PURON® HF System to Expand Drinking Water Treatment Plant in Sao Paulo Koch Membrane Systems was awarded a contract to expand conventional treatment facility providing drinking water to the City of Sao Paulo, Brazil. The new KMS system consists of a submerged UF system utilizing the PURON® HF submerged modules. The system treats raw reservoir water. The system is designed to produce 2,000 lps (7,200 m3/hr) in two phases. © 2013, Koch Membrane Systems, Inc. All rights reserved.
PURON® HF System to Expand Drinking Water Treatment Plant in Sao Paulo KMS Scope of supply included -
Membrane modules and connection kits Engineering package Sequence of operation and controls program Technical services and commissioning supervision
The startup of the first 1,000 lps system was completed successfully in January 2015. The system consistently produces the required capacity to help relieve the drought conditions in the Sao Paulo metropolitan area. Project general contractor: Centroprojekt do Brazil
© 2013, Koch Membrane Systems, Inc. All rights reserved.
Existing WTP – Alto Da Boa Vista (ABV) Existing System: The existing treatment plant treats reservoir water via coagulation, clarification and sand filtration. Existing plant capacity: 15,000 lps (54,000 m3/hr)
The challenge: The demand for drinking water in the city of
Sao Paulo continues to increase. The ABV plant cannot expand its clarifiers and sand filters due to space limitations. The plant management was looking for a way to add 2,000 lps (7,200 m3/hr) water production using minimal footprint.
The solution: Install a submerged UF PURON® HF system in a small area on the side of the existing plant
© 2013, Koch Membrane Systems, Inc. All rights reserved.
PURON® HF System Design Feed Properties Influent Water Critical Characteristics
Parameter Temperature
Value 15-30°C
Ammonia
< 1.6 mg/L
Dissolved Iron
< 0.1 mg/L
Dissolved Manganese
< 0.1 mg/L
Color
< 161 CU
Alkalinity
< 45 mg/L
Total Suspended Solids*
< 20 mg/L
Turbidity*
< 20 NTU
pH
5.4 – 8.8
* - High algae and solids excursions are expected for periods up to 3 months © 2013, Koch Membrane Systems, Inc. All rights reserved.
PURON® HF System Design – Phase 1 Membrane System Design Number of membrane filtration trains Membrane module designation Nominal membrane area per module
6 PURON® HF 2650 2,650 m2
Number of module positions installed per train
7
Total Number of installed modules
42
Total installed membrane area
© 2013, Koch Membrane Systems, Inc. All rights reserved.
111,300 m2
PURON® HF System Design Parameters Parameter
Performance Targets
Net permeate flow with 6 trains in service
1,000 lps (86,400 m3/day)
Net permeate flux with 6 trains in service
32.3 lmh
Net permeate flow with 5 trains in service (maximum 24 hours)
1,000 lps (86,400 m3/day)
Net permeate flux with 5 trains in service (maximum 24 hours)
38.8 lmh
Permeate Turbidity
© 2013, Koch Membrane Systems, Inc. All rights reserved.
< 0.1 NTU Daily average with no reading above 0.5 NTU
Existing WTP – Alto Da Boa Vista (ABV)
© 2013, Koch Membrane Systems, Inc. All rights reserved.
ABV PURON® HF Ultrafiltration System Commissioning Photos
PURON® HF modules
© 2013, Koch Membrane Systems, Inc. All rights reserved.
p8
ABV PURON® HF Ultrafiltration System Commissioning Photos
© 2013, Koch Membrane Systems, Inc. All rights reserved.
p9
ABV PURON® HF Ultrafiltration System Commissioning Photos
© 2013, Koch Membrane Systems, Inc. All rights reserved.
p 10
ABV PURON® HF Ultrafiltration System First Week of Operation – Train 3 42 lmh
200-250 lmh/bar
Permeate Quality: Measured Permeate turbidity is 0.05-0.1 NTU © 2013, Koch Membrane Systems, Inc. All rights reserved.