CAM SWITCHES

Description CAM SWITCHES series NCS have been developed to the latest achievements in the field of switching devices through the application of high quality insulation material and contacts made from silver alloys. Their advantages are high making and breaking capacities, electrical and mechanical endurance and small dimensions. The rotary cam switches are intended for multiple switching operations in main circuit as well as in auxiliary circuits. NCS series is a rotary cam switches which have three current ratings: 20A, 25A and 32A. All ratings has the finger proof terminal. The series comply with IEC 60947-3, IEC 60947-5-1. NCS series mainly apply to 440 Vac and below voltage (240 Vac/50 Hz) as well as DC circuit. Typical applications are breaking and closing, change-over of circuit, selector switches (for example: Auto- Manual), control switch of switchgear and control gear, control switch of instruments.

Application The NCS series cam switches can be used for virtually all purposes which classified by utilization as the following:  Motor switches, they are designed for direct-online starting and stopping of single phase and three phase motors. They also come out as star-delta switches, reversing switches, pole-change over motor switches.  Selector switches and multi-step switches, e.g. Voltmeter selector switches, Ammeter selector switches and etc. for transformers and welding apparatuses.  Cut-Off switches or ON-OFF switches in auxiliary circuits, they are assembled in compliance with the switching programmer according to preference: switches for control, signaling and measuring circuits.  Control switches with spring return, pull to operate and etc.

CAM SWITCHES Cam switches can have 15 layers (30 contacts) in maximum. In principle all sizes and designs of cam switches can be arranged with four difference angles of rotation. Suitable to the application of stop mechanism with 90°, 60°, 45°, 30° at uniform distribution of a full circle, maximum 4, 6, 8 or 12 switch positions are possible. The switches can be used at the ambient temperature from -5°C to +60°C and storage temperature from -25°C to +80°C

Specification Description Rated insulation voltage Ui Rated thermal current Ith Rated operational current Ie AC – 21A, AC – 22A AC – 23A AC – 2 AC – 3 AC – 4 AC – 15 Power rating AC – 23A AC – 2 AC – 3 AC – 4 Rated Impulse Withstand Voltage Uimp DC Switching Capacity Resistive loads Voltage T ≤ 1 ms 24 48 60 110 Inductive loads T = 50 ms 30 48 60 110

220 Voltage 24

V A

NCS – 20 690 20

NCS – 25 690 25

NCS – 32 690 32

A A A A A A

20 15 15 11 3.5 4

25 22 22 15 6.5 5

32 30 30 22 11 6

kW kW kW kW

7.5/3.7 7.5 5.5/3 1.5/1.5

11/5.5 11 7.5/3.7 3/2.2

15/7.5 15 11/5.5 5.5/3

kV

6

6

6

A

20

25

32

A

12

20

25

A

4.5

7.5

10

A

1

1.5

2

A

0.4

0.5

0.6

A

12

20

25

A

5

9

12

A

2

3

3

A

1

1.5

1.5

A

0.4

0.5

0.5

Remark: The power under: AC-23A, AC-3, AC-4 are in three phase three pole, and the divider represents the power under single phase two pole.

Mechanical life Mechanical life without load: 60 x 104 times, operation frequency is 120 times/h. Mechanical life with load: 20 x 104 times under AC-15. 6 x 104 times under DC-13, operation frequency is 300 times/h

CAM SWITCHES Dimension Square escutcheon plate and square escutcheon plate with rectangle plate added M1 and M2 for Model NCS20 and NCS25

Model

NCS - 20

NCS - 25

NCS - 32

Model

NCS-20

NCS-25

Dimension (mm.)

Escutcheon plate

Installation (mm.)

A

B

C

L

a

b

d1

d2

M1

48

48

43

22+9.6n

36

36

M1 with rectangle plate

48

60

43

22+9.6n

36

36

M2

64

64

43

25+9.6n

48

48

M2 with rectangle plate

64

80

43

25+9.6n

48

48

M1

48

48

45.2

23+12.8n

36

36

M1 with rectangle plate

48

60

45.2

23+12.8n

36

36

M2 M2 with rectangle plate M2 M2 with rectangle plate

64 64 64 64

64 80 64 80

45.2 45.2 58 58

26.5+12.8n 26.5+12.8n 26.5+12.8n 26.5+12.8n

48 48 48 48

48 48 48 48

∅8.5 ∅8.5 ∅10 ∅10 ∅8.5 ∅8.5 ∅10 ∅10 ∅10 ∅10

∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5

Escutcheon plate

Dimension (mm.)

Installation (mm.)

A

B

C

D

E

F

a

b

d1

d2

M1

48

48

43

40+9.6n

40

1-4

36

36

M2

64

64

43

35+9.6n

48

1-4

48

48

M2 with rectangle plate

64

80

43

35+9.6n

48

1-4

48

48

M1

48

48

45.2

23+12.8n

40

1-4

36

36

M2

64

64

45.2 34.4+12.8n

48

1-4

48

48

M2 with rectangle plate

64

80

45.2 34.4+12.8n

48

1-4

48

48

∅24 ∅24 ∅24 ∅24 ∅24 ∅24

∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5 ∅4.5

Re: n for number of layers

CAM SWITCHES

Description

Escutcheon plate

NCS-20

M3

NCS-25

M3

Dimension (mm.) A

B

C

D

E

Installation (mm.) F

G

a

b

c

d1

d2

d3

∅10 ∅4 ∅20 48 85 25 47.2 34+12.8n 29 1-4 36 36 41.5 ∅10 ∅4 ∅20 48 85 25

45

34+9.6n

29

1-4

36 36 41.5

Re: n for number of layers

Type of handle Type R

Type F

Type I

Type S

Type P

Type O

Remark: Handle type S, P and O for escutcheon plate size M2 only and Key handle is available for size M1, M2 and M3

CAM SWITCHES Operating Position Diagram of Limited Movement Type

4 step

6 step

8 step

12 step

Operating Position Diagram of Spring Return Type

L to R

R to L

L / R to C

CAM SWITCHES Application Ammeter selector switch Size Rated current Voltage

Wire size Terminal Lug

M1 48x48mm / 48x64mm (with name plate) M2 64x64mm / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

Voltmeter selector switch Size

Wire size

M1 48x48mm / 48x64mm (with name plate) M2 64x64mm / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG

Terminal Lug

Fork terminal

Size Rated current Voltage

M2 64x64mm (without name plate) / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

Rated current Voltage

Circuit breaker control switch Pull and turn

Wire size Terminal Lug

Circuit breaker control switch Pull to lockout Size Rated current Voltage

Wire size Terminal Lug

M2 64x64mm (without name plate) / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

CAM SWITCHES Changeover switch M1, M2 Limited movement

Size Rated current Voltage

Wire size Terminal Lug

M1 48x48mm / 48x64mm (with name plate) M2 64x64mm / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

Changeover switch M2 Type (O) handle for M2 only

Size Rated current Voltage

Wire size Terminal Lug

M2 64x64mm (without name plate) / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

Changeover switch M2 Type (S) handle for M2 only Size Rated current Voltage

Wire size

M2 64x64mm (without name plate) / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG

Terminal Lug

Fork terminal

Key changeover switch Control and removable Size Rated current Voltage

Wire size Terminal Lug

M1 48x48mm / 48x64mm (with name plate) M2 64x64mm / 64x80mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

CAM SWITCHES Key changeover switch Lock and removable

Size Rated current Voltage

Wire size

M3 48x85mm 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG

Terminal Lug

Fork terminal

Size Rated current Voltage

M1 48x48mm (without name plate) / 48x64mm (with name plate) 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

Padlock switch Push and lock

Wire size Terminal Lug

Discrepancy control switch Circuit breaker type

Size Rated current Voltage

Wire size Terminal Lug

Square 48x48mm 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

Discrepancy control switch Disconnector switch type Size Rated current Voltage

Wire size Terminal Lug

Round ∅ 52 mm 20A / 25A / 32A Rated voltage : 690VAC Rated impulse withstand voltage : 6KV Rated insulation voltage : 690VAC 2 x 0.5 - 2.5 mm / 14 AWG Fork terminal

Cam Switch.pdf

Typical applications are breaking and closing, change-over of circuit, selector switches (for example: Auto- Manual),. control switch of switchgear and control ...

1MB Sizes 3 Downloads 224 Views

Recommend Documents

cam-camready.pdf
Lusheng Ji†. , H. Jonathan Chao*. *New York University †AT&T Labs-Research. Tandon School of Engieering 1 AT&T way. Brooklyn, NY 11201 Bedminster, ...

cam Newsletter 1_16
Please contact John Morris to report incidents or volunteer to patrol at 302-430-8455. .... Have you filed a complaint with the better business bureau? Yes No.

pdf-1891\cam-jansen-the-school-play-mystery-cam-jansen ...
pdf-1891\cam-jansen-the-school-play-mystery-cam-jansen-puffin-chapters.pdf. pdf-1891\cam-jansen-the-school-play-mystery-cam-jansen-puffin-chapters.pdf.

2016-17 CAM School Calendar.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. 2016-17 CAM ...

CAM NANG VIEC LAM.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. CAM NANG ...

solid cam tutorials pdf
Page 1 of 1. File: Solid cam tutorials pdf. Download now. Click here if your download doesn't start automatically. Page 1 of 1. solid cam tutorials pdf. solid cam ...

2389 CAM e-MTA.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. 2389 CAM ...

2014-5 CAM Newsletter.pdf
Descent of the River Sella/ ESP. Dalsland Canoe Marathon/ SWE .... 2014-5 CAM Newsletter.pdf. 2014-5 CAM Newsletter.pdf. Open. Extract. Open with. Sign In.

Cam nang toan tap CryptoCurrency.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. Cam nang toan ...

Mastering CAD/CAM (Engineering Series)
Online PDF Mastering CAD/CAM (Engineering Series), Read PDF Mastering .... feature-based modeling, parametrics, NURBS, collaborative design, PDM, and ...

2015-1 CAM Newsletter.pdf
WORLD CHAMPIONSHIPS 2015. DAY TIME ACTIVITY. 1 - Thursday 14:00 Team leaders meeting. 09:00. 09:05. 09:10. K1 Women Jun 18.3 km. C1 Women ...

2970/L8262-CAM - Asian Development Bank
May 11, 2016 - The Kingdom of Cambodia has received a loan from the Asian Development Bank (ADB) towards the cost of GMS Flood and Drought Risk Management and Mitigation Project. Part of this loan will be used for payments under the contract named ab

M.Tech-Mech-CAD CAM-Syllabus.pdf
Page 1 of 60. ACADEMIC REGULATIONS. COURSE STRUCTURE. AND. DETAILED SYLLABUS. JAWAHARLAL NEHRU TECHNOLOGICAL UNIVERSITY ...

E-07 -- Cam Switches 20A, 25A
NOMINAL RATING. Dimensions for Type A11, A12. Dimensions for Type A21, A22. / 45. Continuous. AC3-Power. Type. 36. 45 g. Current. 1th 2. 3 x 380V. 36. 46.