEE C37.90.1 Page 4 of 9

Model UC625 (P874) IEEE C37.90.1 Test Voltage: 2.5 to 3KV, Repetition rate: 50/sec, Duration 2sec, Source impedance 150 to 200 Ohms Observations No effect was observed during or after the test. Power ports – Oscillatory waveform - Transverse Mode Test Voltage: 2.5 to 3KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 150 to 200 Ohms Observations No effect was observed during or after the test. Power ports – Fast Transient waveform - Common Mode Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration 2sec, Source impedance: 80 Ohms or less, polarity: +ve Observations No effect was observed during or after the test. Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration 2sec, Source impedance: 80 Ohms or less, polarity: -ve Observations No effect was observed during or after the test. Power ports – Fast Transient waveform -Transverse Mode Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 80 Ohms or less, Polarity: +ve Observations No effect was observed during or after the test. Test Voltage: 4 to 5KV, Repetition rate: 50/sec, Duration: 2sec, Source impedance: 80 Ohms or less, Polarity: -ve Observations No effect was observed during or after the test. Comments No erroneous was present, no component failure occurred, and there was no change in calibration. PASS

EMC Test Report P874-IEEE C37.90.1 Page 5 of 9

Model UC625 (P874) IEEE C37.90.1

TEST PROCEDURE SURGE WITHSTAND CAPABILITY (SWC) FOR PROTECTIVE RELAYS AND RELAY SYSTEMS

Revision 0

01/01/2001

(1) Object This document outlines the test requirements and procedure for carrying out and documenting surge withstand capability (SWC) tests for the purpose of testing for compliance of our products with the IEEE standard C37.90.1-1989. For reasons of clarity, the product to be tested will be referred to as the "EUT" (Equipment Under Test) and "AE" as Auxiliary Equipment and "PSU" as power supply unit. (2) Reference Documents Generic Standard = IEEE C37.90-1989 Basic Standard = IEEE C37.90.1-1989 (3) Test Conditions Ambient Temperature = -20°C to 55°C measured 30cm from enclosure Relative Humidity = Outside enclosure < 55% non condensing at temp of <40deg C = Inside enclosure < 95% for 96 hr non condensing (4) Set-up Procedure for Monitoring EUT (4.1) Stimulation and Monitoring of the EUT Operation and performance of the EUT must be monitored during testing. This will be achieved by operating the module in a manner designed to exercise all functions. The test may be based upon the set-up described in the Functional Test Specification/Procedure for the EUT, as used by the test department. (4.2) Table Top Set-up Place the EUT on a 100mm stand off box at the position marked EUT and connect the primary earth point to the table top ground plane using the earth strap provided. Place the power supply on a 100mm stand off box at the position marked PSU and EMC Test Report P874-IEEE C37.90.1 Page 6 of 9

Model UC625 (P874) IEEE C37.90.1 connect the earth strap provided. Connect the PSU to the EUT with a cable length of no greater than 1 metre. Place the test generator on a 100mm stand off box at the position marked TG and connect the earth strap provided. Connect the capacitive coupler 100nF/1000V. (4.3) EUT Set-up during Surge Testing During the Surge tests, the EUT must be powered and stimulated in a mode representative of normal operation in the field. For P874 Alarm cards, this would mean the application of an input signal compatible with the input requirements. The EUT should also be tested in its most vulnerable mode, and care should be taken to ensure the most sensitive input range is tested, and also that any product with a wide-ranging specification should be tested at the sensitive part of its specification. Typically the inputs could be normally open or closed. (4.4) Monitoring EUT Behaviour during Surge Testing Any variation to the output ports of the EUT during surge testing must be recorded. This can be achieved for both display and relay ports by visually monitoring attached LED’s. However the comms is somewhat more difficult and requires the connection of a computer running a test comms program. (5) Applying Tests Refer to IEEE C37.90.1 for examples of test set-ups and background information. (5.1) Before Commencing Tests Read the operating instructions for the surge generator, especially sections relating to safety when using high voltage test-gear. The surge generator must be checked for correct operation prior to conducting the tests. THE STANDARD STATES THAT THE TEST RESULT IS A PASS WHEN NO ERRONEOUS OUTPUT IS PRESENT, NO COMPONENT FAILURE OCCURRS, AND THERE IS NO CHANGE IN CALIBRATION EXCEEDING NORMAL TOLERANCES. (5.2) Alarm ports – Common Mode – Oscillatory and Fast transient The test is applied between an alarm port and the local ground plane via the Capacitive Coupler typically 100nF/1000V, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the capacitive coupler before proceeding with any tests. (5.2.1) Run the test with the Surge generator set for Oscillatory mode and carefully monitor the EUT for any disturbance. Note the level of the disturbance for inclusion in the report. When the test has finished, check for correct operation of the EUT and that no configuration change or loss of function has occurred. (5.2.2) Repeat (5.2.1) above for all alarm ports and states.

EMC Test Report P874-IEEE C37.90.1 Page 7 of 9

Model UC625 (P874) IEEE C37.90.1 (5.2.3) Repeat (5.2.1) and (5.2.2) above with Surge generator set for Fast Transient mode. (5.3) Relay ports - Common mode – Oscillatory and Fast transient The test is applied between a relay port and the local ground plane via the Capacitive coupler typically 100nF/1000V, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the Capacitive coupler before proceeding with any tests. Repeat the procedure (5.2) above for all relay ports and states. (5.4) Display ports - Common mode – Oscillatory and Fast transient The test is applied between a display port and the local ground plane via the Capacitive Coupler typically 100nF/1000V, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the capacitive coupler before proceeding with any tests. Repeat the procedure (5.2) above for all display ports and states. (5.5) Power ports - Common mode The test is applied between a power port and the local ground plane via the Capacitive Coupler typically 100nF/1000V, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the capacitive coupler before proceeding with any tests. Repeat the procedure (5.2) above for all power ports and states. (5.6) Alarm ports – Transverse mode – Oscillatory and Fast transient The test is applied between two alarm inputs connected together via the capacitive coupler typically 100nF/1000V and the test generator, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the capacitive coupler before proceeding with any tests. (5.6.1) Run the test with the surge generator set for Oscillatory mode, and carefully monitor the EUT for any disturbance. Note the level of the disturbance for inclusion in the report. When the test has finished, check for correct operation of the EUT and that no configuration change or loss of function has occurred. (5.6.2) Repeat (5.6.1) above for all alarm port combinations and states and both polarities. (5.6.3) Repeat (5.6.1) and (5.6.2) above with Surge generator set for Fast Transient mode. (5.7) Relay ports – Transverse mode – Oscillatory and Fast transient The test is applied between two different relay ports connected together via the capacitive coupler typically 100nF/1000V and the test generator, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the capacitive coupler before proceeding with any tests. Repeat (5.6) above for all relay ports and states. 5.8) Display ports – Transverse mode – Oscillatory and Fast transient EMC Test Report P874-IEEE C37.90.1 Page 8 of 9

Model UC625 (P874) IEEE C37.90.1 The test is applied between two different relay ports connected together via the capacitive coupler typically 100nF/1000V and the test generator, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the capacitive coupler before proceeding with any tests. Repeat (5.6) above for all display ports and states. 5.9) Power ports – Transverse mode – Oscillatory and Fast transient The test is applied between two different power ports connected together via the capacitive coupler typically 100nF/1000V and the test generator, all port wires not being tested should be kept as far away as possible. Ensure that the plastic cover is always placed over the capacitive coupler before proceeding with any tests. Repeat (5.6) above for all power ports. (6) The Test Report A report must be compiled after the tests have been completed. This report must be filed along with other reports detailing the EMC characteristics. It is essential that the report is accurate and complete. (6.1) The Title Page The report will be titled: RTK EMC TEST REPORT PRODUCT CHARACTERISTICS AND PERFORMANCE DURING THE APPLICATION OF SURGE WITHSTAND CAPABILITY (SWC) FOR PROTECTIVE RELAYS AND RELAY SYSTEMS BASED ON (IEEE C37.90.1) The title page must include the following information: a) Product catalogue number b) Date of test c) Name of Engineer d) Signature of Engineer (6.2) Content of the report The main body of the report will consist of the following: a) The ambient temperature and humidity b) Magnitude of disturbance observed during application to the EUT input ports. c) Magnitude of disturbance observed during application to the EUT output ports d) Magnitude of disturbance observed during application to the EUT power ports e) Details of any observations made during the tests EMC Test Report P874-IEEE C37.90.1 Page 9 of 9

Model UC625 (P874) IEEE C37.90.1 f) If applicable, a printout of the trace from the oscilloscope showing the maximum observed level of disturbance during tests g) If applicable, any deviations in the set-up from the functional test procedure h) A copy of this test procedure i) A list of all test equipment used including calibration due dates where applicable.

EMC Test Report P874-IEEE C37.90.1 Page 10 of 9

RTK UC625 Type Test.pdf

BASED ON. IEEE C37.90.1. PRODUCT Model UC625 (P874) Alarm System. COMPILED BY Tim McLeman. SIGNED. DATE 10th June 2009. Page 1 of 10 ...

99KB Sizes 3 Downloads 127 Views

Recommend Documents

S rtk etzs,1*: " Zof
Jun 20, 2016 - submitted by department following the template attached to this ... Email: [email protected] I Website: www.depeddasma.edu.ph.

RTK for Website 2016.pdf
BALLENTINE SUSAN OTHER $637.50. BALLENTINE KAYLA SUPPORT STAFF $9,524.27. BALLIRO ANGELINA OTHER $517.50. BALOGH LINDA OTHER $2,175.00. BALSER DIANE TEACHER $74,890.47. BARON MICHELLE TEACHER $39,670.47. BARRON JANNA SUPPORT STAFF $14,964.85. BARTLET

11 reserves ring type station type
OCELLUS. OUTPOST. 15 Lambda Aurigae. X. N. N. N. BD+49 1280. FEDERATION. DEMOCRACY. AGR/IND. Yimakuapa. X. Y. N. N. DINDA [15]. FEDERATION.

Practical Type Inference for the GADT Type System
Portland State University ... opportunity to develop my interests in computer science and to pursue graduate ..... 7.13 Type inference for reified state monad (1).

Granville - Production Type
Carraque Scones. Charming fast horse. Milton S. Hershey Candy .... Granville harbour hosts a small maritime emergency rescue team. The number of rocks and.

Nullable Type Inference - OCaml
Dec 11, 2002 - Imperative programming languages, such as C or Java deriva- tives, make abundant ... In languages using the ML type discipline, the option type type α option ..... //docs.hhvm.com/manual/en/hack.nullable.php. [3] Facebook ...

Practical Type Inference for the GADT Type System
opportunity to develop my interests in computer science and to pursue graduate ...... algebraic data types that I made in the course of this dissertation research. Here ..... APP This rule types a function application by typing the function (f) and i

struct tag-name { data-type member1; data-type ...
3. The tag name such as book_bank can be used to declare structure variables of its type .... static struct student s2,s3={“bbb”,”00CS002”,20,90,30}; s2=s1 ...

Name BP ACC Damage Type Attack Type Energy ...
A Pokémon with Solar Power receives a permanent +3 boost to its Special Attack as .... If the user moves after the target, the power of the user's next move is ...

Type I and Type II Fractional Brownian Motions
Benoit Mandelbrot (commodity and asset prices). Consider a stationary .... What matters, in the choice of linear representation, is how best to represent the joint distribution of the (finite) ... Frequency Domain Simulation: When ut is i.i.d. ...

BDE Type Taxonomy - GitHub
Dec 4, 2015 - bslmf::IsFundamental baltzo::Loader bslma::DeallocatorGuard bslma::DestructorProctor utility meta- function protocol bdlt::Date bslstl::StringRef.

E-Type
Subject: Design and Analysis of Algorithm. Assignment No : 1. E-Type. E.1.1. Define the following asymptotic notation: a)Big Oh b)Big Omega c)Theta d)Little Oh ...

Granville - Production Type
of Chausey, which includes a small harbour, .... carried out and extensions were made to the hippodrome, telephone lines were ..... of Production Systems SAS.

Nullable Type Inference - OCaml
Dec 11, 2002 - [1] Apple (2014): Swift, a new programming language for iOS and. OS X. Available at https://developer.apple.com/swift. [2] Facebook (2014): ...

Haemophilus type b conjugate vaccines
Nov 25, 2017 - 4.8 of the SmPC, with an unknown frequency. The package leaflet should be updated accordingly. The CMDh agrees with the scientific conclusions made by the PRAC. Grounds for the variation to the terms of the Marketing Authorisation(s).

Briggs Type Indicator
implemented in either a real hardware robot or a simulated software robot (sobot) ... It must also be able to interact with humans and its environment in real time. AnyRobot is designed to ...... The pie charts represent the percentages in which.

Moement type creation.pdf
Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. Moement type creation.pdf. Moement type creation.pdf. Open.

type title here
1Institute for Intelligent Systems 2Sandia National Labs. 3Department of ... tests of cognitive abilities, then multitasked in a flight simulator in which task difficulty.

Type Title Here - Neometals Ltd.
Jan 20, 2016 - offtake agreement with Mitsubishi Corporation and existing processing plant that reduces capex and time to first output. Additionally, due to previous mining conducted by Galaxy Resources (GXY), .... Our EV calculations using Total Min

type title here
general and domain-specific. Applied Implications and Future work. These findings provide novel information regarding the impact of emotion on multitasking.

UREA Perstrip UF Type II
Composition Materials Co., Inc. - 125 Old Gate Lane - Milford, CT 06460 ... RESPIRATORY PROTECTION: Recommend a 3M #8710 dust and mist respirator.

Probe-type deformers
Nov 12, 2014 - blended affine transformation Blend(wi, Ai) ∈ Aff+(3) which satisfies Blend(wi, Ai) = Ak for wi = ..... http://skaji.org/files/WEB-exponential.pdf.