SPECIFICATION OIL IMMERSED TRANSFORMER 400 kVA 3Ph 50Hz 22000 – 400/230 V.

FM – EGD – 01 - 09 Rev. 00

Page 1/7

TRANSFORMER TECHNICAL SPECIFICATION 1. SPEC No : T0400200609 2. CUSTOMER : 3. REQUIREMENT :

Quantity

1

kVA

Phase

400

3

4. SCOPE : This specification covers oil immersed transformer X Core type Shell type

Description Hz. 50

X

Voltage 22000 - 400/230

Natural self - cooled Forced - air - cooled Forced - oil - forced - air cooled

The transformer will be designed suitable for used X Outdoor installation With cable end box Indoor installation X Without cable end box On the system voltage 3.3 kV. 12 kV. 6.6 kV. X 22 kV. 11 kV. 24 kV. 33 kV. 5. STANDARD : The transformer , all equipment and materials shall be manufactured and tested in accordance with the latest applicable standard specifications and codes in the following list :

X

ANSI American Nation Standards Institute Incorporated (ANSI.C57.12) IEEE Institute of Electrical and Electronic Engineers NEMA National Electrical Manufacture’s Association ASTM American Society of Testing Materials VDE Regulation and DIN Standard (VDE 0532/11) IEC International Electrotechnical Commission (Publication 60076-1 to 60076-5) BSI British Standard Institution (BS 171-1 to 171-5) TIS.384-2543

FM – EGD – 01 - 09 Rev. 00

Page 2/7

TRANSFORMER TECHNICAL SPECIFICATION 6. SERVICE CONDITION The transformer and accessories shall be designed and constructed for installation the following conditions : Altitude : up to 1000 M above sea level Ambient : air temperature 40° C maximum 35° C average on one day 7. RATING High Voltage Tension : Low Voltage Tension : Tapping : Range Winding Location

22000 V. 400/230 V. -4x2.5% X ± 2x2.5% HV winding LV winding Adjusted inside the transformer tank Adjusted outside the transformer tank X On the top of the transformer cover. On the side of the transformer thank X DIN 42530,42531,42539 On the top of the transformer cover On the side of the transformer tank Inside the cable box

X X

HT and LT Bushing : Accordance with Mounted

X

Vector Group of Polarity : Dyn11 Frequency : 50 Hz. Operation duty : Continuous Operation ( DB ) Neutral point of the star winding will be designed for X

100% accessible loading 50% accessible loading

8. LOSS AND IMPEDANCE VOLTAGE : The guaranteed losses and impedance voltage of the offered transformer shall comply with the figures in the table below : Rating kVA

No load loss

Load loss at 75° C

Voltage at 75° C

400

1000

61000

4.0

FM – EGD – 01 - 09 Rev. 00

Watt loss

Percent Impedance

Page 3/7

TRANSFORMER TECHNICAL SPECIFICATION 9. TRANSFORMER CONSTRUCTION Tank Each transformer shall be provided with a steel case of substantial construction , which shall be oil-tight and gas tight. The tank shall be capable of withstanding , without leakage or permanent distortion , a pressure of+5 p.s.i and shall withstand continuously a vacuum of 5 p.s.i inside of the tank. The tank cover shall be provided with suitable hand holes , if required. A grounding pad shall be provided on the tank wall near the base. Core Core shall be constructed of high quality , nonaging , high permeability silicon steel and designed to accessible loading 110% rated voltage without making injury to the transformer core. The steel shall be in thin laminations , annealed after cutting and rolled to insure smooth surface at the edges. Both sides of each sheet shall be insulated with a durable , heat resistant baked enamel or varnish. The cores shall be rigidly clamped with positive locking devices to insure adequate mechanical strength to support the windings and reduce vibration to a minimum during operation. Windings The design , construction and treatment of winding shall give proper consideration to all service factor , such as high dielectric and mechanical strength of insulation coil characteristic , uniform electrostatic flux distribution prevention of corona formation , and minimum restriction to free oil circulation. For transformer 1000 kVA and above the completed assembly of core and coil shall be tighted rigidly with the pressure ring made injury and shall be dried in a vacuum sufficient to insure elimination of air and moisture within the insulating structure. After the drying , process , assemble shall be immediately impregnated with dry oil. Insulation class of winding as below :

FM – EGD – 01 - 09 Rev. 00

Terminal

Insulation class (kV)

Low frequency test (kV)

HV.

24

50

125

LV.

-

3.0

-

Neutral

-

3.0

-

BIL (kV)

Page 4/7

TRANSFORMER TECHNICAL SPECIFICATION The insulation resistance between winding and earth tested by Meggar ohm. Meter not less than 2500 Vdc P-E not less than 1000 M ohm. S-E not less than 1000 M ohm. P-S not less than 1000 M ohm. At the ambient temperature 32° C and relative humidity 80% Bushing The bushing shall conform and be located to the requirement of the reference standard. Basic impulse insulation level (BIL) for bushings : HV. 125 kV HV. Neutral kV LV. 30 kV LV. Neutral 30 kV Transformer oil The transformer oil shall be will filtered and the dielectric strength before filling in transformer tank is not less than 30 kV / 2.5 mm. gap as tested by the method specified by ASTM D877 or IEC 156. The dielectric strength of the sample of insulating oil taken from a new transformer shall not be less than 27 kV : when measured in accordance with ANSI Standard Method of testing Electrical Insulating Oil C59.2-1966 or equal. Terminal Arrangement H.T. and L.T. bushings shall be equipped with solderless pad type connectors for AL. And CU. Conductor size as follow :

Terminal

Transformer Rating kVA

HV. LV. Neutral

400

Size (mm2)

diameter (mm)

Number of Circuits

35 - 120

7.5 – 16.0

1

120 - 240

12.9 – 20.2

4

120 - 240

12.9 – 20.2

4

Applicable to AL. and Cu. Conductors

Tank cleaning and Painting All surfaces shall be thoroughly cleaned by chemical. Interior surface shall be finished with oil - resisting point. Exterior surface shall be painted with a primer coat and two (2) finish weather – resisting coats , Gray gloss Enamel Tys NC – G001

FM – EGD – 01 - 09 Rev. 00

Page 5/7

TRANSFORMER TECHNICAL SPECIFICATION 10. TEMPERATURE : Average winding temperature rise by resistance method when carrying max. continuous rated capacity : 65° C Average top oil continuous rated capacity : 60° C Hottest spot winding temperature rise when carrying max. continuous rated capacity : 80° C 11. ACCESSORIES : The transformer shall equipped with the following accessories : X Oil drain , filter press sampling valve. X Liquid level gauge X Upper filter press connection X Off-load tap changer X Lifting lugs. X Tank grounding provision. X Name plate. Oil thermometer. Dehydrating breather Buchholz relay X Mechanical Pressure relief device

Other standard accessories as per enclosed drawing. 12. TEST : Each transformer shall be given the following test inaccordance with the reference standard. 1. Measurement of insulation resistance 2. Separate source AC withstand voltage test 3. Induced AC voltage test 4. Measurement of winding resistance 5. Measurement of voltage ratio and check of phase displacement 6. Measurement of no-load loss and current 7. Measurement of short – circuit impedance and load loss 8. Temperature rise , if required. We shall furnish four certified copies of test reports showing all the above tests at our expenses.

FM – EGD – 01 - 09 Rev. 00

Page 6/7

SPEC 400kVA T04002006 STD.PDF

STANDARD : The transformer , all ... standard specifications and codes in the following list : ANSI American ... VDE Regulation and DIN Standard (VDE 0532/11).

297KB Sizes 7 Downloads 203 Views

Recommend Documents

Group 284 Spec. 260 Spec. 288 Spec. 237 Spec. 265 ...
0-Chan Dimr. Use. Group. Position #. Special. Color. 1. 284. 1. Spec. 2Bm 19. 6x16 ... 36° Source Four R02. 34. 403. K. Front. 1Bm 12. 36° Source Four R08 ...

Undertale Spec Script.pdf
Whoops! There was a problem loading more pages. Retrying... Undertale Spec Script.pdf. Undertale Spec Script.pdf. Open. Extract. Open with. Sign In. Details.

CS4 Spec Sheet.pdf
Advanced design. software allows ... Designed and Optimized for Post 2009 Digital TV Frequencies. The ClearStreamTM 4 ... CS4 Spec Sheet.pdf. CS4 Spec ...

CIFF Spec ver1.0 Rev03 - GitHub
Regulations for the Manipulation of CIFF Image Objects 4. A. ... Among the regulations stipulated by the CIFF (Camera Image File Format), the present document.

GO7 Spec Sheet.pdf
Geotab GO7TM - The World's Only Expandable Plug-&-Play Platform. GO7TM Device. GO7TM is a small yet extremely powerful. telematics measurement tool.

Wagtail 'TumblrField' spec -
lessthanideal solutions like permitting arbitrary blobs of HTML within the field) ... as bold / italic text and links, but not image embedding or heading types;.

Wagtail 'TumblrField' spec -
lessthanideal solutions like permitting arbitrary blobs of HTML within the field) ... On submitting the form, these fields will be validated according to each block ...

d800-spec-sheet.pdf
Whoops! There was a problem loading more pages. Whoops! There was a problem previewing this document. Retrying... Download. Connect more apps.

BGP Type Flow Spec BGP Flow Provider Flow Spec BGP ... - Groups
BGP Type Flow Spec. BGP Flow Provider. Flow Spec. BGP Flow web resource. (New). BGP Flow. Decoder. (New). BGP. Driver. (New). ONOS. Flow Rule.

Donnington spec TT Jn15.pdf
Website www.sm-t.co.uk Emails [email protected]. The Donnington the ideal parking lift for parking space problems. All businesses need to ...

panasonic-ncr18650-ga-spec-sheet.pdf
the elections were by and large peaceful and declared free. and fair by both national and international observers. Financial Highlights. Profit before tax ... Chairman. Whoops! There was a problem loading this page. Retrying... panasonic-ncr18650-ga-

NSF-Tank-Spec-Material.pdf
Dow requests that customers considering use of Dow products in medical applications notify Dow so that. appropriate assessments may be conducted. Dow does not endorse or claim suitability of its products for. specific medical applications. It is the

EN-DDL10160-Spec Sheet.pdf
specifications without prior notice. ZA Sales & Distribution. Building 6 Pinewood Office Park 33. Riley Road, Woodmead Gauteng. South Africa. Tel : +27 (0) 11 ...

NSF-Tank-Spec-Material.pdf
processing latitude, good color retention and long life expectancy. • Rotational molding or injection molding. • For intermediate bulk containers, toys, general ...

SPEC 500kVA 22000 T05002009.pdf
Page 2 of 7. TRANSFORMER TECHNICAL SPECIFICATION. 1. SPEC No : T0500200909. 2. CUSTOMER : 3. REQUIREMENT : Quantity. Description.

Colorado 100cm Tallboy Spec Sheet.pdf
Colorado 100cm Tallboy Spec Sheet.pdf. Colorado 100cm Tallboy Spec Sheet.pdf. Open. Extract. Open with. Sign In. Main menu. Whoops! There was a ...

Venus G999 Dining Spec Sheet.pdf
Southbank: Eureka Tower, 7 Riverside Quay. Thomastown: Northpoint, 187 Settlement Road. Nunawading: 328 Whitehorse Road G Phone: 96826868 Web: www.gainsville.com.au Email: [email protected]. 5 Year Structural Warranty. Exclusive Design by Gainsv

Utah Bedroom Furniture Spec Sheet.pdf
Page 1 of 5. Showroom Information. Southbank: Eureka Tower, 7 Riverside Quay. Thomastown: Northpoint, 187 Settlement Road. Nunawading: 328 Whitehorse Road. Phone: 96826868 Web: www.gainsville.com.au Email: [email protected]. GAiNSViLLE. G. AMERI

Spec ONE PLUS .pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. Spec ONE ...

AIR SEA CONTAINER SPEC SHEET.pdf
AIR SEA CONTAINERS. SPECIFICATION SHEET. H. H ex. Page 1 of 1. AIR SEA CONTAINER SPEC SHEET.pdf. AIR SEA CONTAINER SPEC SHEET.pdf.

Odyssey IV spec sheet - MIT AUV Lab
mass spectrometer, manipulator and buoyancy drive. About MIT Sea Grant AUV Lab. Dedicated to the development and application of autonomous underwa-.

Spec-Selector Fire-SP510.pdf
Automatic speed control. Set to any percent speed and Jog ... some small commercial and. industrial buildings. ... Spec-Selector Fire-SP510.pdf. Spec-Selector ...

EN-DLB072D-Spec Sheet.pdf
Dimensions mm (L) x mm (W) x 72mm (H) x 85mm (OD) x. 87mm (RD) x mm. SKU Table and Ordering. SKU Code Colour lm Wattage Lumens/Watt Product Type.

JCB 3CX Spec Sheet.pdf
Cooling system Hot climate specification, pressurised 14.5 psi (1.0 bar) suction fan. Pressurised recovery tank with. integral filler neck. A. B. C. BACKHOE LOADER | 3CX. Page 4 of 12. JCB 3CX Spec Sheet.pdf. JCB 3CX Spec Sheet.pdf. Open. Extract. Op