Earth leakage and overloads short-circuit protection with self-reclosing

P 2

P.2.01 GB

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

CONTENTS Associated breaking element Earth leakage protection systems with self-reclosure

Page 3-4

Parameters related to self-reclosure relays

5

Protection and earth leakage reclosure

6

REC, built in system

Built in

7

WRU-25 RA / WRU-35 RA, Relays with built-in transformer

9

RGU-RA / RGU-10 RA / RGU-10C RA, Relays with external transformer

10

WG-35 / WG-70 / WG-105 / WG-140 / WG-210 WRU-25 2R / WRU-RM / WRU-RT, other relays with different functions

Contactor

10 11

GU72-D RA / CBS-8

12

CBS-8

13

Overload and earth leakage protection / earth leakage reclosure WRKRT-25 T / WRKRT-25 N

14 MCB

15

Overload and earth leakage protection and reclosure WRU 25 RA-MT, Relays with built-in transformer RGU-10 RA, Relays with external transformer

17 MT

18

WRT-6-25, other relays with different functions

19

RGMT, other relays with different functions

20

Earth leakage and overvoltage protection / overload and earth leakage reclosure RGST-2 / RGST-4

21 MT

Overload reclosure

21 22

RRM-P, RRM-C

MT

22

Breaking elements MCB-P / MCB-T circuit breaker

23

MT motorised overload device

24

MT-FDE, MT-FEE motorised overload device

25

Accessories

26

Dimensions / Connection

27-32

Protección y reconexión diferencial

Protección magnetotérmica y diferencial y reconexión diferencial

Protección y reconexión magnetotérmica y diferencial

Reconexión magnetotérmica

P2-2

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Earth leakage protection systems with self-reclosure Given the necessity and obligation of ensuring effective protection to both people and goods and the complexity of installations requiring continuous supply of electrical energy without removing earth leakage and overload protection, CIRCUTOR has developed a range of equipment which allows safety to be matched with continuous service. Self-reclosure is the ideal solution for installations requiring continuous supply of electrical energy without the usual maintenance staff: • • • • • • • • •

Rural installations Refrigerated chambers Public lighting Mobile telephone repeaters Traffic lights Tunnel lighting ATM’s Cable television etc.

In every self-reclosure system the type of protection to be reconnected and under which conditions must be known. Self-reclosure systems operate under: • Earth leakage current (differential) • Earth leakage current (differential) + overload and short-circuit (overload)

Elements comprising a self-reclosure system

TRANSFORMER

Signal handling + measuring and trip relay

Monitored breaking device

Differential transformer

El transformador diferencial detecta la Fuga a tierra. Éste puede estar incorporado en el relé o ser exterior a él.

Self-reclosure relay Self-reclosure relays offer additional benefits (self with closure, overload or short-circuit protection), to the reliability and safety shown by Series U earth leakage protection. Its functions are: • Fault detection (earth leakage or overload) via a signal generated by the transducer • Analysing if this fault should set off an alarm, with regard to the different preset parameters • Operating on a power device which connects – disconnects the load from the system

P2-3

P.2 Breaking element

Earth leakage and overload/short circuit protection systems with self-reclosure

The breaking element always operates as a power switch which supports the line power to be protected and is outside the relay. The breaking elements which may be associated with self-reclosure relays are: • Motorised overload/short-circuit device (MT series) (see page 24) • Contactor • Circuit breaker with remote-control (MCB) (see page 23), with the double function of overload/short-circuit protection and contactor (the conduct of function is bistable) The features which the breaking elements must know are: • • • • •

Rated current (in the contactors) Rated currents and the protection thermal curve (in overload/short-circuit devices) Features of the command inputs in the operating element Cut off power NA or NC auxiliary signalling of the status of the breaking device

Reclosure

Protection

Earth leakage

Page Earth leakage switch reconnector

6

Differential relay + contactor

8

Differential relay + MCB circuit breaker

14

Differential relay + MT overload device

16

Differential relay + FDE overload device

18

Earth leakage

Earth leakage Overload and Earth leakage Overload and earth leakage

P2-4

Earth leakage + overvoltage

Overload and earth leakage

Differential relay + MT overload device

21

Overload

Overload

RRM relay + MT / FDE overload device

22

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Parameters related to self-reclosure relays Relay status indication Indicators associated with protection are different for instant tripping and sealing. Indications are from the same relay (LED) and as an option may be through auxiliary contacts. Another type of display, depending on the relay, is the instant leakage value and the total number of reclosures.

Rated tripping point for protection Typical values: Earth leakage protection 30 mA – 3 A Overload protection 6 A – 63 A.

Timing (delay) for reclosure Minimum time which the earth leakage must last to cause the relay to trip. Typical values. 20 ms – 1 s

Relay power supply and tolerance The reclosure relays automatically require a permanent auxiliary power supply to be able to manage the automatic connection. Standard value: 230 V a.c..± 15 %. Optional 48 V a.c., 110 V a.c., 400 V a.c..

Time between reclosures This is the time the relay takes from the trip to reclosing. This time may be lineal or exponential.

Output relay Number of relays with output contact sealing NA or NC

Number of different reclosures / Number of types of reclosure Each relay allows a maximum number of the closures before being sealed. This meter may automatically put on zero if the number maximum number of reclosures has not been exceeded during a preset time (return to zero a time for the reclosure meters). This number will be different for the type of reclosure.

Return to zero time for the reclosure meters In order to avoid tripping being mounted up which do not belong to the same fault, a return to zero time for the reclosure meter may be set. This time restarts after each reclosure whenever a maximum number of reclosures is not exceeded. Example: The WRU 25 RA relay has a maximum number of six reclosures before being sealed. In an installation where the transient earth leakage fault lasts for 50 s, the relay will trip 4 times and reclose 3 times (8 s + 16 s + 30 s). While the third reclosure is being timed the fault disappears so the relay stays on ON. At this time the meter returns to zero reconnections. The RESET option restarts the relay returning the reclosure meters to zero.

On site and remote Test and Reset (using the keypad) The automatic earth leakage reclosure relays offer the same benefits as the U series earth leakage protection, among which is the option to check the proper operation of the relay using on-site TEST and RESET using the keypad on the relay itself and remotely using the specific inputs. The test is interpreted by the relay as an external leak. The relay will reconnect after a given time and increase the internal reclosure meter. The reset option restarts and relay return in the reclosure meters to zero.

P2-5

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

PROTECTION AND EARTH LEAKAGE RECLOSURE AUTOMATIC EARTH LEAKAGE RECONNECTOR SWITCH - REC

In the majority of cases (95 %), when the earth leakage protection is tripped, a simple manual reconnection solves the problem because there is no permanent leakage. If there is no REC automatic reconnector, this simple, manual reconnection operation may become a serious problem if there is nobody nearby or if the earth leakage trip is not known: • Food rots in the fridge • Plants wither through lack of watering • Swimminutesg pool water goes bad • The alarm system does not protect • The tilting garage door does not work • The farm may suffer serious damage • There is no mobile telephone coverage (fault with telephone repeater) • The ATM does not work • Streets and squares remain in the dark • Traffic lights stop working • etc.

t

h

e

Pure earth leakage switch with automatic resetting Terminals for the command line: N - L: 230 V AC power supply LI: external reclosure order (optional)

Free of power output indicates in earth leakage status

Motor

Earth leakage

2 or 4 pole breaking element

Manual switch (yellow lever): position I: automatic operation position 0: self-reclosure not permitted

The reclosure metre returns to zero if: • Leakage is not permanent • It always reconnects manually Number of reclosures

Time between reclosures

6

20, 30, 60, 120, 600 s

Hole for padlock Option for manual locking with padlock

Earth leakage protection required by current legislation protects people but unforeseen that trips made provoke a fault with the electrical supply in important installations. REC from CIRCUTOR is safe, easy to install, economic or will guarantee self-reclosure in your installation whenever the leakage is not permanent.

P2-6

P.2

REC 2 Poles

Poles

Class

In (A)

2

AC

40

30 mA

REC 2-40-30

P24111

2

AC

40

300 mA

REC 2-40-300

P24121

2

AC

63

30 mA

REC 2-63-30

P24114

2

AC

63

300 mA

REC 2-63-300

P24124

4

AC

40

30 mA

REC 4-40-30

P24112

4

AC

40

300 mA

REC 4-40-300

P24122

4

AC

63

30 mA

REC 4-63-30

P24113

4

AC

63

300 mA

REC 4-63-300

P24123

Sensitivity

Type

Earth leakage and overload/short circuit protection systems with self-reclosure

REC

Code

On request Class A

REC 4 Poles

Reclosure

Protection

Earth leakage reclosure

Earth leakage protection Electromechanical AC or A, according to type

Class Measuring

Number of reclosures

6

Time between reclosures

10, 20, 30, 60, 120, 600 s

Instant value 30 mA or 300 mA (according to type)

Sensitivity I∆n Delay

Same as last time between reclosures (For example: final reclosure on the third attempt → return to the zero time after 30 s)

Return to zero time for partial meter

Fixed at 20 ms

Diferential transformer

Built in

Test

Via built in button

Reset

Manual, by lifting the lever

Asociated breaking element In and number of poles

Safety seal

Using disconnection lever

Remote signalling (outputs)

Voltage free switched relay for status indication

Remote-control (inputs)

External reset using button

Built in In 40 A or 63 A , 2 or 4 poles

Breaking element control

Electromechanical relay

Features 2 poles

4 poles

Electrical features Auxiliary power supply Outputs contacts

230 / 400 V a.c., 50...60 Hz 2 A maximum for 250 V a.c. / 24 V d.c.

Operating temperature

-25 ºC / + 55 ºC

Assembly features Mounting Dimensions Weight Protection grade Standards

DIN rail 5 modules (90 x 90 mm)

7 modules (125 x 90 mm)

560 g

693 g IP 40

IEC 61008-1, IEC 755, IEC 255-5

P2-7

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

PROTECTION AND EARTH LEAKAGE RECLOSURE INSULATED SWITCH WITH SETTABLE SENSITIVITY AND DELAY

Switch formed by: Earth leakage relay + contactor Class A insulated. High-frequency filtering

Leakage current level indicator via variable flashing

Settable delay

Settable sensitivity

Number of poles and line current defined by the contactor

Earth leakage protection + earth leakage reclosure

APPLICATIONS Street lighting

Office blocks

• Traffic lights • Car parks • Refrigerated chambers

P2-8

P.2

Class

In (A)

Poles

Useful diameter ∅ mm

I∆n or Sensitivity (A)

Delay (s)

Type

Earth leakage and overload/short circuit protection systems with self-reclosure

Earth leakage relay with built in transformer

Code

A

63 (*)

2, 3, 4

25

0,03...3

0,02...1

WRU-25 RA

P24211

A

125 (*)

2, 3, 4

35

0,03...3

0,02...1

WRU-35 RA

P24221

(*) According to contactor Number of reclosures

Time between reclosures (s)

WRU-25 RA

6

8,16,30,59,115,224

WRU-35 RA

6

8,16,30,59,115,224

Type

WRU-35 RA

+

Complete set formed by: Earth leakage relay + Contactor WRU-25 RA

Protection

Reclosure

WRU 25 RA

WRU 35 RA

WRU 25 RA Earth leakage reclosure

Earth leakage protection Class

Selectable 30 mA...3 A

Delay

Selectable 20 ms ... 1s Built in ∅ 25 mm

Test y Reset

In and number of poles

8, 16, 30, 59, 115, 224 s

Return to zero time for partial meter

Built in ∅ 35 mm

Via built in button

Associated breaking element

6

Time between reclosures

TRMS

Sensitivity I∆n

Differential transformer

No. of reclosures

A superinsulated

Measuring

15 minutes

Signalling in the relay – Presence of voltage indicator – Sealed reclosure – Indicates the presence of leakage current without reaching the trip point

LED

Contactor Defined by contactor used

Breaking element control

WRU 35 RA

1 switched relay

Remote signalling (outputs)

Leakage control signal (proportional alternating voltage)

Remote-control (inputs)

External test using button

Features WRU 25 RA

WRU 35 RA

Electrical features Auxiliary power supply Breaking element control contacts

230 V a.c. (± 20 %) 50...60 Hz 250 V a.c. / 8 A a.c.

Operating temperature

- 10 ºC / + 50 ºC

Mechanical features Mounting Dimensions Weight Protection grade Standards

DIN rail 4 modules

6 modules

234 g

415 g

Terminals: IP20, Built in relay: IP41 IEC 61008-1, IEC 755, IEC 255-5

P2-9

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Earth leakage relay with external transformer

I∆n (A)

Delay (s)

Communications

Number of reclosures

Breaking element control

Remote signalling

Type

Code

0,03...3

0,02...1

-

6

Switched relay

-

RGU-RA

P24311

0,03...30

0,02...10

-

Programmable

NA relay-Positive safety

Relay seal

RGU-10 RA

P24612

0,03...30

0,02...10

RS-485

Programmable

NA relay-Positive safety

-

RGU-10C RA

P24632

Selection of differential transformer according to rated line current

+

RGU-RA

WG-35

P10111

70 ∅

WG-70

P10112

105 ∅

WG-105

P10113

140 ∅

WG-140

P10114

210 ∅

WG-210

P10115

Reclosure

RGU-RA

RGU-10 RA

RGU-RA

Number of reclosures

A superinsulated

Measuring

TRMS

Time between reclosures

Selectable 30 mA...3 A

Programmable 30 mA...30 A

Selectable 20 ms ... 1s

Programmable 20 ms ... 1s Inverse curve: Instant or selective

6

Programmable: 0... 10

8, 16, 30, 59, 115, 224 s

Programmable: 1... 900 s

15 minutes

15 / 30 minutes

Return to zero time for partial meter Signalling in the relay

Differential transformer

External, Serie WG

Test y Reset

Via built in button

Associated breaking element

- Presence of voltage - Sealed reclosure - Indicates the presence of leakage current without reaching the trip point

LED

Contactor

In and number of poles

Defined by contactor used 1 switched relay

1 relay simple

LCD

Remote signalling (outputs)

-

Prealarm relay

Remote-control (inputs)

-

ON / OFF

RGU-10 RA

Electrical features

Breaking element control contacts

230 V a.c. (± 20 %) 50...60 Hz 250 V a.c. / 8 A.a.c

Operating temperature

250 V a.c. / 6 A a.c. -10 ºC / +50 ºC

Mechanical features Mounting Dimensions Weight

Presence of voltage One channel tripped Reclosure enabled Sealed status RS-485 Communications

-

RGU-RA

Auxiliary power supply

-

Display

Features

P2-10

RGU-10 RA

Earth leakage reclosure

Earth leakage protection Class

Breaking element control

30 ∅

Code

Complete set formed by: Earth leakage relay + Toroidal transformer + Contactor

Protection

Delay

Type

+

RGU-10-RA

Sensitivity I∆n

Useful diameter (mm)

DIN rail 4 modules

3 modules

261 g

236 g

Protection grade

Terminals: IP20, Built in relay: IP41

Standards

IEC 61008-1, IEC 755, IEC 255-5

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Other earth leakage relays with different functions

Relays with built in transformer Useful diameter ∅ mm

I∆n (A)

Delay (s)

Number of reclosures

25

0,03...3

0,02...1

30

25

0,03...3

0,02...1

3

25

0,3...1

0,02

3

1 NC contact

Breaking element control

Remote signalling

Type

Code

Switched relay

-

WRU-RM

P24231

1 NA-SP contact

1 NA-SP contact

WRU-RT

P24431

1 NA contact

WRU-25-2R

P24412

Protection

WRU-25-2R

WRU-RM

WRU-RT

Earth leakage protection Class

A superinsulated

Measuring Sensitivity I∆n

TRMS Settable 300 mA ... 1 A

Delay

Selectable 30 mA ... 3 A

Fixed 20 ms

Selectable 20 ms ... 1 s

Differential transformer

Built in Ø 25 mm

Test y Reset

Via built in button

Associated breaking element

Contactor

In and number of poles

Defined by contactor used

Reclosure WRU-25-2R

WRU-RM

WRU-RT

Earth leakage reclosure Number of reclosures

31 st

Time between reclosures Return to zero time for partial meter

30 nd

1 at 2 min., 2 at 4 min., remainder every 6 min.

20 s, 40 s y las 28 remainder every 5 minutes

15 minutes

15 minutes

Features WRU-25-2R

WRU-RM

WRU-RT

Electrical features Auxiliary power supply Breaking element control contacts Operating temperature

230 V a.c. (± 20%) 50...60 Hz 250 V a.c. / 8 V a.c. -10 ºC / +50 ºC

Mechanical features Mounting Dimensions Weight Protection grade Standards

DIN rail 4 modules 234 g Terminals: IP20, Built in relay: IP41 IEC 61008-1, IEC 755, IEC 255-5

P2-11

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Other earth leakage relays with different functions

Relés con transformador externo I∆n (A)

Delay (s)

Communications

Number of reclosures

Breaking element control

Remote signalling

Type

Code

0,03...3

0,02...1

-

6

Switched relay

-

GU72-D RA

P24321

0,03...30

0,02...10

RS-485

Prog.: 0...10

8 relays (independent)

Pre-alarm relay

CBS-8

P12811

Protection

GU-72 RA

CBS-8

Earth leakage protection Class

A superinsulated

Measuring

TRMS

Sensitivity I∆n

Selectable 30 mA...3 A

Delay

Selectable 20 ms ... 1 s

Differential transformer

0,03…6 A with external transformers WG/WGS 0,03…60 A with external transformers WGP/WGPS Programmable 0,20 ms ... 10 s Inverse curve: Instant or selective External, Serie WG

Test y Reset

Via built in button

Associated breaking element

Contactor

In and number of poles

Defined by contactor used

Reclosure GU-72 RA

CBS-8

Earth leakage reclosure No. of reclosures Time between reclosures Return to zero time for partial meter

6

Programmable

8, 16, 30, 59, 115, 224 s

Programmable

15 minutes

Programmable

Features RGU-RA

CBS-8

Electrical features Auxiliary power supply

230 V a.c. (± 20 %) 50...60 Hz

Breaking element control contacts

250 V a.c. / 8 A a.c.

Operating temperature

- 10 ºC / +50 ºC

Mechanical features Mounting Dimensions Weight Protection grade Standards

P2-12

Panel

DIN rail

72 x 72 mm

8 modules

349 g

609 g Terminals: IP20, Built in relay: IP41 IEC 61008-1, IEC 755, IEC 255-5

P.2 • • • •

8 earth leakage protection programmable relays, class A Frequency filtering Disconnection delay using inverse curve Independent programminutesg per channel

Earth leakage and overload/short circuit protection systems with self-reclosure

CBS-8

Reduction of unforeseen trips Increases the continuity of the production process Smaller size

Displays in TRMS

Signalling LED 2 signalling LEDs: - ON / Fault trip - Pre-alarm / Reclosure status

- Instant leakage current - Leakage current trip

Connection indicator

Test and reset buttons

With the associated breaking element to carry out earth leakage protection

Test and reset buttons

Parameter display

Programmable Setting using rotating parameter menu. 4 buttons

- Sensitivity - Delay - Channel to be set

Communications Option for RS485 Communications. MODBUS Protocol. Only displays programminutesg parameters, leakage values and status of each channel.

Accessories

TT (see page 26)

WG and WGP differential transformers

P2-13

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Overload and earth leakage protection / Earth leakage reclosure INSULATED RELAY WITH SETTABLE SENSITIVITY AND DELAY

Switch formed by: Earth leakage relay + circuit breaker Class A insulated. High-frequency filtering

Settable delay

Settable sensitivity

+ Leakage current level indicator via variable flashing

Relay input: WRKRT-25 T : for resetting WRKRT-25 N : for remote control

Number of poles and line current defined by the contactor

Overload and earth leakage protection + earth leakage reclosure

Applications Street lighting

Telephone systems

• Traffic lights • Cable TV

P2-14

P.2

Poles

Useful diameter ∅ mm

In (A)

Delay (s)

Type

Code

Up to 63 A

2, 3+N

25

0,03...3

0,02...1

WRKRT-25 T

P23111

Up to 63 A

2, 3+N

25

0,03...3

0,02...1

WRKRT-25 N

P23121

Earth leakage and overload/short circuit protection systems with self-reclosure

Earth leakage relay with built in transformer

With sensitivity adjustment on 0.03 A, delay cancelled

Complete set formed by: Earth leakage relay + MCB circuit breaker (suitable for the line)

Protection

Reclosure

WRKRT-25 T

WRKRT-25 N

WRKRT-25 T

Earth leakage and overload protection Class

A Superinsulated

Measuring

TRMS

Sensitivity

Selectable 30 mA ... 3 A

Delay

Selectable 20 ms ... 1 s Built in ∅ 25 mm

Test y Reset

Via built in button

Associated breaking element

MCB.T circuit breaker

Number of poles , In, thermal curve, cut off power

Number of reclosures Time between reclosures

Differential transformer

WRKRT-25 N

Earth leakage reclosure 30

6

20 s, 40 s, los 28 remainder every 5 minutes.

Return to zero time for partial meter

15 minutes

Signalling in the relay

MCB.P circuit breaker

LED

Defined by circuit breaker used Remote-control (inputs)

- Presence of voltage indicator - Sealed reclosure - Indicates the presence of leakage current without reaching the trip point External reset using button

Inputs ON (earth leakage only) and relay OFF

Features WRKRT-25 T / WRKRT-25 N Electrical features Auxiliary power supply Breaking element control contacts

WRKRT-25 T / WRKRT-25 N Mechanical features

230 V a.c. (±20 %) 50...60 Hz Maximum current 3 A a.c.

Operating temperature

Mounting Dimensions Weight

-10 ºC / +50 ºC Protection grade Standards

DIN rail 4 modules 235 g Terminals: IP20, Built in relay: IP41 IEC 61008-1, IEC 755, IEC 255-5, IEC 947-2

Accessories

Circuit breaker MCB (page 23)

P2-15

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

OVERLOAD AND EARTH LEAKAGE PROTECTION AND RECLOSURE INSULATED RELAY WITH SETTABLE SENSITIVITY AND DELAY

Switch formed by: Earth leakage + overload relay Class A insulated. High-frequency filtering

Settable delay

+ Leakage current level indicator via variable flashing

Settable sensitivity

Number of poles and line current defined by the contactor

Overload and earth leakage protection + Overload and earth leakage reclosure

APPLICATIONS Street lighting

P2-16

Office blocks

P.2

In

Poles

Sensitivity

Type

Code

Up to 63 A

2,4

30 mA

WRU-25 RA-MT

P24241

Type

Number of reclosures

Time between reclosures

WRU-25 RA-MT

6

1 minutes

Earth leakage and overload/short circuit protection systems with self-reclosure

Earth leakage relay with built in transformer

Complete set formed by: Earth leakage relay + MT overload device

Protection

Reclosure

WRU-25 RA-MT

WRU-25 RA-MT

Earth leakage protection Class

A superinsulated

Measuring

TRMS

Sensitivity I∆n

Selectable 30 mA...3 A

Delay

Selectable 20 ms ... 1 s

Differential transformer

Built in ∅ 25 mm

Test y Reset

Via built in button

Associated breaking element

Overload device Serie MT

Rated In thermal curve, cut off power and no. of poles

Defined by overload device used

Breaking element control

Earth leakage and overload reclosure Number of reclosures

6

Time between reclosures

8, 16, 30, 59, 115, 224 s

Return to zero time for partial meter

15 minutes In the overload device. Using disconnection lever.

Safety sealing Signalling in the relay

- Presence of voltage indicator - And/or earth fault indicator

LED Remote signalling (outputs)

Leakage control signal (proportional alternating voltage)

1 switched relay

Features WRU-RA-MT Electrical features Auxiliary power supply Breaking element control contacts Output contacts Operating temperature

230 V a.c. (±15 %) 50...60 Hz 250 V a.c. / 8 A a.c. Maximum current 3 A -10 ºC / +50 ºC

Assembly features Mounting

DIN rail

Dimensions

4 modules

Weight Protection grade Standards

234 g Terminals: IP20, Built in relay: IP41 IEC 61008-1, IEC 755, IEC 255-5

Accessories

MT overload decive (page. 24)

P2-17

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Earth leakage relay with external transformer

Class

In (A)

Poles

Toroidal

Delay (s)

Type

Code

A

According to contactor

2,3,4

Serie WG

0,02...1

RGU-10 RA

P24612

Type

Number of reclosures

Time between reclosures

RGU-10 RA

Programmable

Programmable

Complete set formed by: Earth leakage relay + WG toroidal + MT / MT-FDE overload device

Protection

Reclosure Earth leakage and overload reclosure

Earth leakage and overload protection Class

A superinsulated

Measuring

Time between reclosures

TRMS

Return to zero time for partial meter

Programmable 30 mA...30 A

Sensitivity I∆n

Programmable 20 ms ... 1 s Inverse curve: Instant or selective

Delay Differential transformer

Via built in button

Associated breaking element

Defined by overload device used 1 relay simple

Programmable: 1... 900 s 15 / 30 minutes

- Presence of voltage - A channel has tripped- Reclosure enabled - Sealed status - RS-485 Communications

LED

Overload device Serie MT, MT-FDE

Breaking element control

Programmable: 0... 10

Signalling in the relay

External, Serie WG

Test y Reset

In and number of poles

No. of reclosures

Display

LCD

Remote signalling (outputs) Remote-control (inputs)

Prealarm relay ON / OFF

Features Electrical features Auxiliary power supply

230 V a.c. (± 20 %) 50...60 Hz

Breaking element control contacts

5 A a.c. current

Operating temperature

-10 ºC / +50 ºC

Mechanical features Mounting Dimensions

DIN rail 3 modules

Weight Protection grade Standards

236 g Terminals: IP20, Built in relay: IP41 IEC 61008-1, IEC 755, IEC 255-5

Accessories

MT overload device (page 24)

P2-18

MT overload device (page 25)

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Other earth leakage relays with different functions

Relays with built in transformer Nº Reclosures

Useful diameter ∅ mm

I∆n (A)

Poles

25

0,03

According to MT

25

0,3

According to MT

Delay (s)

Breaking element control

Remote signalling

Type

Code

10

Relay ON/OFF

Sealed through reclosure

WRT-6-25-0,03

P21121

10

Relay ON/OFF

Sealed through reclosure

WRT-6-25-0,3

P21122

overload

earth leakage

0,02

2

0,02

2

Protection

Reclosure WRT-6-25

WRT-6-25

Earth leakage and overload protection Class

Earth leakage and overload reclosure

A Superinsulated

Measuring

No. of reclosures

TRMS

Sensitivity I∆n

Fixed 30 mA or 300 mA (according to type)

Delay

Fixed 20 ms ∅ 25 mm built in relay

Differential transformer Test y Reset Associated breaking element

Time between reclosures

1 minutes

Return to zero time for partial meter

30 minutes

Safety sealing

Via built in button

2 per overload device and 10 per earth leakage

In the overload device. Using disconnection lever.

Overload device Serie MT

Rated In thermal curve, cut off power and no. of poles

Defined by overload device used

Features Electrical features Auxiliary power supply

Assembly features 230 V a.c. (±15 %) 50...60 Hz

Breaking element control contacts

250 V a.c. / 8 A a.c.

Output contacts

250 V a.c. / 8 A a.c.

Operating temperature

Mounting Dimensions Weight

-10 ºC / +50 ºC

Protection grade Standards

DIN rail 6 modules 425 g Terminals: IP20, Built in relay: IP41 IEC 61008-1, IEC 755, IEC 255-5

Accessories

MT Overload device (page 24)

P2-19

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Other earth leakage relays with different functions

Relays with external transformers Number of reclosures

Useful diameter ∅ mm

I∆n (A)

Poles

According to WG

0,03 / 0,3

According to MT

Delay (s)

Overload

earth leakage

2

10

0,02

Breaking element control

Remote signalling

Type

Code

Relay ON / OFF

2

RGMT

P21130

Protection

Reclosure

Protection

Earth leakage and overload reclosure

Class

A Superinsulated

Measuring

2 per overload device and 10 per earth leakage

Number of reclosures

TRMS 0,03 / 0,3 A

Sensitivity I∆n Delay

Fixed 20 ms

Differential transformer

Time between reclosures

3 minutes

Return to zero time for partial meter

30 minutes

External, Serie WG

Test y Reset Associated breaking element

In the overload device. Using disconnection lever.

Safety sealing

Via built in button Overload device Serie MT

Rated In thermal curve, cut off power and no. of poles

Defined by overload device used

Features Electrical features Auxiliary power supply

Assembly features 230 V a.c. (±15 %) 50...60 Hz

Breaking element control contacts

250 V a.c. / 8 A a.c.

Output contacts

250 V a.c. / 8 A a.c.

Operating temperature

Mounting

DIN rail

Dimensions

6 modules

Weight -10 ºC / +50 ºC

350 g Front: IP54, casing and terminals: IP20

Protection grade

IEC 61008-1, IEC 755, IEC 255-5, IEC 947-2, IEC 60898

Standards

Complete Kits The equipment is formed by: • RGMT earth leakage relay

2 Poles Type

Type

Code

P21210

WRGMT-C-4-10 A

P21221

WRGMT-C-2-10 A

P21211

WRGMT-C-4-16 A

P21222

WRGMT-C-2-16 A

P21212

WRGMT-C-4-20 A

P21223

WRGMT-C-2-20 A

P21213

WRGMT-C-4-25 A

P21224

WRGMT-C-2-25 A

P21214

WRGMT-C-4-32 A

P21225

WRGMT-C-2-32 A

P21215

WRGMT-C-4-40 A

P21226

WRGMT-C-2-40 A

P21216

WRGMT-C-4-50 A

P21227

WRGMT-C-2-50 A

P21217

WRGMT-C-4-63 A

P21228

WRGMT-C-2-63 A

P21218

WRGMT-C-2-6 A

• MT series of motorised overload device or MT-FDE series motorised overload switch with overload protection function and breaking element • WG series differential transformer

P2-20

4 Poles Code

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

EARTH LEAKAGE AND OVERVOLTAGE PROTECTION OVERLOAD AND EARTH LEAKAGE RECLOSURE BREKING ELEMENT: MT

The RGST-2 / RGST-4 is equipment which protects against permanent overvoltages. This continuously measures line voltages and if the value in any phase exceeds the previously set limits, either by a maximum or minimum voltage, the RGST set associated with a breaking device (MT series motorised overload device or similar) interrupts the electricity supply. After a certain time, it tries to reconnect again. Also the RGST, with a WG series transformer is an earth leakage protection relay. The RGST, connected to a motorised overload device allows reclosure in the event of an earth leakage and/or overload trip.

Complete set formed by: RGST Relay + Toroidal WG + MT / MT-FDE overload device Nºumber of reclosures

Useful diameter ∅ mm

I∆n (A)

Poles

according to WG

0,3...0,5

2

0,02

0...3

according to WG

0,3...0,5

4

0,02

0...3

Delay (s)

overload

Breaking element control

Remote signalling

Type

Code

0...10

1 switched

1 NA

RGST-2

P21141

0...10

1 switched

1 NA

RGST-4

P21142

earth leakage

Protection

Reclosure

Earth leakage, overload and overvoltage protection Maximum voltage

Programmable 235...270 V a.c.

Minimum voltage

Programmable 180...210 V a.c.

Conection delay

Programmable 100...980 ms (only for overvoltages)

Class

A Superinsulated

Measuring Sensitivity I∆n Delay Differential transformer

External Serie WG

Test y Reset

Via built in button

No. of poles, In, thermal curve, cut off power

Breaking element control

Time between programmable reclosures Return to zero time for partial meter

TRMS Programmable: 30...500 mA Fixed 20 ms

Associated breaking element

Earth leakage and overload reclosure No. of programmable reclosures

MT series motorised overload device + F6 coil Defined by overload device used

Safety sealing

0...3 per overload device 0...10 per earth leakage 1...60 min. per overload device; 3...250 secs. per earth leakage and overvoltage Programmable 30...60 minutes In the overload device. Using disconnection lever.

Signalling in the relay LED

Display Remote signalling (outputs) Remote-control (inputs)

– Protection and reclosure status indication – Selected parameter indication Numerical. 3 digits. Total number of reclosures and parameter setting NA free of power reclosure seal output Remote ON / OFF input

Using relay (3 relays) ON / OFF and F6 coil. The overload device disconnection is guaranteed in the event of an auxiliary power supply failure

Features Electrical features

Accessories

Auxiliary power supply

230 V a.c. (±15 %) 50...60 Hz

Operating temperature

-10 ºC / +50 ºC

Assembly features Mounting Dimensions Weight WG Transformer (page 10)

MT Overload device (page 24)

Protection grade Standards

DIN rail 8 modules 565 g Front: IP54, Casing: IP20, Terminals: IP20 IEC 61008-1, IEC 755, IEC 255-5, IEC 947-2, IEC 60898

P2-21

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

OVERLOAD RECLOSURE BREAKING ELEMENT: MT RRM-P, RRM-C The RRM is a relay for overload protection reclosure. It allows the control, remote signalling and remote-control of the associated motorised overload switch (MT and MT-FDE series). The functions of the RRM relay are: • Motorised overload device control: - Self-reclosure - Remote connection/disconnection (not reconnectable) • Signalling: - On site via LED - Remote signalling using relay blocking reclosure in RRM-P - RS485 communications in RRM-C • Automatic switch remote-control

Type

Comunication

Code

RRM-P

Not available

P25130

RRM-C

RS-485

P25131

Complete set formed by: RRM Relay + MT / MT-FDE overload device

Protection

Reclosure

RRM-P Protection

RRM-C Overload

RRM-P Reclosure

Associated breaking element

Overload device Serie MT

Number of poles, In, thermal curve, cut off power

Defined by overload device used

Breaking element control

Control motor contact

RRM-C Overload

Number of programmable reclosures Time between programmable reclosures

Selectable: 0,1,2,4,6,8 times 0.5, 1, 2, 3, 4, 5 minutes

Return to zero time for programmable partial meter Safety sealing

30 minutes In the overload device. Using disconnection lever.

Signalling in the relay – Presence of voltage indicador and no overload trip – Indication of trip through external order – Sealed by ending of reclosures – Reclosure in process

LED

Remote signalling (outputs) Remote-control (inputs)

Relay seal

RS-485 communications

ON / OFF free of power input in breaking element (External OFF not reconnectable)

Features Electrical features

Assembly features

Auxiliary power supply

230 V a.c. (±20 %) 50...60 Hz

Mounting

Breaking element control contacts

250 V a.c., 1 A

Dimensions

Operating temperature

-10 ºC + 50 ºC

Weight Protection grade Standards

DIN rail 1 module 88 g Terminals: IP20, Built in relay: IP41 IEC 947-2

Accessories

MT overload device (page 24)

P2-22

MT-FDE Overload device (page 25)

P.2 The MCB.P or MCB.T our circuit breakers which combine overload functions with contactor functions in the same equipment. The MCB.T version also includes two auxiliary contacts which show the status of the remote control input and the overload input. Both the MCB.P and the MCB.T version include an ordinary contact to indicate a trip from an overload device or from the manual action of the circuit breaker. There are two trip conditions for the circuit breaker: • Tripping from overheating, delayed, (overload protection) • Rapid tripping, electromagnetic (protection against shortcircuiting)

Remote-control operates on the same complex as the overload device, guaranteeing disconnection for any event by remote control after manual or overload device tripping. The remote control operates electro-magnetically, applying a control voltage lasting 20 ms, to the ON terminals (Terminals 1-3) and OFF terminals (Terminals 2-3). It includes an optical displays of the system status (red = ON, green = OFF), regardless of the cause of the trip.

2 Poles

4 Poles

MCB.P

MCB.T

MCB.P

MCB.T

In (A) Type

Code

Type

Code

Type

Code

Type

Code

6

MCB.P C-2p-6A

P20210

MCB.T C-2p-6A

P20310

-

-

-

-

10

MCB.P C-2p-10A

P20211

MCB.T C-2p-10A

P20311

MCB.P C-3p+N-10A

P20221

MCB.T C-3p+N-10A

P20321

16

MCB.P C-2p-16A

P20213

MCB.T C-2p-16A

P20313

MCB.P C-3p+N-16A

P20223

MCB.T C-3p+N-16A

P20323

20

MCB.P C-2p-20A

P20214

MCB.T C-2p-20A

P20314

MCB.P C-3p+N-20A

P20224

MCB.T C-3p+N-20A

P20324

25

MCB.P C-2p-25A

P20215

MCB.T C-2p-25A

P20315

MCB.P C-3p+N-25A

P20225

MCB.T C-3p+N-25A

P20325

32

MCB.P C-2p-32A

P20216

MCB.T C-2p-32A

P20316

MCB.P C-3p+N-32A

P20226

MCB.T C-3p+N-32A

P20326

40

MCB.P C-2p-40A

P20217

MCB.T C-2p-40A

P20317

MCB.P C-3p+N-40A

P20227

MCB.T C-3p+N-40A

P20327

50

MCB.P C-2p-50A

P20218

MCB.T C-2p-50A

P20318

MCB.P C-3p+N-50A

P20228

MCB.T C-3p+N-50A

P20328

63

MCB.P C-2p-63A

P20219

MCB.T C-2p-63A

P20319

MCB.P C-3p+N-63A

P20229

MCB.T C-3p+N-63A

P20329

Features 2 Poles

4 Poles

2 Poles

Overload Calibres In (A) Rated cut off power (IEC 947-2) Characteristic curve Rated operating voltage Operating frequency range

4 Poles

Motor 6-10-16-20-25-32-40-50-63

6...16 A: 20 kA

20...63 A: 15 kA

Rated voltage

230 V a.c.

Activation impulse

< 20 ms

C or D according to type

Deactivation impulse

< 20 ms

230 / 400 V a.c.

Mechanical features

50...60 Hz

Mounting

Operating temperature

-25 ºC / +55 ºC

Dimensions

Storage temperature

-40 ºC / +70 ºC

Mechanical life Weight Protection grade Standards

DIN rail 3 modules

5 modules

20.000 operations 375 g

615 g

IP 20 (DIN 40050) IEC 947-2, IEC 60898

P2-23

Earth leakage and overload/short circuit protection systems with self-reclosure

MCB.P, MCB.T Circuit breaker

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

MOTORISED OVERLOAD DEVICE, MT Overload device with remote-control. Protection against short-circuit and overloads. Also used as a breaking element. Includes auxiliary contacts for indicating overload status. After a disconnection from short-circuit, overload or manual disconnection the overload switch may be connected again using an electrical order with the sequence “DISCONNECTION (0) - CONNECTION ( I )“

2 Poles

4 Poles

Curve C

I∆n (A)

Curve D

Curve C

Curve D

Type

Code

Type

Code

Type

Code

Type

Code

6

MT-C-E62-6A

P20110

MT-D-E62-6A

P20130

MT-C-E64-6A

P20120

MT-D-E64-6A

P20140

10

MT-C-E62-10A

P20111

MT-D-E62-10A

P20131

MT-C-E64-10A

P20121

MT-D-E64-10A

P20141

16

MT-C-E62-16A

P20112

MT-D-E62-16A

P20132

MT-C-E64-16A

P20122

MT-D-E64-16A

P20142

20

MT-C-E62-20A

P20113

MT-D-E62-20A

P20133

MT-C-E64-20A

P20123

MT-D-E64-20A

P20143

25

MT-C-E62-25A

P20114

MT-D-E62-25A

P20134

MT-C-E64-25A

P20124

MT-D-E64-25A

P20144

32

MT-C-E62-32A

P20115

MT-D-E62-32A

P20135

MT-C-E64-32A

P20125

MT-D-E64-32A

P20145

40

MT-C-E62-40A

P20116

MT-D-E62-40A

P20136

MT-C-E64-40A

P20126

MT-D-E64-40A

P20146

50

MT-C-E62-50A

P20117

MT-D-E62-50A

P20137

MT-C-E64-50A

P20127

MT-D-E64-50A

P20147

63

MT-C-E62-63A

P20118

MT-D-E62-63A

P20138

MT-C-E64-63A

P20128

MT-D-E64-63A

P20148

Features 2 Poles

4 Poles

2 Poles

Overload Calibres In (A) Number de Poles

6-10-16-20-25-32-40-50-63 2

4

Rated cut off power

10 kA

Characteristic curve Rated operating voltage Operating frequency range

Rated voltage

230 V a.c.

Minimum voltage

210 V a.c.

Activation impulse

50 ms

C or D according to type

Desactivation impulse

50 ms

240 / 415 V a.c.

Mechanical features

50...60 Hz

Mounting

DIN rail

Operating temperature

-25 ºC / +55 ºC

Dimensions (mm)

Storage temperature

-55 ºC / +55 ºC

Mechanical life

> 20.000 Operations

Weight (g)

645

Protection grade Standards

P2-24

4 Poles

Motor

5,5 modules:

7,5 modules:

890

IP 40 (DIN 40050) IEC 947-2, IEC 60898

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

MT-FDE, MT-FEE MOTORISED OVERLOAD DEVICE MT-FDE series overload device with remote control. Protection against short-circuit and overloads. Also used as a breaking element. After a disconnection from short-circuit or overload, the overload device may be reconnected. The reclosure is done in a different way using the position of the lever in operating mode: • “MANU” is done manually in the same switch using the sequence OFF and then ON • “AUTO” is done using an electrical impulse following the sequence OFF and then ON

For currents above 63 A MT-FDE / MT-FEE 3 Poles In (A)

Type

4 Poles

Weight (Kg)

Code

Type

Weight (Kg)

Code

80

MT-FDE-80A

2,9

P20D60

MT-FDE-80A

3,4

P20D70

100

MT-FDE-100A

2,9

P20D61

MT-FDE-100A

3,4

P20D71

125

MT-FDE-125A

2,9

P20D62

MT-FDE-125A

3,4

P20D72

160

MT-FDE-160A

2,9

P20D63

MT-FDE-160A

3,4

P20D73

250

MT-FEE-250A

3,8

P20E64

MT-FEE-250A

4,6

P20E74

Features FDE

FEE

FDE

Magnetotérmico Calibres In (A) Number of Poles Rated cut off power (IEC 947-2) Characteristic curve Rated operating voltage Operating frequency range

FEE

Motor

80-100-125-160

250

Rated voltage

230 V a.c.

3 or 4 according to type

Minimum voltage

210 V a.c.

25 kA

Activation impulse

50 ms

C or D according to type

Desactivation impulse

50 ms

240 / 415 V a.c.

Mechanical features

50...60 Hz

Operating temperature

-25 ºC / +55 ºC

Storage temperature

-55 ºC / +55 ºC

Mounting Dimensions (mm)

Panel (base + pluggable base) 3 Poles: 81 x 130 x 185 4 Poles: 108 x 130 x 185

Weight

According to type

Protection grade

IP 40 (DIN 40050)

Standards

IEC 947-2, IEC 60898

P2-25

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Accessories Earth leakage transformers, WG series Weight (g)

Useful diameter (mm)

Type

Code

Weight (g)

Useful diameter (mm)

Type

Code

75

20 ∅

WGS-20

P10131

2.400

70x175

WG-70 x 175

P10116

94

30 ∅

WGS-30

P10132

5.450

115x305

WG-115 x 305

P10117

180

35 ∅

WG-35

P10111

7.400

150x350

WG-150 x 350

P10118

274

70 ∅

WG-70

P10112

13.400

200x500

WG-200 x 500

P10119

544

105 ∅

WG-105

P10113

1.222

140 ∅

WG-140

P10114

2.040

210 ∅

WG-210

P10115

Earth leakage transformers, WGP series (only for cbs-8) Useful diameter (mm)

Type

Code

20 ∅

WGSP-20

P10141

30 ∅

WGSP-30

P10142

35 ∅

WGP-35

P10121

70 ∅

WGP-70

P10122

105 ∅

WGP-105

P10123

140 ∅

WGP-140

P10124

210 ∅

WGP-210

P10125

Useful diameter (mm)

P2-26

Type

Code P19911

Code

70x175

WGP-70x175

P10126

115x305

WGP-115x305

P10127

150x350

WGP-150x350

P10128

Toroidal protection tube

TT-35

Type

Adapters

TT-70

P19912

TT-105

P19913

TT-140

P19914

Description

Equipment

Type

Code

TT-210

P19915

Accessory for mounting on DIN rail

WG-35 ... WG-210

PA-TC/WG

P19921

Panel adapter

RGU-10 RA

Panel adapter

M59991

PA-TC/WG

Panel adapter

REC 2P REC 4P

RGU-RA

GU72-D RA

Earth leakage and overload/short circuit protection systems with self-reclosure

P.2

Dimensions / Connections

P2-27

P.2 Earth leakage and overload/short circuit protection systems with self-reclosure

Dimensions / Conexiones

WRU-35-RA

P2-28

WRU-25-RA

WRU-25-RA-MT

WRU-RM

WRU-RT

WRU-25-2R

WRKRT-25T

MCB.P MT-2 Poles

RRM-P MT-4 Poles

WRT-6-25

Earth leakage and overload/short circuit protection systems with self-reclosure

P.2

Dimensions / Conexiones

RRM-C

P2-29

Earth leakage and overload/short circuit protection systems with self-reclosure

P.2 Dimensions / Conexiones

WRGMT-C2

RGMT

CBS-8

P2-30 WRGMT-C4

RGST-2

Con contactor RGST-4

RGU-10-RA

Earth leakage and overload/short circuit protection systems with self-reclosure

P.2

Dimensions / Conexiones

Con MT

P2-31

cod. C3P021-01

Earth leakage and overload/short circuit protection systems with self-reclosure

P.2

P2-32

Vial Sant Jordi, s/n 08232 Viladecavalls Barcelona (Spain) Tel. (+34) 93 745 29 00 Fax: (+34) 93 745 29 14 e-mail: [email protected] web: www.circutor.com

CIRCUTOR se reserva el derecho a modificar el contenido de este catálogo sin previo aviso CIRCUTOR no asume ninguna responsabilidad de cualquier daño causado a personas o materiales, debido a un uso erróneo o inapropiado de estos productos.

Diseño: Comunicación • CIRCUTOR, SA

Self Reclosing Breaker Catalogs.pdf

There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. Self Reclosing Breaker Catalogs.pdf. Self Reclosing Breaker Catalogs.pdf. Open. Extract. Open with. Sign In. Main menu.
Missing:

3MB Sizes 10 Downloads 133 Views

Recommend Documents

pdf breaker freeware
File: Pdf breaker freeware. Download now. Click here if your download doesn't start automatically. Page 1 of 1. pdf breaker freeware. pdf breaker freeware. Open.

ZooKoo Osram Night Breaker Laser.pdf
NIGHT BREAKER® LASER lamps. shine more light on the street. thanks to innovative laser ablation. technology, an improved. filament and pure xenon gas filling. More light and improved visibility. can help drivers identify and react. to traffic hazard

gsa captcha breaker cracked.pdf
can import database of other captcha software to this. tool. 5.It submits captcha at a success rate of more than. 90%. 6.Incase it fails to identify a particular captcha then it. sends to online captcha solving services or lets us to. solve it manual

APTT Ice Breaker Activities.pdf
Loading… Page 1. Whoops! There was a problem loading more pages. Retrying... APTT Ice Breaker Activities.pdf. APTT Ice Breaker Activities.pdf. Open. Extract.

Watch The Breaker Upperers (2018) Full Movie Online Free ...
Watch The Breaker Upperers (2018) Full Movie Online Free .MP4_________.pdf. Watch The Breaker Upperers (2018) Full Movie Online Free .MP4_________.

Watch Breaker Morant (1980) Full Movie Online.pdf
There was a problem loading more pages. Retrying... Watch Breaker Morant (1980) Full Movie Online.pdf. Watch Breaker Morant (1980) Full Movie Online.pdf.

Simple Energy-Tripped Circuit Breaker with ... - Linear Technology
Simple Energy-Tripped Circuit Breaker with Automatic. Delayed Retry. Design Note 495. Tim Regan. 10/11/495. Figure 1. Energy-Tripped Circuit Breaker Trips ...

record-breaker-2015-slides-host-us.pdf
record-breaker-2015-slides-host-us.pdf. record-breaker-2015-slides-host-us.pdf. Open. Extract. Open with. Sign In. Main menu.

record-breaker-2016-date-a-thon-recipes-us.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item.

Watch Breaker' Morant (1980) Full Movie Online Free ...
Watch Breaker' Morant (1980) Full Movie Online Free .Mp4______________.pdf. Watch Breaker' Morant (1980) Full Movie Online Free .Mp4______________.

Airport self check self check self check-in
then the admin will update its details in the panel and if the flight gets .... Microsoft SQL Server 2005 is comprehensive, integrated data management and ...

record-breaker-2016-date-a-thon-recipes-04-pears-us.pdf ...
record-breaker-2016-date-a-thon-recipes-04-pears-us.pdf. record-breaker-2016-date-a-thon-recipes-04-pears-us.pdf. Open. Extract. Open with. Sign In.