: Headquarters

: Philippines

Hitachi Asia Ltd. (Philippines Branch)

AKS Building, 3, Kanda Neribei-cho, Chiyoda-ku, Tokyo, 101-0022, Japan TEL : <81>(3) 4345-6000 FAX : <81>(3) 4345-6914

25th Floor, Pacific Star Building, Cor. Makati & Sen. Gil. Puyat Ave., Makati, Metro Manila TEL : <63>(2) 819-7528, -7529 FAX : <63>(2) 819-7539

: Singapore

Hitachi Asia Ltd.

: Thailand

Power & Industrial Systems Group 24 Jurong Port Poad, #03-05 Cwt Distripark, Office Block, Singapore, 619097 TEL : <65>(6305) 7400 FAX : <65>(6305) 7401

: Vietnam

Hitachi Asia Ltd.(Ho Chi Minh City Office) 7th Floor, The Landmark, 5B Ton Duc Thang Street District 1, Ho Chi Minh City TEL : <84>(8) 829-9725 FAX : <84>(8) 829-9729

4th Floor, North Tower World Finance Centre, Harbour City Canton Road, Tsim Sha Tsui, Kowloon Hong Kong TEL : <852>2735-9218 FAX : <852>2375-3192

: India

Hitachi India Trading Pvt. Ltd.

Hitachi China Ltd. (Beijing Office)

Hindustan Times House (10th Floor) 18-20, Kasturba Gandhi Marg., New Delhi, 110001 TEL : <91>(11) 331-5635, 371-2817, -3953, -3958 FAX : <91>(11) 331-3742

Room 1412, Beijing Fortune Building 5 Dong San Huan BeiLu Chao Yang District, Beijing 100004 TEL : <86>(10) 6590-8851, -8852, -8853, -8854 FAX : <86>(10) 6590-8850

: Indonesia

Hitachi Asia Ltd. (Jakarta Office)

Hitachi (Shanghai) Trading Co., Ltd.

Mid Plaza 1, 10th Floor, J.I. Jend. Sudirman Kav. 10-11, Jakarta 10220 TEL : <62>(21) 574-4313 FAX : <62>(21) 574-4312

18th Floor, Rui Jin Building, No.205, Maoming Road(S) Shanghai, 200030 TEL : <86>(21) 6472-1002 FAX : <86>(21) 6415-8272

: Malaysia

Taiwan Hitachi Asia Pacific Co., Ltd.

Suite 17.3, Level 17, Menara IMC (Letter Box No.5) No. 8 Jalan Sultan Ismail, 50250, Kuala Lumpur TEL : <60>(3) 201-8751 FAX : <60>(3) 201-8757, -8758

3rd Floor, Hung Kuo Building No.167 Tun-Hwa North Road, Taipei (105) , Taiwan TEL : <886>(2) 2718-3666 FAX : <886>(2) 2718-8180

Information in this brochure is subject to change without notice.

http://www.hitachi-ies.co.jp/english/index.htm

ww

Hitachi Asia (Malaysia) Sdn. Bhd.

die

Hitachi East Asia Ltd.

Sun Red River Bldg, 6th Floor, 23 Phan Chu Trinh Street Hoan Kiem District Hanoi TEL : <84>(4) 933-3123 FAX : <84>(4) 933-3125

w.

(Ha Noi Office)

nh ath

: China

e.x

Hi tachi C i r cui t B r e ak e r s & M i n i a tu r e Ci r c u i t Br ea k er s

18th Floor, Ramaland Building, 952 Rama IV Road Bangrak, Bangkok 10500 TEL : <66>(2) 632-9292 FAX : <66>(2) 632-9299

yz

Hitachi Asia (Thailand) Co., Ltd.

For further information, please contact your nearest sales representative.

www.dienhathe.vn

Printed in Japan (H) SI-E123 (0709)

ww

Hitachi Industrial Equipment Systems Co., Ltd.

w.

die

nh ath

e.x

yz

Circuit Breakers & Miniature Circuit Breakers

www.dienhathe.vn

a ppLications such as conductors, motors, and starters.

designed for circuit protection of low-voltage distribution

They are designed for use in switchboard, control centers,

systems. They are suitable for application as main breakers and

panel boards, combination starters, and separate individual

for protection of branch and feeder circuits and connected

enclosures. In these various enclosures, they are applicable to

apparatus. These breakers provide overload protection for

the requirements of lighting, distribution, and other power

conductors and short-circuit protection for all circuit elements

circuits.

yz

Hitachi Circuit Breakers and Miniature Circuit Breakers are

e.x

c ontents

Applications..........................................................................................................................................1

Fuse-Free Breakers

New Line-up Series (Features) ........................................................................................................................... 2

nh ath

Classification and Composition ......................................................................................................................... 4 Composition in terms of Interrupting Capacity ............................................................................................... 5 Ratings and Specifications ................................................................................................................................. 6 Construction ..................................................................................................................................................... 15 Characteristics .................................................................................................................................................. 19 Caution.............................................................................................................................................................. 20 Selection ........................................................................................................................................................... 21 Accessories ........................................................................................................................................................ 25

die

Dimensions ....................................................................................................................................................... 39

Earth Leakage Breakers and Earth Leakage Relays Classification and Composition ....................................................................................................................... 67 Ratings and Specifications ............................................................................................................................... 68

w.

Construction ..................................................................................................................................................... 72 Application of Earth Leakage Relays .............................................................................................................. 75 Dimensions ....................................................................................................................................................... 76

ww

Earth Leakage Breakers for Welders ............................................................................................................ 106

Miniature Circuit Breakers

Features........................................................................................................................................................... 108 Specifications .................................................................................................................................................. 109 Characteristic curve and Compensation curve............................................................................................. 110

Residual Circuit Breakers Features............................................................................................................................................................111 Specifications .................................................................................................................................................. 112

Air Circuit Breakers (AKN, AKS, AKH series) Ordering ......................................................................................................................................................... 114 Ratings ............................................................................................................................................................ 120 Dimensions ..................................................................................................................................................... 142

www.dienhathe.vn

1

FUSE-FREE BREAKER NEW L INE-UPS WITH FULLY INTEGRATED C ONFIGURATION, A DVANCED P ERFORMANCE AND SIMPLIFIED OPERATION Hitachi Global Series

yz

Hitachi has been developing new Molded Case Circuit

breakers and these are innovative high quality breakers, new technology fulfills improving the performance and new design satisfies all application requirements

nh ath

and world customers. It's a new solution of the breakers.

w.

die

featURes

New color of the face

e.x

Breakers and now we have just launched new type circuit

Renew the color of the face of the breakers from

ww

black to brighter color, Light Gray, and the impression of the distribution panels will be improved brightly and sophisticated.

2

www.dienhathe.vn

High breaking performance

Breaking performance of standard type (F series) are lcs = 100%lcu which is world level performance of the breaking current by new solution of breaking system and new breaking system reduces thermal and

60AF

100AF

250AF

400AF

600AF

Types

F-60RB

F-100KB FXK125-S FXK125-H

F-250FB F-250KC FXK250-S FXK250-H

F-400R FX400

F-600F FX600

install accessories

Easy to install the accessories and

1000AF

1200AF

F-800R FX800

FX1000

FX1200

nh ath

Easy to

800AF

e.x

AF

yz

mechanical stress to distribution systems and they can be used any distribution system.

easy to change the specifications

Hitachi Global series provides wide range of the

frame and the varieties of accessories for customers.

die

The specifications of breakers can be changed by cassette type internal accessories. They can be

installed by users, quickly responding to changing specifications.

Dimensions are unified

Dimensions are unified for the economical and standard types, contributing to total cost reduction of the control panel.

ww

Specifications.

w.

Applicable type are stated in table of Ratings and

Breaking Capacity at 230V

Even height is unified in addition to the conventional projected area unification. This compatibility reduces the total cost in mounting panels. Interrupting capacity is also unified for the fuse-free breaker and earth leakage breaker within the frame of the same

Standard type

FX, FXK, RX, RXK Economical type

SX, SXK, EX, EXK

rated current, enabling easy, smooth replacement.

www.dienhathe.vn

3

c Lassification

and

c oMposition

Hitachi Fuse-Free Breakers are produced in the variety of types shown below. Any type can be freely chosen according to the purposes of applications and circuit conditions, making it possible to design an electric circuit with high economy and reliability.

Fuse-Free Breaker for General Purpose

L Series

High Interrupting Capacity Breaker



30A – 1600A frame

50A – 800A frame

Economical Breaker



nh ath

e.x



S Series

yz

F Series

Standard Breaker

30A – 225A frame

4

ww

w.

M Series

die

Motor Breaker

www.dienhathe.vn

30A – 800A frame

c oMposition

in

teRMs

of inteRRUpting

c apacitY

AC 230V — 240V – 30

Interrupting capacity kA (sym)

5

50 – 100 7.5

150

10

30

S-30E

F-30FB

50

S-50EB

S-50SB

14

25

60

S-60RB

F-60RB

S-100EB

S-100S

42

S-100SB

S-225SB, SXK225

400

SX400, S-400S

600

SX600, S-600S

50

85

100

L-100E

FXK250-S F-250FB

FXK250-H F-250KC

L-225E

FX400, F-400R

L-400E

FX600, F-600F

L-600E

F-1600CB, F-1600B, F-1600E

AC 380V — 440V Transformer capacity (kVA)

– 50

75 – 100

Interrupting capacity kA (sym)

1.5

2.5

30

S-30E

F-30FB

50

S-50EB S-50SB

60

S-60RB

100 125

5

200 – 500

7.5

10

15

750 – 1000

18

die w.

600

25

30

35

50

2500 – 3500

85

125

175

L-50E

FXK125-S

S-225SB, SXK225

400

22

1500 – 2000

F-60RB

S-100S, S-100SB

225 250

FXK250-S F-250FB

FXK125-H

L-100E

FXK250-H F-250KC

L-225E

SX400 S-400S

FX400 F-400R

L-400E

SX600 S-600S

FX600 F-600F

L-600E

SX800, S-800S

FX800 F-800R

F-800RH

L-800E

FX1000, FX1200, F-1000K, F-1200K, F-1000C, F-1200C

ww

1600

FX800 F-800RH L-800E F-800R

e.x

1600

nh ath

FX1000, FX1200, F-1000K, F-1200K, F-1000C, F-1200C

1000 – 1200

175

FXK125-H

1000 – 1200

800

125

FXK125-S

SX800 S-800S

800

Frame (AF)

35

2000 – 3000

L-50E

100 125 225 250

750 – 1500

200 – 500

yz

Frame (AF)

Transformer capacity (kVA)

F-1600CB, F-1600B, F-1600E

F Series

S Series

www.dienhathe.vn

5

R atings Table 1

F

and

specifications

series Type

F-30FB

F-60RB

F-60R

F-100S

FXK125-S

FXK125-H

F-100KB

Appearance

Number of poles

2

3

3

4

4

2 (*1)

3

3 5 10 15 20 30

15 20 30 40 50 60

15 20 30 50 60 75 100

15 20 30 40 50 63 75 100 125

Rated Insulation Voltage Ui (V)

690

690

690

690

Rated Impulse withstand Voltage Uimp (kV)

6

6

8

8

690V







440V

2.5 / 1

10 / 10

10 / 5

DC

Dimensions (mm)

d c

b

a

10 / 10

10 / 5

30 / 30

50 / 50

10 / 10

10 / 5

30 / 30

50 / 50

380V

2.5 / 1

10 / 10

10 / 5

30 / 30

240V

7.5 / 2

25 / 25

35 / 18

50 / 50

100 / 100

85 / 85

230V

7.5 / 2

25 / 25

35 / 18

50 / 50

100 / 100

85 / 85

250V

2.5 / 1



5/2







125V

5/2



7.5 / 2







a

52

75

52

75

100

120

b

130

130

150

c

60

60

60

d

84

84

85

0.6

0.53

0.74



25 / 13



40 / 20



90

150

150 68

86

94

94

106

1.4

1.4

1.4

1.4

● (*2)

○ (*3) ○ (*3) ○ (*3)

○ (*3) ○ (*3) ○ (*3)









TB2

○ ○

○ ○

STB

STB-2M

STB-2M

STB-1B

Front Terminal

2.3

Front Terminal ● (*2)

○ ○

○ ○ ○ ○ ○ ○

STB-3H STB-2S (Up to 50A) STB-2S (Up to 50A) (Up to 50A : STB-2D) BSD-3S (60A or more) BSD-3S (60A or more)

STB-3J (Up to 50A : STB-2)

BSD







Flush Mounting Base Assembly

GKW(STB)













GK • GKW(BSD)







○ (Up to 50A)

○ (Up to 50A)



Plug-in Mounting Base Assembly Drawout Assembly

PK







○ (60A or more)

○ (60A or more)



PDK











— MIW-3D

MIW

MIW-2E

Motor-operating Mechanism

MMK-S



MMK-C



MMK



Lock Cover

LC

LC-2E

HL HA

Front Type Rear Type

TMC Short Type

Trip Button

MIW-2C

MIW-3H

MIW-3H



























LC-2C

○ ○

LC-2C



○ ○

HA-107

HA-104





HA-106



HA-108

HA-108

HMS12





LC-1B

LC-2E

HMS12



TMC-1

HM-57

TMC-1





HM-S13

HM-S13

HM-S11

TMC-2C

TMC-2C

TMC-2C

TMC-3C —

TMC-1S

TMC-1S









Long Type

TMC-2D

TMC-2D











BTC

BTC-1

BTC-2C

BTC-2C

BTC-2C

BTC-3C





IEC Rail 35 mm Automatic Tripping Device

MIW-1C







ww

Terminal Cover

HM

MIW-2E

w.

Handle Lock Handle Operating Mechanism

BTC-1









Full Magnetic

Full Magnetic

Full Magnetic







www.dienhathe.vn



Thermal-Magnetic Thermal-Magnetic ●

● : Standard ○ : Option 2-pole types marked with (*1) are supplied in 3-pole type. Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF. Flush Mounting Base Assembly, GKW are standard in case of up to 250AF and FX400. Please state that number of poles of breakers when order MIW. Installation of phase separators is required in case of types marked (*2). Tripping system of F-1000K and F-1200K are induction heat system, please state frequency when ordering. For DC use, the tripping character is only instantaneous trip in case of F-1000K and F-1200K. The accessories marked (*3) can be installed by customers.

6



68



TB

— 120

○ ○ ○ ○ ○ ○

SHT

Front Terminal

50 / 50

90

● (*2)

UVT

AUX

40 / 20

○ ○ ○

Shunt Trip

Auxiliary Switch

1.3



Front Terminal

Undervoltage Trip

AL

0.96

25 / 13

Front Terminal

○ ○ ○ ○

Alarm Switch

Mechanical Interlock

Attention

— 50 / 50

2.5 / 1

Phase Separator for Line Side

Exterior Accessories

30 / 30

2.5 / 1

0.48

Rear-connecting Stud

8



415V

Net Weight (kg)

Terminal Block

4 15 20 30 40 50 60 75 100

400V

Standard Connection Type

Interior Accessories

yz

(Icu/Ics)

3

690

e.x

IEC 60947-2

2 (*1)

15 20 30 40 50 63 75 100 125



nh ath

AC

die

Rated Breaking Capacity (kA)

1. 2. 3. 4. 5. 6. 7. 8. 9.

2

Rated Current (A) (Base ambient temperature 40ºC)

Full Magnetic ●

FXK250-S

F-250FB

2 (*1)

3

4

FXK250-H

2 (*1)

F-250KC

3

4

F-400R

2 (*1)

3

FX400

4

F-600F

2 (*1)

3

2 (*1)

3

FX600

4

3

125 150 175 200 225 250

250 300 300 400

200 / 225 / 250 300 / 350 / 400 adjustable

500 600

300 / 350 / 400 500 / 600 adjustable

690

690

690

690

690

690

8

8

8

8

8

8















yz

125 150 175 200 225 250

30 / 30

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

30 / 30

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

50 / 50

100 / 100

100 / 100

100 / 100

100 / 100

100 / 100

50 / 50

85 / 85

100 / 100

85 / 85

100 / 100

50 / 50

85 / 85

100 / 100

85 / 85

100 / 100

25 / 13





40 / 20





40 / 40





25 / 13





40 / 20





40 / 40





105

140

105

140

68

103

68

103

95

127

95

127

1.6

3.1

1.6

3.1

165

Front Terminal

257

Front Terminal

● (*2)

○ ○ ○

○ (*3) ○ (*3) ○ (*3)

○ ○ ○





○ ○

○ ○











○ ○





MIW-4M

MIW-4H

MIW-4M







— LC-4H

LC-4J



HL-4J







40 / 40







280

210

210

257

274

274

103

103

103

133

8.2



5.1

5.9

Front Bar Terminal

141 10

141 13

Front Bar Terminal

9.7 Front Bar Terminal

● (*2)

● (*2)

● (*2)

● (*2)

○ ○ ○ ○ ○ ○

○ (*3) ○ (*3) ○ (*3) ○ ○ ○

○ ○ ○ ○ ○ ○

○ (*3) ○ (*3) ○ (*3) ○ ○ ○

























○ (GK)

○ (GK)



○ (GK)

















MIW-5D

MIW-5F

MIW-5

MIW-5G

























LC-4H











HL-5

HL-5

HL-6

HL-6

w.



LC-4J

6.1

MIW-4H



HL-4J

133 5.3

40 / 40

140

die





103

Front Bar Terminal

● (*2)

○ (*3) ○ (*3) ○ (*3)

185

100 / 100



nh ath

165

140

e.x

30 / 30 30 / 30

HA-210

HA-206

HA-210

HA-206

HA-405

HA-406

HA-402

HA-402

HM-S25

HM-S21

HM-S25

HM-S21

HM-405

HM-406

HM-402

HM-407

TMC-4H

TMC-4J

TMC-4H

TMC-5B

TMC-5B

TMC-5D

TMC-5D



TMC-4JS



























BTC-4J



BTC-4J



BTC-5B

BTC-5B





— Thermal-Magnetic ●

ww

TMC-4J TMC-4JS











Thermal-Magnetic

Thermal-Magnetic

Electronic Relay

Thermal-Magnetic

Electronic Relay











www.dienhathe.vn

7

Table 1

F

series Type

F-800R

FX800

F-800RH

F-1000K

F-1000C

Appearance

Number of poles

3

4

3

3

4

3

4

3

4

700 800

1000

500 / 600 / 700 800 / 900 / 1000 adjustable

Rated Insulation Voltage Ui (V)

690

690

690

690

690

Rated Impulse withstand Voltage Uimp (kV)

8

8

8

8

8











690V

DC

85 / 43

400V

50 / 50

50 / 50

85 / 43

380V

50 / 50

50 / 50

85 / 43

240V

100 / 100

100 / 100

230V

100 / 100

100 / 100

125 / 32 125 / 32



40 / 40



40 / 10







40 / 40



40 / 10





a

210

280

210

210

280

210

b

274

274

c

103

103

d

141

141 13.5

● (*2)

Alarm Switch

AL

Auxiliary Switch

AUX

TB2

○ ○ ○ ○ ○ ○

Shunt Trip

SHT

Undervoltage Trip

UVT TB STB



BSD



GKW(STB)



GK • GKW(BSD)

○ (GK)

11

274

Front Bar Terminal

280

280 410

103

150

150

141

190

190

10.5

13.5

Front Bar Terminal

26

33

Front Bar Terminal

26

33

Front Bar Terminal

● (*2)

● (*2)

● (*2)

● (*2)

○ (*3) ○ (*3) ○ (*3) ○ ○ ○

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○

























○ (GK)

○ (GK)

○ (GK)

○ (GK)









PK



Drawout Assembly

PDK











MIW

MIW-5

MIW-5G

MIW-5

MIW-8

MIW-8

MMK-S











MMK-C











MMK









— —

Lock Cover

LC









Handle Lock

HL

HL-6

HL-6

HL-6





Handle Operating Mechanism

HA

HA-402

HA-402

HA-402

HA-801

HA-801

HM-402

HM-407

HM-402





TMC-5D

TMC-5D

TMC-5D

TMC-6

TMC-6

HM TMC

Front Type

Short Type

Rear Type

BTC

Long Type

IEC Rail 35 mm Automatic Tripping Device Trip Button







































Thermal-Magnetic

Electronic Relay

Thermal-Magnetic

Thermal-Magnetic

Electronic Relay











ww

Terminal Cover

1. ● : Standard ○ : Option 2. 2-pole types marked with (*1) are supplied in 3-pole type. 3. Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF. 4. Flush Mounting Base Assembly, GKW are standard in case of up to 250AF and FX400. 5. Please state that number of poles of breakers when order MIW. 6. Installation of phase separators is required in case of types marked (*2). 7. Tripping system of F-1000K and F-1200K are induction heat system, please state frequency when ordering. 8. For DC use, the tripping character is only instantaneous trip in case of F-1000K and F-1200K. 9. The accessories marked (*3) can be installed by customers.

8

210

410

Plug-in Mounting Base Assembly

Motor-operating Mechanism

Attention

125 / 32

125 / 32



10.5

Mechanical Interlock Exterior Accessories

125 / 63



Phase Separator for Line Side

Flush Mounting Base Assembly

85 / 22 85 / 22

40 / 40

Front Bar Terminal

Rear-connecting Stud

85 / 22

85 / 22

40 / 40

Net Weight (kg)

Terminal Block

85 / 22 85 / 22

125V

Standard Connection Type

Interior Accessories

125 / 63

85 / 22

85 / 22

250V

die

Dimensions (mm)

d c

b

a

85 / 43

50 / 50

e.x

(Icu/Ics)

50 / 50

50 / 50

nh ath

AC

IEC 60947-2

50 / 50

415V

w.

Rated Breaking Capacity (kA)

440V

yz

700 800

400 / 450 / 500 600 / 700 / 800 adjustable

Rated Current (A) (Base ambient temperature 40ºC)

www.dienhathe.vn

R atings

FX1000

3

F-1200K

F-1200C

3

4

FX1200

3

4

F-1600CB

3

and

S pecifications

F-1600B

3

4

F-1600E

3

4

3

4

600 / 700 / 800 1000 / 1200 adjustable

800 / 900 / 1000 1200 / 1400 / 1600 adjustable

1000 1200 1400 1600

800 / 900 / 1000 1200 / 1400 / 1600 adjustable

690

690

690

690

690

690

690

8

8

8

8

8

8

8













45 / 34

yz

1200

600 / 700 / 800 1000 / 1200 adjustable

500 / 600 / 700 800 / 900 / 1000 adjustable

85 / 22

85 / 22

85 / 85

85 / 22

85 / 22

85 / 64

85 / 22

85 / 22

85 / 85

85 / 22

85 / 22

85 / 64

85 / 85

85 / 22

85 / 22

85 / 85

85 / 22

85 / 22

100 / 75

85 / 85

85 / 22

85 / 22

85 / 85

85 / 22

85 / 22

100 / 75

e.x

85 / 85 85 / 85

125 / 125

125 / 32

125 / 32

125 / 125

125 / 125

125 / 32

125 / 32

125 / 125



40 / 10









40 / 10







210

210

410

280

210

280

410

210

410

410

150

150

150

150

190

190

190

190

Front Bar Terminal

26

33

Front Bar Terminal

26

33

Front Bar Terminal

● (*2)

● (*2)

● (*2)

○ (*3) ○ (*3) ○ (*3) ○ ○ ○

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○



















○ (GK)

○ (GK)

○ (GK)











MIW-8

MIW-8





















TMC-6B

TMC-6









40 / 10





40 / 10





210

280

210

410

280

210

280

410

370

150

150

140

190

190

37

49

Front Bar Terminal

37

191 49

Front Bar Terminal

27

36

Front Bar Terminal

● (*2)

● (*2)

● (*2)



○ (*3) ○ (*3) ○ (*3) ○ ○ ○

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ —

























○ (GK)

○ (GK)

○ (GK)

















MIW-8

MIW-8

MIW-8D

MIW-8D

○ ○





































○ ○ ○ ○









HA-801

HA-801

HA-801











TMC-6

TMC-6B

















































Electronic Relay

Thermal-Magnetic

Electronic Relay

Electronic Relay

Electronic Relay

Magnetic

Electronic Relay























HA-801

ww



Front Bar Terminal

die

○ HA-801

125 / 94 125 / 94

○ (GK)

w.

○ HA-801

26

125 / 32

125 / 32

nh ath

26

125 / 32

125 / 32

www.dienhathe.vn

9

Table 2

S series Type

S-30S

S-30E

S-50E

S-50EB

S-50SB

S-60RB

S-100EB

Appearance

Number of poles

2

3

3

2

3

2

3

2

3

2

3

2

3

3 5 10 15 20 30

5 10 15 20 30 40 50

5 10 15 20 30 40 50

5 10 15 20 30 50

5 10 15 20 30 50 60

60 75 100

Rated Insulation Voltage Ui (V)

500

500

500

500

690

690

250

Rated Impulse withstand Voltage Uimp (kV)



4



4

6

6

6

690V















440V









2.5 / 1

5/2



415V



1.5 / 1



1.5 / 1

2.5 / 1

5/2



400V

1.5 / 1

1.5 / 1

1.5 / 1

1.5 / 1

2.5 / 1

5/2



380V

1.5 / 1



1.5 / 1



2.5 / 1

5/2



240V

2.3 / 1.3



2.3 / 1.3



7.5 / 2

10 / 3

10 / 3

230V

2.5 / 1.3

5/2

2.3 / 1.3

250V







125V







(Icu/Ics)

DC

50

75

75

95

96

96

60

60

60

d

79

76

79

0.32

0.47

Front Terminal

Phase Separator for Line Side (*2)

0.25

0.37

0.47

0.32

7.5 / 2

10 / 3

10 / 3



2.5 / 1



2.5 / 1



2.5 / 1



5/2



5/2



5/2



52

75

52

75

52

75

50

75

96

130

130

60

60

60

60

76

84

84

84

0.25

0.37

0.48

0.6

Front Terminal Front Terminal Front Terminal Front Terminal

0.5

130

0.7

0.5

0.7

Front Terminal

Front Terminal









AL





Auxiliary Switch

AUX



Shunt Trip

SHT



○ ○ ○



○ ○ ○

○ ○ ○ ○

○ ○ ○ ○

○ ○ ○ ○

Undervoltage Trip

UVT















TB









TB2









○ ○

○ ○

○ ○

STB









STB-2M

Rear-connecting Stud



STB-3K STB-3K (Up to 50A :STB-2M) (Up to 50A :STB-2M)

BSD













Flush Mounting Base Assembly

GKW(STB)















GK • GKW(BSD)















Plug-in Mounting Base Assembly Drawout Assembly

PK



PDK



Motor-operating Mechanism

MIW



MMK-S



MMK-C



MMK

— LC-0B —

Lock Cover

LC

Handle Lock

HL

Handle Operating Mechanism

HM

Front Type Rear Type

TMC Short Type Long Type

IEC Rail 35 mm Automatic Tripping Device Trip Button







MIW-2E

MIW-2E

MIW-2E





































LC-03

LC-0B

LC-03

LC-2G

LC-2G

LC-2G







HL-2G

HL-2G

HL-2G



BTC



































TMC-0G

TMC-0C TMC-0A

TMC-0G









TMC-1S

TMC-1S

TMC-1S









TMC-2D

TMC-2D

TMC-2D









BTC-1

BTC-1

BTC-1















Full Magnetic

Full Magnetic

Full Magnetic

Full Magnetic

Full Magnetic

Full Magnetic

Full Magnetic















TMC-0C

TMC-0A

ww

Terminal Cover

HA





w.

Mechanical Interlock

HA-108 —

HM-S12 TMC-1

HA-108 —

HM-S12 TMC-1

● : Standard ○ : Option 2-pole types marked with (*1) are supplied in 3-pole type. Please state "For DC" in case of DC use . Especially, state please state kind of the power supply in case of from 30AF to 100AF. Please state that number of poles of breakers when order MIW. Installation of phase separators is required in case of types marked (*2). The accessories marked (*3) can be installed by customers.

10



Alarm Switch

Terminal Block

Attention

50

c

Net Weight (kg)

Exterior Accessories

75

b

Standard Connection Type

Interior Accessories

50

5/2

die

Dimensions (mm)

a

d c

b

a

e.x

IEC 60947-2

nh ath

AC

yz

3 5 10 15 20 30

Rated Breaking Capacity (kA)

1. 2. 3. 4. 5. 6.

2

Rated Current (A) (Base ambient temperature 40ºC)

www.dienhathe.vn

HA-108 —

HM-S12 TMC-1

R atings

S-100SB

2

S-100S

3

S-225SB

2

3

2 (*1)

3

SXK225

2 (*1)

3

S-400S

2 (*1)

SX400

3

S-600S

2 (*1)

3

125 150 175 200 225

250 300 350 400

200 / 225 / 250 300 / 350 / 400 adjustable

2 (*1)

3

and

SX600

S-800S

3

S pecifications

SX800

3

3

500 600

300 / 350 / 400 500 / 600 adjustable

700 800

400 / 450 / 500 600 / 700 / 800 adjustable 690

60 75 100

690

690

690

690

690

690

690

690

690

6

6

6

6

8

8

8

8

8

8





















10 / 3

10 / 3

15 / 8

15 / 8

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

10 / 3

10 / 3

15 / 8

15 / 8

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

10 / 3

10 / 3

15 / 8

15 / 8

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

10 / 3

10 / 3

15 / 8

15 / 8

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

36 / 18

35 / 9

25 / 7

35 / 18

35 / 18

50 / 25

50 / 25

50 / 25

50 / 25

85 / 43

85 / 43

85 / 43

85 / 43

25 / 7

35 / 18

35 / 18

50 / 25

50 / 25

5/2



5/2



10 / 5



10 / 5



25 / 13





7.5 / 2



7.5 / 2



15 / 8



15 / 8



25 / 13





75

65

105

105

140

140

130

150

165

165

257

257

60

60

60

68

103

103

84

85

85

95

133

133

1.6

1.6

Front Terminal

Front Terminal

Front Terminal

○ ○ ○ ○

● (*2)

● (*2)

○ ○ ○

○ (*3) ○ (*3) ○ (*3)





○ ○

○ ○





0.53

0.74

Front Terminal

0.7

● (*2)

○ ○ ○ —

○ ○

90

1



○ ○ ○

STB-3K STB-3H (Up to 50A :STB-2M) (Up to 50A : STB-2D) —

































MIW-2E

MIW-2C

MIW-4F



















5.3

6.1

5.1

50 / 25

50 / 25



40 / 20







40 / 20





40 / 20







40 / 20



5.9

nh ath

52

e.x

35 / 9

yz

60 75 100

125 150 175 200 225

210

210

210

210

274

274

274

274

103

103

103

103

141

141

141

141

10

9.7

10.5

11

Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal ● (*2)

● (*2)

● (*2)

● (*2)

● (*2)

● (*2)

○ ○ ○ ○ ○ ○

○ (*3) ○ (*3) ○ (*3) ○ ○ ○

○ ○ ○ ○ ○ ○

○ (*3) ○ (*3) ○ (*3) ○ ○ ○

○ ○ ○ ○ ○ ○

○ (*3) ○ (*3) ○ (*3) ○ ○ ○





































○ (GK)

○ (GK)



○ (GK)

○ (GK)

○ (GK)





























MIW-4L

MIW-5D

MIW-5F

MIW-5

MIW-5G

MIW-5

MIW-5G











































die



LC-2C

LC-4E



HL-4E

HA-108

HA-104

HA-207

HA-209

HA-405

HA-406

HA-402

HA-402

HA-402

HA-402



HM-S22

HM-S23

HM-405

HM-406

HM-402

HM-407

HM-402

HM-407



HM-S12

LC-2F













HL-2F

HL-5

HL-5

HL-6

HL-6

HL-6

HL-6

w.

LC-2G HL-2G

TMC-2C

TMC-4K

TMC-4J

TMC-5B

TMC-5B

TMC-5D

TMC-5D

TMC-5D

TMC-5D



TMC-4JS

TMC-4JS













TMC-2D



















BTC-1

BTC-2C

BTC-4G

BTC-4J

BTC-5B

BTC-5B

























ww

TMC-1 TMC-1S





Full Magnetic

Full Magnetic





Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Electronic Relay Thermal-Magnetic Electronic Relay Thermal-Magnetic Electronic Relay ●







www.dienhathe.vn









11

Table 3

L

series Type

L-50E

L-100E

L-225E

L-400E

L-600E

L-800E

Appearance

3

4

690

690

690

690

690

690

8

8

8

8

8

8













125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

400V

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

380V

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

240V

175 / 88

175 / 88

175 / 88

175 / 88

175 / 88

175 / 88

230V

175 / 88

175 / 88

175 / 88

175 / 88

175 / 88

175 / 88

250V













125V













120

c

103

103

103

123

123

133

2.5 ● (*2)

STB BSD



SHT

Undervoltage Trip

UVT TB TB2

Flush Mounting Base Assembly

GKW(STB)



GK • GKW(BSD)



Plug-in Mounting Base Assembly Drawout Assembly

PK



PDK



2.0

2.5

5.2

Front Terminal

7.0

Front Terminal

140

185

210

280

280

274

274

103

103

103

133

141

6.1

8.2

10.0

141 13.0

Front Bar Terminal Front Bar Terminal

10.5

13.5

Front Bar Terminal

● (*2)

● (*2)

● (*2)

● (*2)

● (*2)

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○































○ (GK)

○ (GK)

○ (GK)

○ (GK)





















MIW

MIW-3E

MIW-3E

MIW-5D

MIW-5D

MIW-5

MIW-5

MMK-S













MMK-C













MMK













Lock Cover

LC

LC-2C

Handle Lock

HL



Handle Operating Mechanism

HM

HA TMC

Front Type

Short Type

Rear Type

BTC

Long Type

LC-2C











HL-5

HL-5

HL-6

HL-6

HA-106

HA-106

HA-405

HA-405

HA-402

HA-402

HM-S11

HM-S11

HM-405

HM-405

HM-402

HM-402

TMC-3C

TMC-3C

TMC-5B

TMC-5B

TMC-5D

TMC-5D

























BTC-3C

BTC-3C







Full Magnetic

Full Magnetic

Thermal-Magnetic







ww

BTC-5B



BTC-5B

— —









Thermal-Magnetic Thermal-Magnetic ●



1. ● : Standard ○ : Option 2. Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF. 3. Please state that number of poles of breakers when order MIW. 4. Installation of phase separators is required in case of types marked (*2). 5. The accessories marked (*3) can be installed by customers.

12

210

257

○ ○ ○ ○ ○ ○ ○

die

AUX

○ ○ ○ ○ ○ ○ ○

Shunt Trip

Trip Button

185

d

Auxiliary Switch

Automatic Tripping Device

140 257

AL

IEC Rail 35 mm

120 150

Alarm Switch

Terminal Cover

90

150

Front Terminal

Motor-operating Mechanism

Attention

90

b

Phase Separator for Line Side (*2)

Exterior Accessories

4

125 / 32

Standard Connection Type

Mechanical Interlock

3 700 800

2.0

Rear-connecting Stud

4 500 600

415V

a

Terminal Block

3

440V

Net Weight (kg)

Interior Accessories

4 250 300 350 400

w.

Dimensions (mm)

d c

b

a

3

e.x

DC

4

nh ath

AC

(Icu/Ics)

3

125 150 175 200 225

690V

IEC 60947-2

4

15 20 30 50 60 75 100

Rated Impulse withstand Voltage Uimp (kV)

Rated Breaking Capacity (kA)

3

5 10 15 20 30 50

yz

Number of poles Rated Current (A) (Base ambient temperature 40ºC) Rated Insulation Voltage Ui (V)

www.dienhathe.vn

Thermal-Magnetic ●

R atings

Table 4

and

s pecifications

M series Type

MS-30E

MS-50EB

3

3

MS-50SB

MS-100SB

MFXK100-S

MS-225SB

MSXK225

MFXK225-S

Appearance

0.8 1.2 1.4 2 2.5 4 5 6.3 10 12 16 25 7.1 8 10 12 32 40 45 16 25 32

Rated Current (A) (Base ambient temperature 40ºC)

3

3

3

3

3

60 75 90

60 75 90

125 150 175 225

125 150 175 225

125 150 175 225 690

Rated Insulation Voltage Ui (V)

500

500

690

690

Rated Impulse withstand Voltage Uimp (kV)

4

4

6

6









690V

AC

(Icu/Ics)

Dimensions (mm)

d c

b

a





1.5 / 1

2.5 / 1





2.5 / 1

10 / 3

415V

1.5 / 1

1.5 / 1

2.5 / 1

400V

1.5 / 1

1.5 / 1

2.5 / 1

380V





2.5 / 1

240V





7.5 / 2

230V

5/2

5/2

7.5 / 2

a

75

75

75

b

96

96

130

c

60

60

60

d

76

76

84

0.37

0.6

Net Weight (kg)

0.37

Standard Connection Type AL

Auxiliary Switch

AUX SHT

Undervoltage Trip

UVT



TB



TB2



Rear-connecting Stud

STB



BSD



GKW(STB)



GK • GKW(BSD)

PDK

Mechanical Interlock

MIW

Motor-operating Mechanism

MMK-C

Lock Cover

LC

PK

MMK-S MMK HL

HA

— —







10 / 10

5/3

5/3

10 / 5

30 / 30

15 / 8

15 / 8

30 / 15

30 / 30

15 / 8

15 / 8

30 / 15

10 / 3

30 / 30

15 / 8

15 / 8

30 / 15

10 / 3

30 / 30

15 / 8

15 / 8

30 / 15

35 / 9

50 / 50

35 / 18

35 / 18

50 / 25

35 / 9

50 / 50

35 / 18

35 / 18

50 / 25

75

90

105

105

105

130

150

165

165

165

60

68

60

68

68

84

94

85

95

95

0.74

1.6

1.6

1.6

1.6

● (*2)

● (*2)

● (*2)

● (*2)

● (*2)

○ ○ ○

○ ○ ○

○ ○ ○

○ (*3) ○ (*3) ○ (*3)

○ (*3) ○ (*3) ○ (*3)



















○ ○

○ ○

○ ○

○ ○

○ ○

○ ○





































STB-2M

STB-3K























○ —













MIW-2E

MIW-2E







MIW-4F

MIW-4L

MIW-4M

















































LC-03

LC-03

LC-2G

LC-2G

LC-4E

LC-2F

LC-4J

HL-4E

HL-2F

HL-4J

HA-207

HA-209

HA-210 HM-S25





HL-2G

HL-2G

○ ○





HA-108

HA-108







HM-S12

HM-S12

HM-S13

HM-S22

HM-S23

TMC-0G

TMC-0G

TMC-1

TMC-1

TMC-2C

TMC-4K

TMC-4J

TMC-4J

Short Type





TMC-1S

TMC-1S



TMC-4JS

TMC-4JS

TMC-4JS

Long Type





TMC-2D

TMC-2D













BTC-1

BTC-1

BTC-2C

BTC-4G

BTC-4J

BTC-4J

















ww

HM

IEC Rail 35 mm Trip Button

8



TMC

Rear Type

Automatic Tripping Device

6

○ ○ ○ ○



w.

Handle Lock Handle Operating Mechanism Front Type

690

6

○ ○ ○



die

Plug-in Mounting Base Assembly Drawout Assembly

Terminal Cover

Attention

○ ○ ○

Shunt Trip

Terminal Block

Exterior Accessories



Alarm Switch

Flush Mounting Base Assembly

690

8

Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal

Phase Separator for Line Side (*2)

Interior Accessories

10 / 3

690

e.x

IEC 60947-2

500V 440V

nh ath

Rated Breaking Capacity (kA)

1. 2. 3. 4.

3 0.7 1.4 2.3 2.6 4.2 5.6 7.4 9 10 14 16 25 33 40 45

yz

Number of poles

BTC

Full Magnetic Full Magnetic Full Magnetic Full Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic —















● : Standard ○ : Option Please state that number of poles of breakers when order MIW. Installation of phase separators is required in case of types marked (*2). The accessories marked (*3) can be installed by customers.

www.dienhathe.vn

13

Selecting Table of a Motor Breaker for 3-phase Induction Motor 400 – 440V AC

200 – 220V AC Motor Capacity (kW)

Motor Breaker Rated Current Type (A)

Motor Capacity (kW)

0.2

1.4

11

0.4 0.75 1.5 2.2 3.7 5.5 7.5

2.5 4 8 10 16 25 32

15 18.5 22 30 37

MS-30E

Motor Breaker Rated Current Type (A) MS-50EB, 45 MS-50SB 60 MS-100SB, 75 MFXK100-S 90 (125)* MS-225SB, (150)* MFXK225-S

Motor Capacity (kW) 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5

Motor Breaker Rated Current Type (A) 0.8 1.4 2.5 4 MS-30E 6.3 10 16

Motor Capacity (kW) 11 15 18.5 22 30 37 45

Motor Breaker Rated Current Type (A) 25 MS-30E, MS-50EB 32 40 MS-50SB 45 60 MS-100SB, 75 MFXK100-S 90 MS-225SB, (125)* MFXK225-S

yz

Table 5

16

50

e.x

Note: 1. Starting conditions are set within 3 seconds at 500% (2 seconds at 600%) of full load current for types MS-30E, MS-50EB, MS-50SB and within 8 seconds at 500% (5 seconds at 600%) of full load current for other types. 2. Specify the rated current since the figures with asterisks are the mere reference current.

MS-50SB

Hr.

Tripping Time

Min.

Min. value

Sec.

Min. value

Max. interrupting time

Hr.

Hr.

MFXK225-S

Min.

Cold start max. value

Min.

Cold start max. value

Hot start max. value Tripping Time

Hot start max. value

Max. interrupting time

www.dienhathe.vn

Min. value

Sec.

Min. value

Sec.

Sec.

ww

Max. value

Min. value

14

MS-225SB

Tripping Time

Tripping Time

Min.

Hr.

MS-100SB

w.

die

Sec.

Max. value

Tripping Time

Max. value of less than 30A

Sec.

Min. Tripping Time

Max.

Min.

MFXK100-S

Max. value of 31 to 50A

Min.

Hr.

Hr.

MS-30E, MS-50EB

nh ath

● Overcurrent Tripping Characteristics

Max. interrupting time

c onstRUction Hitachi Fuse-Free Breaker is comprised a switching mechanism, arc extinguishing devices, and a tripping unit contained in a compact molded case.

The arc is thus confined, divided and extinguished.

■ Tripping Unit

■ Arc Extinguishing Device

■ Positive Indication

The series of grid plates is mounted in parallel between supports of insulating material. The slots in the steel plates extend directly over the contacts and draw the arc from moving contact up into the divided chamber.

The handle position gives positive indication of whether the breaker is ON (top), OFF (down) or tripped (midway).

e.x w.

die

nh ath

Thermal Magnetic Type

ww

Fig. 1

yz

The switching mechanism is a quick-make/quick-break type utilizing a trip-free toggle mechanism.

The tripping unit of the Fuse-Free Breaker is produced in two types: a thermal-magnetic type and a full-magnetic type. The tripping unit is provided for each pole of the breaker, and if any one pole operates, all of the poles open the circuit simultaneously.

■ Switching Mechanism

www.dienhathe.vn

15

Fig. 2

Full magnetic Type Handle

yz

Molded cover

e.x

Line terminal

Fixed contact

Moving contact

Principle (How the tripping mechanism operates) Normality

Fig. 4

Yoke

Movable iorn core

Cylinder (Brass tube)

Armature

Pole piece Spring silicon liquid oil

die

Magnet coil

nh ath

Full magnetic type tripping mechanism

Molded case

Fig. 3

Time-Delay Action (2)

ww

w.

This figure shows that the movable iron core and armature do not move at less than rated current of the breaker.

Fig. 5

Time-Delay Action (1)

When overcurrent flows through the magnet coil, only the movable iron core moves for the pole piece, overcoming viscosity of the silicon liquid oil.

Fig. 6

The armature is pulled at the pole piece, overcoming the core spring by increasing of the flux, and the armature operates the tripping mechanism of the breaker.

16

Load terminal

Instantaneous Action

When a large current flows through the magnet coil, take short circuit for instance, armature is pulled at pole piece instantly without moving iron core, and it operates the tripping mechanism of the breaker.

www.dienhathe.vn

Construction of Current-Limiting Type Breakers (L series) Moving contact

Handle

L - S er i e s b re a k e rs r ap i d l y i nterrupt high faulty current by electromagnetic repulsing mechanism.

Quick-make, quick-break, trip-free mechanism

Arc extinguishing device

Tripping unit Current

Available Current

Line terminal

yz

Load terminal

Let thru current by standard FFB Let thru current by current-limiting type FFB

Time

About 4 to 8ms

Current limiting contact

Arc extinguishing device

nh ath

Fig. 7 Construction of L-100E

e.x

About 10 to 20ms

w.

die

When a current flows through a conductor in one direction while another current flows through a conductor in the opposite direction (as shown in the figure on the left), an electromagnetic repulsing force act between the conductors. The currentlimiting type breaker utilizes this force to complete high-speed current interruption within an extremely short period of time.

Fig. 8

Current limiting characteristics

ww

Function of Hitachi Current-Limiting Type Breaker is as follows:

Fig. 9-1 When a short circuit current flows through this breaker, an electromagnetic repulsing force works in the direction shown above.

Fig. 9-2 The electromagnetic repulsing force causes the moving contact to swing apart from the fixed contact before the breaking mechanism functions, accomplishing extremely quick breaking.

www.dienhathe.vn

Fig. 9-3 The breaking mechanism has functioned to open the circuit.

17

Construction of Electronics Type Breakers (FX400 – FX1200) Double Instantaneous Trip*

Owing to high-speed current interruption, excellent current limiting is achievable. Thus breaker stress with respect to temperature or mechanic is reduced circuits are securely protected.

Double electronic and mechanical instantaneous tripping characteristic protects equipments from short circuit.

Higher MT current Reduces Miss trip by motors rush Current

Easy Coordination*

Instantaneous tripping current is now greater *than conventional models. Reduces probability of miss trip at high inrush current. Improvement of the voltage equilibrium characteristic of the earth leakage breaker.

Tripping characteristics include adjustable long time delay & short time delay in proportion to long time delay (setting current x 1,000%) are contribute to easier coordination with other electric appliance such as down stream circuit breakers, transformers and wires.

*In-house comparison

*over 400A frame

FFB tripping characteristics

15

5,000A

600A

8,000A

800A

10,000A

1,000A

17,000A

1,200A

20,000A

(FFB)

Current (rated current magnification)

ww

w.

die

10

MT Current

400A

nh ath

Motor startup inrush current

Frame

e.x

Time

18

yz

Excellent Current Limiting Function

www.dienhathe.vn

C HARACTERISTICS ■ Full-magnetic type

Because of its tripping device with proper time-delay characteristics, Hitachi Fuse-Free Breaker automatically opens circuits for overcurrents up to about 800% of its ampere rating. For heavy short-circuit currents, its instantaneous magnetic tripping device functions to break the circuit. These characteristics are specified in Circuit Breakers IEC60947-2, as shown in Table 6, according to which Hitachi Fuse-Free Breaker is designed.

The rated current of a full-magnetic type which has no thermal element will not undergo a change despite variations in ambient temperature. Instead, the viscosity of the oil in its dash pot relay varies with temperature, causing the operating time to change as shown in Fig. 11. The rate of change in the operating time which the example below illustrates is as follows: If this tripping device adjusted to an ambient temperature of 40ºC is employed at a site whose ambient temperature is 50ºC, and if it trips over a circuit because of an overcurrent, its operating time will be reduced to 85% of standard time.

Overcurrent Tripping characteristics

■ Thermal-magnetic type

Current (percent rated current)

When employing or testing a thermal-magnetic type at ambient temperatures other than 40ºC, the operating current for tripping varies (as shown in Fig. 10). It is necessary to compensate for the rated current according to the temperature compensation curve prepared for each frame. Application of the temperature curve is as follows: The compensation current I is represented by:

die

I1 x 100

I=

At 40ºC

nh ath

Tripping device of Hitachi Fuse-Free Breaker is factory-adjusted for application at an ambient temperature of 40ºC, the base ambient temperature specified by IEC standard.

At 20ºC

X (%)

200 180 160 140 120 100 80 60

0

10

20

30

40

50

Ambient temperature (ºC)

Fig. 11 Example of Application of Ambient Temperature Compensation Curve for Full-magnetic Type

Fuse-Free Breaker is applicable to ambient temperatures up to 50ºC. Application at a site whose ambient temperature exceeds 50ºC is a special case, for which users are requested to contact Hitachi for advice.

ww

w.

Where I = value of compensation current, I1 = value of current required at certain ambient temperature, and X = rate of increase or decrease of current at a certain ambient temperature compensation curve for determining the amount of compensation for the rated current value. The example shown below illustrates that the rated current of a device adjusted at the base ambient temperature 40ºC at a site whose ambient temperature is 50ºC decreases to 90% of the rating.

Base ambient temperature 40ºC 300

Tripping time (%)



Tripping current value varies

e.x

All poles loaded Conventional Conventional non-tripping C o n v e n t i o n a l t r i p p i n g time (h) current current 1.05 times current setting 1.3 times current setting 2* *1 hour when ln ≤ 63A

Tripping time

Table 6

yz

1. Overcurrent Tripping

Tripping time

At 20ºC At 40ºC

Compensation rate of rated current (%)

Tripping current value varies

Base ambient temperature 40ºC

130 120 110 100 90 80

0

Current (percent rated current)

10

20

30

40

50

Ambient temperature (ºC)

Fig. 10 Example of Application of Ambient Temperature Compensation Curve for Thermal-magnetic Type

www.dienhathe.vn

19

C AUTION 1. Standard mounting is shown in the diagram below. 15 degree 15 degree or less or less

Metal plate coated Line end

Line end

B

A

15 degree 15 degree or less or less

5. Insulation clearance on line end of FFB is as follows:

FFB Load end

Fig. 14

Vertical wall

Fig. 12

yz

Load end Vertical wall

Standard Mounting Method

Table 7

2. Reversible connection types are available.

Insulation Clearance

Reverse connection is basically prohibited (See following figure (Fig.13)) Load

Classification

ON side

ON side

OFF side

OFF side

1

2

Load

Power source

(a) Correct connection

(b) Incorrect connection

3 4

5

6

F-100KB



225AF

FXK250-S, FXK250-H

S-225SB, SXK225

400AF

F-400R

S-400S

600AF

F-600F

S-600S

800AF

F-800F, F-800RH

S-800S

1000AF

F-1000K



1200AF

F-1200K



) dimension is 400V class

30

25

40

40

50 100

40 40

80 (110)

50

150 (190)

100

die

100AF

Maximum applicable voltage

It is recommended that line side’s live parts of front connected type breakers are insulated by insulation tape or insulation barrier.

Remarks

1. Please state "Reversible connection type" when ordered.

AC460V

w.

S series

2. Installation of phase separators on the load side is required.

ww

F series

30A Frame, 50A Frame (Excluding L-50E) 60A Frame L-50E 100A Frame 125A 225A 250A Frame F-250FB F-250KC 400A Frame, 600A Frame, 800A Frame 1000A Frame, 1200A Frame, 1600A Frame

(

Minimum dimensions (mm) A B

6. Insulation of line side’s living parts

But reversible connection type available as follows: Frame

FFB frame

nh ath

Power source

e.x

If mounting in another direction is inevitable, contact Hitachi for advice.

Insulation barrier Taping A

Dimension is the same as A of above table

3. Don’t install the breaker at a site whose ambient temperature of an installation site exceeds 50ºC. If installing the breaker in such a high ambient temperature is unavoidable, contact with Hitachi in advance.

4. Application of full magnetic type for DC circuit Breakers for AC and breakers for DC are separately calibrated, and different application cannot be performed. If DC application, please specify pure DC, single-phase full-wave rectified or three-phase full-wave rectified, etc.

20

www.dienhathe.vn

Fig. 15

SELECTION 1. Select a breaker type according to the purpose

2. Estimate the available short-circuit current and select economical frames — whose interrupting capacity is higher than that estimation — from among the following series:

■ Protection of general wiring: Table 1 to 4 ■ Protection of motor: Table 5 ■ Protection of branch lamp circuit: Table 6 ■ Protection against earth leakage

F series: Standard type for general service S series: Small-scaled and low-cost, economical type L series: High-performance, current-limiting, high-interrupting capacity type



nh ath

e.x

yz

In estimating short circuit currents, there are many considerations, such as characteristics of transformer, connecting wire size and the distance from the transformer to the faulty point and so on. The below charts bring you an easy solution for selecting the breaker type.

AC 460V (Transformer voltage: 415V) 50A 125A frame

100AF 125A frame

FXK125-H

die

FXK125-H

225AF 250AF frame

FXK250-H

FXK250-S

400A frame

ww

w.

FXK125-S

Fig. 16 Example of selection

600A frame

www.dienhathe.vn

800A, 1000A, 1200A frame

21

■ Rated Current of main circuit for motor

● Rated

The motor groups connected to this circuit are divided into subgroups, each consisting of motors which are started simultaneously. Each subgroup is regarded as one motor for convenience (and the sum of the full load current of each motor within this subgroup is regarded as the full load current of this virtual motor). Then select the rated current of a subgroup whose full-load current is largest from the Table 8, 9, 10, 11. The sum of this tentative rated current and the full-load current of all the other subgroups is selected as the rated current of the breaker under consideration.

currents for heater and lamp circuits Select a circuit breaker whose current rating corresponds to the value of the current allowable for the circuit. ● The rated current of a motor circuit is selected as follows:

■ Rated current of branch circuit for motor Table 8, 9, 10, 11 shows rated currents of the breakers which have been selected on condition that they will not effect erroneous operation at motor starting time. Where two or more motors are connected to one branch circuit, the sum of the rated currents of these motors forms the basis for selecting the rated current of the breakers.

Directly Starting a 3-phase Induction Motor (400 – 440V AC)

110

(220)

350

150 190

(300) (380)

500 600

FFB Interrupting capacity (kA) Sym 2.5

5

7.5

10

15

F-30FB

22

e.x

Rated current (A) 15 15 15 15 15 20 30 30 50 60 60 75 100 100 150 175 225 225

25

30

FXK125-S S-60RB

F-60RB

S-50SB

nh ath

Motor Full-load Capacity current (kW) (A) 0.2 0.7 0.4 1.4 0.75 2.3 1.5 4.2 2.2 5.6 3.7 9.0 5.5 14 7.5 16 11 25 15 33 18.5 40 22 45 30 60 37 75 45 90 55 (110) 75 (150) 90 (180)

FXK125-S

S-100S S-100SB S-225SB SXK225

FXK250-S

die

Table 8

yz

3. Select the rated current as follows:

S-400S

SX400

S-600S

SX600

35

43

50

85

FXK125-H

L-50E

FXK125-H

L-100E

FXK250-H

L-225E

F-400R FX400 F-600F FX600

L-400E L-600E

Star-delta Starting a 3-phase Induction Motor (400 – 440V AC) Motor Full-load current (A)

Capacity (kW) 18.5 22 30 37 45 55 75 90 110

40 45 60 75 90 (110) (150) (180) (220)

150

(300)

190

22

(380)

FFB Rated Interrupting capacity (kA) Sym current 2.5 5 7.5 10 15 22 25 30 35 43 50 (A) For a capacity of 15 kW or less, select the same breaker among those for direct-starting 75 S-100S 75 FXK125-S FXK125-H S-100SB 100 125 150 S-225SB FXK250-S FXK250-H SXK225 175 225 350 S-400S F-400R SX400 FX400 400 S-600S F-600F 600 SX600 FX600

ww

Table 9

w.

Note: (1) The starting conditions are set within 15 seconds at 500% (10 seconds at 600%) of full load current.

700

S-800S

www.dienhathe.vn

FX800

85

L-100E

L-225E

L-400E L-600E F-800R F-800RH L-800E

Selecting table of Fuse-Free Breaker for Motor Branch Circuit Directly Starting 3-phase Induction Motor (200 – 220V AC)

25

50

7.5 11 15 18.5 22 30 37 45 55 60 75 90

33 45 60 75 90 (120) (150) (180) (220) (240) (300) (360)

60 75 100 100 150 200 225 225 350 400 500 600

Table 11

5

10

14

25

30

35

85

175

FXK125-H

L-50E

FXK125-S

FXK125-H

L-100E

FXK250-S

FXK250-H

L-225E

S-400S SX400

F-400R FX400

L-400E

S-600S SX600

F-600F FX600

L-600E

S-30E S-30FB S-60RB

42

50

FXK125-S

F-60RB

S-50EB, S-50SB S-100SB

S-100S S-100SB

S-100EB

S-225SB SXK225

nh ath

5.5

FFB Interrupting capacity (kA) Sym

yz

Rated current (A) 15 15 15 15 20 30

e.x

Motor Full-load Capacity current (kW) (A) 0.2 1.4 0.4 2.6 0.75 4.2 1.5 7.4 2.2 10 3.7 16

Star-delta Starting a 3-phase Induction Motor (200 – 220V AC)

Motor Full-load Capacity current (kW) (A) 75 90 (120) (150) (180) (220) (240) (300)

90

(360)

700

S-800S, F-800R, SX800

w.

18.5 22 30 37 45 55 60 75

FFB Rated Interrupting capacity (kA) Sym current 2.5 5 10 14 25 30 35 50 85 (A) For a capacity of 15 kW or less, select the same breaker among those for direct-starting 125 150 S-225SB FXK250-S FXK250-H SXK225 200 225 350 F-400R S-400S, SX400 FX400 400 500 F-600F S-600S, SX600 FX600 600

die

Table 10



ww

A motor breaker is used to protect wiring and a motor against overload. Its rated current is about the same value as full-load current of the motor. The applicable conditions are subject to the following restrictions: 1) Only one motor is installed on the circuit under consideration. 2) Starting current is less than 600% of the full-load current and motor load is light (for specific requirements for each rated current, refer to Table 12).

Table 12

125

175

L-225E

L-400E L-600E F-800RH FX800

L-800E

Applicable Conditions of Motor Breaker

Rated current (Amperes) 50 or less From 51 to 150

Starting condition Starting current/ Starting time full load current 500% Within 3 sec 600% Within 2 sec 500% Within 8 sec 600% Within 5 sec

When the above restrictions cannot be met use a general type FFB. When ordering, please specify the Frame (selected by the interrupting capacity) and the rated current. (About the same as full load current of the motor.) ● When

using the breaker for the transformer primary circuit.

Since exciting inrush current may be 20 to 30 times the transformer rated current, the breaker rated current should be selected more than two times the transformer rated current.

www.dienhathe.vn

23

4. Application to discrimination coordination In a discrimination coordination system, only the breaker nearest the fault opens to isolate the faulty circuit from the rest of the power system. This system results in maximum continuity of service. ELECTRONICS TYPE breakers are best suited to application as the upstream (main) breaker.

Main circuit breaker

Branch circuit breaker

Normal circuit

Table 13

Faulty circuit

Fig. 17

Discrimination between standard FFBs and ELECTRONICS TYPE FFBs

230V class

5 10 25 35 100 50 100 85 / 100 100 100 100 125 125 5 10 35 35 50 50 85 175 175 175 175 175 175

380V class

24

Interrupting Interrupting Capacity(kA)

Type Capacity (kA)

2.5 7.5 10 50 30 50 30 50 50 50 50 85 85 2.5 5 10 15 35 35 35 125 125 125 125 125 125

FX600 100

FX800 100

5 5 5 5 5 5 5 4 — — — — — 4 4 5 4 — — — 5 5 4 — — —

5 7.5 10 10 14 10 14 10 — — — — — 5 7.5 14 10 — — — 14 14 10 — — —

5 7.5 10 10 14 10 14 10 10 — — — — 5 7.5 14 10 10 — — 14 14 10 10 — —

FX400 50

FX600 50

2.5 4 4 4 4 4 4 4 — — — — — 2.5 4 4 4 — — — 4 4 4 — — —

2.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 — — — — — 2.5 5 7.5 7.5 — — — 10 10 7.5 — — —

w.

F-30FB F-50FC F-60RB FXK125-H FXK125-S FXK125-H FXK250-S, F-250FB FXK250-H, F-250KC FX400, F-400R F-600F, FX600 FX800, F-800R FX1000 FX1200 S-50SB S-60RB S-100S, S-100SB S-225SB, SXK225 SX400, S-400S SX600, S-600S SX800, S-800S L-50E L-100E L-225E L-400E L-600E L-800E

FFB for main circuit

ww

FFB for branch circuit Type

FX400 100

FX1000 125

FX1200 125

F-1600CB 125

5 10 25 35 85 50 85 35 18 — — — — 5 10 25 25 18 — — 125 125 42 18 — —

5 10 25 35 85 50 85 35 22 22 — — — 5 10 25 25 22 22 — 125 125 65 22 22 —

5 10 25 35 85 50 85 65 25 25 25 — — 5 10 25 25 25 25 25 125 125 125 42 42 42

FX800 50

FX1000 85

FX1200 85

F-1600CB 85

2.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 — — — — 2.5 5 7.5 7.5 7.5 — — 10 10 7.5 7.5 — —

2.5 7.5 10 50 25 35 22 22 18 — — — — 2.5 5 10 15 22 — — 30 30 22 18 — —

2.5 7.5 10 50 25 50 22 22 22 22 — — — 2.5 5 10 15 22 22 — 30 30 22 22 22 —

2.5 7.5 10 50 25 50 30 30 22 22 22 — — 2.5 5 10 15 22 22 22 85 85 50 22 22 22

yz

F-30FB F-50FC F-60RB F-50HB FXK125-H FXK125-S FXK125-H FXK250-S, FXK250-H, F-250FB, F-250KC FX400, F-400R F-600F, FX600 F-800F, FX800, F-800R FX1000 FX1200 S-30E, S-50EB, S-50SB S-100EB, S-60RB S-100SB S-225SB, SXK225 SX400, S-400S SX600, S-600S SX800, S-800S L-50E L-100E L-225E L-400E L-600E L-800E

Type Capacity (kA)

e.x

Interrupting Interrupting Capacity(kA)

nh ath

FFB for main circuit

die

FFB for branch circuit Type

www.dienhathe.vn

A CCESSORIES Interior Accessories ■ Available accessories inside of FFB are as follows: Shunt Trip (SHT)

The Undervoltage Trip is used to automatically trip the breaker when the line voltage drops to 35 to 70% of its normal value. The standard mounting method of the breaker with this trip is vertically on the wall with its line end positioned upward.

The Shunt Trip is used to trip the breaker electrically from a remote point. Since this trip coil does not have a continuous rating, the coil circuit must be broken by making connections to the load end of the breaker (Fig. 20 (a)). If a separate power supply is to be used, the customer is requested to specify an auxiliary switch to prevent the coil from being burnt by overheating (Fig. 20 (b)). The standard mounting method of the breaker with this trip is on the wall with its line end positioned upward.

nh ath

e.x

yz

Undervoltage Trip (UVT)

w.

die

Lead wire 0.5mm2 PVC-insulated wire (yellow), 0.5 meter long

Auxiliary Switch (AUX)

When the breaker is tripped, this switch closes to energize an indicating light or sound an alarm. It employs a microswitch equipped with a C-contact.

The auxiliary switch, a device interlocked with opening and closing operation of a breaker, is used to open or close control circuits as the breaker operates. It employs a microswitch equipped with a C-contact.

ww

Alarm Switch (AL)

■ Terminal Symbols and Connection Condition of AL Switch Condition of Breaker ON and OFF

■ Terminal Symbols and Connection Condition of AUX Switch

Connection condition of AL switch

Condition of Breaker

Connection condition of AUX switch

S-2 (S-5)

A-2 (A-5)

S-1 (S-4)

ON and OFF

A-1 (A-4)

S-3 (S-6)

A-3 (A-6)

S-2 (S-5) Tripped

A-2 (A-5)

S-1 (S-4)

OFF or Tripped S-3 (S-6)

(

): for 2C contacts

A-1 (A-4) A-3 (A-6)

(

): for 2C contacts

www.dienhathe.vn

25

Terminal Block for Interior Accessories

TB

TB2 3P

16.5

40

8.5

10

6P

47.5

16.5

6P

3 8

10.5

10

10

10

(E) 7.9

(E) 7.9

32

62

(F) 10

(F) 10

(F) 10 10 32

3P

yz

10

7

12 62

7

16.5

10 (F)

TB2

Fig. 18 External View of a Breaker with Terminal Block for an Interior Accessory

e.x

TB

10

16.5

Fig. 19 Dimensions of FFB with Terminal Block for Interior Accessory

Table 14

Rating of Alarm Switch and Auxiliary Switch

AC

DC

(a) Uni-power

(b) Separate power (excepting F-250FB F-250KC)

Table 15

die

Fig. 20 Wiring Diagram of Shunt Trip

Coil rating of SHT and UVT

250V 500V 110V 220V

SHT

Type

FXK125-S, FXK125-H, FXK250-S, FXK250-H, F-250FB, F-250KC L-225E, S-400S, SX400, F-400R, FX400, L-400E

S-600S, SX600, F-600F, FX600, L-600E, S-800S, SX800, F-800R, F-800RH, FX800, L-800E, FX1000, FX1200, F-1000C, F-1000K, F-1200C, F-1200K, F-1600CB, F-1600B

(

Common use for 50 and 60 Hz

)

Time constant — 10 ms or less

UVT

Input (VA) 100 (for 400V: 200VA)

Voltage

Input (VA)





50Hz AC 100V 200V 230V 240V

AC 100-110V AC 200-220V AC 230-240V AC 380V AC 400-440V AC 480V

ww

F-30FB, S-50SB, F-60RB, F-50KB, L-50E, S-100EB, S-100S, S-100SB, F-100S, F-100RB, F-100KB, L-100E

w.

Voltage

S-30E, S-50EB, S-225SB, SXK225

26

Rated current 2A 1A 0.5A 0.25A

nh ath

Voltage

60Hz AC 100V 110V 200V 220V —

200

DC 100V DC 110V

www.dienhathe.vn

50Hz AC 100V 200V 230V 240V 400V 415V

60Hz AC 100V 110V 200V 220V 400V 440V

20

— 20

30

Applicability of interior accessories

F-30FB F-60RB

F-100S F-100KB

✶ FXK125-S ✶ FXK125-H ✶ FXK250-H ✶ FXK250-S F-250FB F-250KC

S-50SB, S-100EB, S-100SB, S-60RB

S-100S

S-225SB ✶ SXK225

F Type

S S-30E S-50EB

✶ FX400 ✶ F-400R

✶ FX600 F-1200K ✶ FX800 F-1600B F-600F F-800R F-1000K F-800RH

✶ SX400 ✶ S-400S

✶ SX600 S-600S ✶ SX800 S-600S

L

L-225E L-400E

L-50E L-100E M MS-30E MS-50EB

✶ MFXK100-S ✶ MFXK225-S MS-225SB MF-250FB

MS-50SB MS-100SB

Accessories 2

3

2

3

2

3, 4

2, 3

2, 3, 4

2, 3, 4

e.x

Number of poles

✶ FX1000 ✶ FX1200 F-1600CB

L-600E L-800E

yz

Table 16

3, 4

1C

1C

1C

1C

1C

1C

1C

2C

2C

2C

AUX

1C

1C

1C

1C

1C

1C

1C

2C

2C

2C

1C

1C

1C

1C

1C

1C

2C

1C

1C

1C

1C

1C

1C

1C

2C

2C

2C

1C

1C

2C

2C

2C

2C

2C

2C

2C

2C

2C

2C

2C

2C

SHT

UVT

AL + AUX AL + SHT AL + UVT

1C

Handle of Breaker

1C

ww

AL + AUX + SHT AL + AUX + UVT

w.

AUX + SHT AUX + UVT

1C

die

1C

nh ath

AL

AL

1C

1C

1C

1C

1C

1C

2C

1C

1C

1C

1C

2C

2C

1C

2C

1C

1C

2C

2C

AUX

SHT

2C

2C

1C

1C

2C

2C

2C

2C

1C

2C

2C

UVT

Notes: 1. 2C means that it can be mounted 1C, if required. 2. *: Terminal block (TB) for UVT wiring is equipped. 3. The accessories of marked ✶ types can be installed by customers. 4. AL 2C or AUX 2C is available in case of FXK125-S / H and FXK250-S / H

www.dienhathe.vn

27

Exterior Accessories ■ Accessories mounted on the outside of breaker are as follows:

3. Flush-mounting Base Assembly (GKW, GK)

■ Rear Connecting Stud (STB) and Bar Stud (BSD) ■ Plug-in Mounting Base Assembly (PK) ■ Flush Mounting Base Assembly (GK) ■ Mechanical Interlock (MI) ■ Motor Operating Mechanism (MMK, MMK-C) ■ Electro-magnetic Operating Mechanism (MK-C) ■ Handle Operating Mechanism

The flush-mounting base assembly is an accessory for mounting a breaker on a switchboard. A breaker is secured via insulating bushings to an exclusive mounting frame by using screws as same method as the rear connecting stud or bar stud. A rectangular hole sized a little larger than that of a breaker is cut into the switchboard and the breaker is embedded into this hole and secured to the switchboard by the mounting frame. The flush plate is mounted on the breaker.

1. Rear Connecting Stud (STB) and Bar Stud (BSD)

e.x

yz

Rear connecting stud is used as rear connecting terminal.

nh ath

Fig. 23 FFB with Flush-mounting Base Assembly

Fig. 21 FFB with Rear Connecting Studs

4. Mechanical Interlock (MIW)

For 600A frame or less and S-800S, molded insulating bushings are provided.

2. Plug-in Mounting Base Assembly (PK)

This mechanical interlock prevent from any of two breakers to be closed.

ww

w.

die

The plug-in mounting base assembly is an accessory demounting a breaker by saving the trouble of removing the connection wiring from it when inspecting or replacing a breaker mounted on a switchboard or a panel board.

Fig. 24 FFB with Mechanical Interlock

5. Drawout Mechanism (PDK) The drawout mechanism is an accessory for easy mounting and removal of F-1600E.

Fig. 22 FFB with Plug-in Mounting Base Assembly

Fig. 25 FFB with Drawout Mechanism

28

www.dienhathe.vn

6. Motor Operating Mechanism (MMK-S) • This mechanism is suitable to remote control a breaker by utilizing a motor. Since the control circuit is self holding type, the operation of this mechanism is completed by brief closing of push button switch contact. As soon as completing of operation, the control circuit is opened and the motor is stopped by instant operation of a limit switch. • The manual operation is also available.

Standard Ratings of Motor Operated Mechcanism Type

e.x

Table 17

yz

Fig. 26 Motor Operating Mechanism

MMK-S

3P F series Type of FFB

FX400 F-400R

L-50E L-100E S-225SB SXK225

L-225E L-400E SX400 S-400S

nh ath

L series

FXK125-S FXK125-H

S series DC100 DC110 AC100 Max. operational current peak (A) AC110 AC200 AC220 Power supply (VA)

F-400R L-225E L-400E





0.2 (0.6) 0.1 (0.3) 50

0.3 (0.9) 0.15 (0.45) 100



0.3 (0.9) 0.15 (0.45) 100

ww

w.

die

0.2 (0.6) 0.1 (0.3) 500

4P

F100KB F-250FB F-250KC L-50E L-100E

Fig. 27 Control Circuit of Motor Operating Mechanism

www.dienhathe.vn

29

DIMENSIONS

OF

MMK-S

F-100KB

e.x

yz

FXK125-S, FXK125-H

Drilling plan

F-250FB, F-250KC

Mounting screw for MMK-S x 2 (M4)

Mounting screw for FFB x 6 (M4)

L-50E

ww

w.

SX400, FX400

die

Phase separator

nh ath

S-225SB

L-100E

30

www.dienhathe.vn

Drilling plan

M4 screw hole or ø5 holes x 6

7. Motor Operating Mechanism (MMK-C) • This mechanism is suitable to remote control a breaker by utilizing a motor. There is one type as follows.

yz

MMK-C (Compact Type): The breaker is operated by rotation of a single phase series commutator motor with reduction gear.

Table 18

Standard Ratings of Motor Operated Mechcanism Type F-400R FX400

F series

L-225E L-400E S-400S 3 3 1.5 1.2 100

L series

Max. operational current peak (A)

S series DC100 ∙ 110V AC120V AC240V

w.

L series S series

F-400R FX400 F-600F FX600 F-800R F-800RH FX800 FX1000C F-1000K FX1000 F-1200C F-1200K FX1200 F-1600CB F-1600B L-225E L-400E L-600E L-800E S-400S S-600S S-800S

ww

F series

die

Operating time (sec) Power supply (VA)

Type

MMK-C F-800R F-800RH FX800 F-1000C* F-1000K* F-1200C* F-1200K* F-1600CB* F-1600B* L-600E L-800E S-800S 8 8 4 1.5 200

nh ath

Type of FFB

F-600F FX600

e.x

Fig. 28 Motor Operating Mechanism



S-600S 6.5 6.5 3.5 1.5 200

PS X n f a b CP 2 Si R M IS S LS

www.dienhathe.vn

*excepting 4 poles FFB

F-1000C (4P) F-1000K (4P) F-1200C (4P) F-1200K (4P) F-1600CB (4P) F-1600B (4P) — — 10 10 5 1.5 400

Push-button Switch Auxiliary Electromagnetic Contactor For operating FFB“ ON” For operating FFB“ OFF” Closed by operation (normally open) Opened by operation (normally closed) Circuit Protector Timer Silicon Rectifier Resister Motor Limit Switch

31

DIMENSIONS

OF

MMK-C

L-225E (Standard Type)

e.x

yz

(Rear Connecting Type)

nh ath

(Built-in Type)

(Built-in Type)

32

w. ww

(Rear Connecting Type)

die

FX400, F-400R SX400, L-400E (Standard Type)

www.dienhathe.vn

FX600, F-600F SX600, L-600E (Standard Type)

e.x

yz

(Rear Connecting Type)

nh ath

(Built-in Type)

(Built-in Type)

ww

w.

(Rear Connecting Type)

die

FX800, F-800R F-800RH, SX800 L-800E (Standard Type)

www.dienhathe.vn

33

FX1000, F-1000K (Standard Type)

e.x

yz

(Rear Connecting Type)

nh ath

(Built-in Type)

(Built-in Type)

34

ww

w.

(Rear Connecting Type)

die

FX1200, F-1200K (Standard Type)

www.dienhathe.vn

F-1600B, F-1600CB (Standard Type)

ø13.5 holes

Manual handle

w. ww

(Built-in Type)

die

nh ath

e.x

yz

(Rear Connecting Type)

www.dienhathe.vn

35

8. Terminal Cover (TMC)

B

A

D C

Fig. 30 Shape of Terminal Cover

TMC-0G TMC-1 TMC-1S TMC-2D TMC-2C TMC-3C TMC-4K TMC-4J TMC-4JS TMC-4H TMC-5B TMC-5D TMC-6 TMC-6B Remarks

A S-30E, S-50EB 75 (50) 75 (50) F-30FB, S-50SB, S-60SB, 75 (50) F-60RB, S-100EB, S-100SB 75 (50 S-100S, F-100S, 90 (60) FXK125-S, FXK125-H F-100KB, L-50E, L-100E 90 (60) S-225SB 105 105 SXK225 FXK250-S, FX-250-H 105 F-250FB, F-250KC 105 L-225E, S-400S, F-400FB, 147 L-400E S-600S, F-600F, L-600E, SX600, FX600, S-800S, 210 F-800R, F-800RH, L-800E, SX800, FX800 F-1000K, F-1200K 210 FX1000, FX1200 210

Dimensions with (

) are for 2-pole types

D 5 28 5 36

63

63

36

56 79 79 28 71

85.5 56 53 51 99

36 50 50 5 40

147

99

110

154

91.5

129

159 159

145 138.5

130 130

Fig. 31

ww

w.

Terminal Cover (BTC)

Dimensions B C 19.5 56 48 59.5 25 56 56 59.5

Remarks

Short type Long type

nh ath

Applicable breakers

Short type

die

Types

e.x

Fig. 29

All Types (Excepting TMC-0G)

yz

TMC-0G

Types BTC-1 BTC-2C BTC-3C BTC-4G BTC-4J BTC-5B

Applicable FFB Type F-30FB, S-50SB, S-60RB, F-60RB, S-100EB, S-100SB S-100S, F-100S, FXK125-S, FXK125-H F-100KB, L-50E, L-100E S-225SB, MS-225SB SXK225, FXK250-S, FXK250-H L-225E, L-400E, S-400S, F-400R, SX400, FX400

9. Handle operating mechanism

■ Door Interlock

This device is mounted on the face or door of a switchboard or a control board, making it possible to open or close a breaker from the outside. Following interlocks are attached as standard.

For a handle mounted on a hinged door, this door interlock allows the door to be opened only when the breaker’s operating handle is placed at the OPEN COVER position. When the handle is placed at the ON or OFF position, this device will prevent the door from being opened.

■ Handle Interlock This handle interlocks is for preventing unnecessary manipulations of a breaker. Users are requested to provide a padlock for this device.

36

■ Color of Handle and Nameplate The standard colors of handle and nameplate are as follows: Handle: No1.5 (Black) Nameplate: Black letters on silver aventurine

www.dienhathe.vn

yz

Handle Operating Mechanism

(with padlock)

■ Dimension of HA Type Handle (3P)

Center line of FFB (ELB) handle

Center line of FFB (ELB) handle

Stopper for door interlock

Use the padlock (30mm dimension)

Release lever

Door

ø11 hole

Door drilling for handle mechanism Center line of FFB handle (ELB)

HA-108 HA-106 HA-206 HA-207 HA-209 HA-210 HA-405 HA-406 HA-402

HA-801

F-100KB L-50E, L-100E

A

B

C

D

E

Fig.33-1

102

115

91

108

Fig.33-1

104

114

88

105

Fig.33-1 Fig.33-1 Fig.33-1 Fig.33-1

102 102 110 100 106 106

115 115 118 118 110 110

110 127 131 90 96 98

Fig.33-1

113

120

Fig.33-1

113

Fig.33-1

113

F-250FB, F-250KC S-225SB SXK225 FXK250-S, FXK250-H L-225E, S-400S, F-400R, L-400E SX400, FX400 S-600S, F-600F, L-600E, SX600, FX600 S-800S, F-800R, F-800RH, L-800E,SX800, FX800 FX1000, F-1000K, FX1200, F-1200K FX1600CB, F-1600B

Fig.33-1

4-ø5.5 Mounting holes Use the padlock (30mm dimension)

Center line of FFB (ELB) handle

ø60 hole

Center line of FFB handle (ELB)

Handle lever center ø11 hole 4-ø6 Mounting holes

Door drilling for handle mechanism

Fig. 33-2

Panel cutting Fig.

S-100S, F-100S F-30FB, S-50SB, S-60RB, F-60RB, S-100EB, S-100SB

Center line of FFB (ELB) handle

4-ø5.5 Mounting holes (For mounting name plate)

(ELB) FFB mounting panel

ww

HA-104

Applicable breakers

w.

Fig. 33-1

Types

4-ø5.5 Mounting holes

Release lever

Door

die

(ELB) FFB mounting panel

Stopper for Door interlock (Mounted on case side)

Center line of FFB (ELB) handle

Handle lever center Stopper for door interlock (Mounted on case side)

Name plate

Center line of FFB (ELB) Center line of FFB (ELB) handle

Max. B

Max. B Stopper for door interlock

nh ath

Max. A

Center line of FFB (ELB) Name plate

Max. A

e.x

Fig. 32

F

G

H

35





75

35

1.5



75

127 144 148 107 115 115

35 35 35 35 35 35

— — — 1.5 — —

— — — — — —

75 75 75 75 75 75

140

157

38



6

78

120

140

157

38



6

78

120

145

162

38

7.5



78

■ Padlock

5

30

(Padlock is not attached as standard) Fig. 34

Fig.33-2

195

200

187

206

100

www.dienhathe.vn





165

37

yz

Handle Operating Mechanism

Fig. 35

(with padlock)

Door

e.x

■ Dimension of HA Type Handle (3P) Dimension in (mm)

Panel

Face plate

Holder

Latch

Panel

ø

(Padlock isn’t attachment)

Door interlock release lever

1. Diam. B= Ø6 or under Dimension A

Padlock

2. Width C= 19 or more

3.Length of straight part D

Setting position

Setting position

Centerline

Fig. 36-2

4-Ø15 holes

Centerline Ø90hole

Center line of FFB handle

Hinge

8

Ho

le

s

4-ø15 holes

ø1 3

die

Drilling plan of doors

Fig. 36-1

Flush plate

=10.5 or more

of right hinge of door

of left hinge of door

Center line of FFB

Max. B

nh ath

Dimensions of padlock

Max. C

Flush plate

Handle Type HM-S11 HM-S12 HM-S13 HM-S21 HM-S22 HM-S23 HM-S25 HM-402 HM-405 HM-406 HM-407

38

Applicable Breakers

ww

w.

Center line of FFB handle

F-100KB L-50E, L-100E F-30FB, S-50SB, S-60SB F-60RB, S-100EB, S-100SB FXK125-S, FXK125-H F-250FB, F-250KC S-225SB SXK225 FXK250-S, FXK250-H S-600S, S-800S, F-600F F-800R, F-800RH, L-600E, L-800E L-225E, S-400S, F-400R, L-400E SX400, FX400 SX600, FX600, SX800, FX800

Bolt

Fig.

Dimension A B 132 — 149

Over 150 (When hinge is 10)

Fig. 36-3

Length between hinge and breaker

■ Padlock C

D





M4 x 50

Fig.36-1

M4 x 65

Fig.36-1

108.5







M4 x 70 M4 x 50 M4 x 45 M4 x 45 M4 x 45

Fig.36-1 Fig.36-1 Fig.36-1 Fig.36-1 Fig.36-1

118 150.5 110.5 118 118

— — — — —

— — — — —

— — — — —

M6 x 130

Fig.36-2

176

137

137

0

M6 x 130 M6 x 130 M6 x 130

Fig.36-2 Fig.36-2 Fig.36-2

170 170 176

137 137 137

140 140 137

6 6 0

L: Straight length

(Padlock is not attached as standard)

Fig. 37 ■ Padlock Dimension HM-402, 405, 406, 407

www.dienhathe.vn

A 45

B 6 — 6.5

L Over 16

DIMENSIONS

Hr.

S-30S / S-50E

Min.

Max. value of less than 30A

Tripping Time

Max. value of 31 to 50A Base ambient temperature 40ºC 300

Tripping Time (%)

200 180 160 140 120 100 80

yz

Sec.

Min. value

20

30

40

Temperature Compensation Curve

e.x

Overcurrent Tripping Characteristic Curve

Terminal Cover

nh ath die

10

Ambient Temperture (ºC)

(2) Mounting holes for M4 screw

2-M4 screw hole or ø5 hole

0

M5 screw

2-M4 screw hole or ø5 hole

■ Terminal Arrangement

ww

w.

■ Drilling Plan

-5

Current (percent rated current)

■ Dimensions (2) Mounting holes for M4 screw

60

2 pole

3 pole For front mounting bolts

www.dienhathe.vn

39

50

Hr.

S-30E / S-50EB

Min.

(MS-30E / MS-50EB)

Tripping Time

Max.

Min. Sec.

Tripping Time (%)

Base ambient temperature 40ºC

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

2-M4 screw hole

2 pole

2-M4 screw hole

3 pole

2-M4 screw hole or ø5 hole

2-M4 screw hole or ø5 hole

ww

w.

die

■ Drilling Plan

M5 screw

nh ath

Mounting fixture

e.x

■ Dimensions

2 pole

■ Terminal Arrangement

Max. applicable crimping terminal: 14 mm2

3 pole

Applicable wire ø1.6 – 22mm2

ø5.5

M5 screw

(Max.)

Bus and crimping terminal connection

40

Wire connection

www.dienhathe.vn

Manufacturing of terminal (Max. 14)

Hr.

S-30FB / S-50SB

Min.

Max. value of less than 30A

Base ambient temperature 40ºC

Min. value for AC Min. value for DC

Tripping Time (%)

Tripping Time

Max. value of 31 to 50A Max. value for DC application

Sec.

(MS-50SB)

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

Temperature Compensation Curve

ww

w.

■ Drilling Plan

3 pole

die

2 pole

2 pole

For front mounting bolts

■ Terminal Arrangement

3 pole For rear connecting studs

■ For Rear Connecting Studs

2 pole

www.dienhathe.vn

3 pole

41

Hr.

F-60RB S-60RB

Max. value of 31 to 60A Max. value for DC application Base ambient temperature 40ºC

Min. value for AC Min. value for DC

Tripping Time (%)

Tripping Time

Sec.

Min.

Max. value of less than 30A

Current (percent rated current)

Ambient Temperture (ºC)

2 pole

3 pole

ww

w.

die

■ Drilling Plan

nh ath

e.x

■ Dimensions

For front mounting bolts

■ Terminal Arrangement

42

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

2 pole

3 pole For rear connecting studs

■ For Rear Connecting Studs

www.dienhathe.vn

Hr.

L-50E

Min.

Max. value of 31 to 50A

Base ambient temperature 40ºC Min. value

Tripping Time (%)

Sec.

Tripping Time

Max. value of less than 30A

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

Temperature Compensation Curve

ww

3 pole

w.

die

■ Drilling Plan

3 pole

For front mounting bolts

■ Terminal Arrangement

For rear connecting studs

■ For Rear Connecting Studs

Max. applicable pressure type wire connector: 22mm2

Breaker underside

M6 screw

Bus or pressure wire connector connection Applicable wire connector: 1.6 to 22mm2

Insulating bushing

Wire connection (15 to 50A) M8 screw

3 pole

www.dienhathe.vn

43

Hr.

Hr.

Max. value

Min.

(MS-100SB)

Max. value for DC application

Min. value Sec.

Sec.

Min. value

Tripping Time

Max. value of 31 to 50A Tripping Time



Max. value of less than 30A

Min.

S-100EB / S-100SB

Min. value for DC

S-100SB

MS-100SB

Current (percent rated current)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions 2-Mounting holes for M4 screw

e.x

Base ambient temperature 40ºC

nh ath

Tripping Time (%)

2-Mounting holes for M4 screw

Ambient Temperture (ºC)

Temperature Compensation Curve

2-M4 tap holes or ø2-5 holes

w.

2-M4 tap holes or ø2-5 holes

2 pole

3 pole

ww

■ Drilling Plan

3 pole

ø2 holes

die

2 pole

2 pole

For front mounting bolts

■ Terminal Arrangement M8 screw

3 pole For rear connecting studs

■ For Rear Connecting Studs

Applicable pressure type wire connector: 38mm2

R2

44

4-M4 tap holes or ø4-5 holes ø17 holes

2 pole Mounting plate M4 Mounting screw Breaker underside

Insulating tube

www.dienhathe.vn

M10 screw

S-100S Tripping Time (%)

Tripping Time

Base ambient temperature 40ºC

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

Temperature Compensation Curve

3 pole

ww

2 pole

w.

die

■ Drilling Plan

2 pole

For front mounting bolts

■ Terminal Arrangement

3 pole

For rear connecting studs

■ For Rear Connecting Studs Breaker underside Max. applicable pressure type wire connector: 38mm2

Mounting plate

M8 screw

Insulating bushing Bus or pressure wire connector connection

Insulating pipe Insulating pipe M10 screw 2 pole

www.dienhathe.vn

3 pole

45

Hr.

Hr.

FXK125-S / FXK125-H (MFXK100-S)

Min.

Min. value Sec.

Min. value

Max. interrupting time

Max. value of 31 to 50A

Current (percent rated current)

Overcurrent Tripping Characteristic Curve (15-30A)

Overcurrent Tripping Characteristic Curve (31-125A)

nh ath

e.x

■ Dimensions

ww

w.

die

■ Drilling Plan

For front mounting bolts

■ Terminal Arrangement

For rear connecting studs

■ For Rear Connecting Studs

Max. applicable pressure type wire connector: 60mm2 (22mm2)

9.5

24

22

M8 screw (M6 screw)

Bus or pressure wire connector connection (

): dimensions only for 50A or less

Applicable wire connector: 1.6 to 22mm2

Wire connection (15 to 50A) Dimensions are only for 60A to125A

46

Max. interrupting time

Current (percent rated current)

yz

Sec.

Tripping Time

Max. value

Tripping Time

Min.

Max. value of 51 to 125A

www.dienhathe.vn

Hr.

L-100E Tripping Time

Min.

Max. value of 31 to 100A Max. value of less than 30A Base ambient temperature 40ºC

Min. value of less than 30A

Tripping Time (%)

Sec.

Min. value of 31 to 100A

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

Temperature Compensation Curve

(4)-M4 tap holes or ø(4)5 holes

w.

(4)-M4 tap holes or ø(4)5 holes

die

■ Drilling Plan

ww

3 pole

3 pole

For front mounting bolts

■ Terminal Arrangement

(6)ø17 holes

For rear connecting studs

■ For Rear Connecting Studs

Max. applicable pressure type wire connector: 38mm2 (22mm2)

Breaker underside

M8 screw (M6 screw)

Bus or pressure wire connector connection (

): dimensions only for 50A or less

Insulating bushing

Applicable wire connector: 1.6 to 22mm2 M10 screw (M8)

Insulating pipe (60 to 100A)

3 pole Wire connection (15 to 50A)

www.dienhathe.vn

(

): dimensions only for 50A or less

47

Hr. Max. value

Cold start max. value

Tripping Time

Hot start max. value

Sec.

Min. value

Max. interrupting time

S-225SB

Min. value

Max. interrupting time

Sec.

Tripping Time

Min.

(MS-225SB)

Min.

Hr.

S-225SB

Current (percent rated current)

MS-225SB

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

e.x

Base ambient temperature 40ºC

nh ath

Compensation rate of rated current (%)

(4) Mounting holes for M4 screw

Ambient Temperture (ºC)

Temperature Compensation Curve

3 pole

■ Drilling Plan

(4) M4 tap holes or ø(4) 5 holes ø(6) 28 holes

ww

w.

(2) M4 tap holes or ø(2) 5 holes

die

2 pole

For front mounting bolts

■ Terminal Arrangement Maximum applicable pressure type-wire connector = 60mm2 Special pressure type wire connector is attached for 175 – 225A as shown on the right table

For rear connecting studs

■ For Rear Connecting Studs

Breaker underside

Rated current (A) Applicable wire size of pressure type wire connector (mm2) 175 – 225 Pressure type wire connector 80, 100, 125 (mm) ø10 holes

Pressure type wire connector directly connected

48

www.dienhathe.vn

Hr. Max. value

Cold start max. value Hot start max. value

Tripping Time

Tripping Time

Min. Sec.

Min. value

Max. interrupting time

SXK225

Min. value

Sec.

(MSKX225)

Min.

Hr.

SXK225

Max. interrupting time

MSXK225

Current (percent rated current)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

Compensation rate of rated current (%)

e.x

Base ambient temperature 40ºC

Phase separator

Trip button

nh ath

Screw of slide cover

Ambient Temperture (ºC)

Temperature Compensation Curve

2-M4 Mounting screw hole

die

2-M4 screw holes or ø5 holes

2-M4 screw holes or ø5 holes ø(6) 28 hole

ww

w.

■ Drilling Plan

For front mounting bolts

■ Terminal Arrangement Terminal Arrangement

For rear connecting studs

■ For Rear Connecting Studs

Max. applicable crimping terminal: 150mm2

46

ø10 hole

M8 screw

A system studs (Standard)

24

Manufacturing of terminal

Crimping terminal directly connected

61 68 95

www.dienhathe.vn

25 right and left pole

t6.5

B system studs

56 center pole 70 right and left pole 110 center pole

49

Hr.

FXK250-S / FXK250-H

Max. value

Tripping Time

Min.

Base ambient temperature 40ºC

Sec.

Min. value Max. interrupting time

Compensation rate of rated current (%)

(MFXK225-S)

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

nh ath

Phase insulator (Removable)

e.x

■ Dimensions

Trip button

■ Drilling Plan

2-M4 screw holes or ø5 holes ø6-28 holes

ww

w.

2-M4 screw holes or ø5 holes

die

2-M4 Mounting holes

For front mounting bolts

■ Terminal Arrangement Maximum applicable pressure type-wire connector = 60mm2 Special pressure type wire connector is attached for 175 – 225A as shown on the right table

For rear connecting studs

■ For Rear Connecting Studs

Rated current (A) Applicable wire size of pressure type wire connector (mm2) 175 – 225 Pressure type wire connector 80, 100, 125 (mm)

Pressure type wire connector directly connected

50

www.dienhathe.vn

Hr.

L-225E Tripping Time

Min.

Max. value

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Sec.

Min. value

Current (percent rated current)

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

Ambient Temperture (ºC)

Temperature Compensation Curve

ww

w.

die

■ Drilling Plan

For front mounting bolts

■ Terminal Arrangement

For rear connecting studs

■ For Rear Connecting Studs

Max. applicable pressure-type Wire connector: 100mm2

ø9 hole A system studs (Standard) B system studs (Customer-changeable)

Bus or pressure-type wire connector connection

Right and left poles Center pole

www.dienhathe.vn

51

Hr.

S-400S/F-400R /L-400E

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Min. value Sec.

Tripping Time

Min.

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

ww

w.

die

■ Drilling Plan

Position of mounting screw special nuts attached

For front mounting bolts

■ For front connection

For rear connecting studs

■ For Rear Connecting Studs

M10 bolt

A system studs (Standard) B system studs (Customer-changeable)

Pressure-type wire connector connection Right and left poles Center pole

52

www.dienhathe.vn

Hr.

Max. interrupting time

Sec.

Tripping Time

Min.

SX400 / FX400

Current (percent rated current)

200A setting 400A setting

yz

Overcurrent Tripping Characteristic Curve

Right and left poles

Phase separator 4-M6 screw hole Center poles

nh ath

Screw of slide cover

Trip button

die

■ Drilling Plan

e.x

■ Dimensions

4-M6 screw hole or ø7 hole

ww

w.

4-M6 screw hole or ø7 hole

6-ø35 hole

For front mounting bolts

■ Terminal Arrangement

M10 bolt

For rear connecting studs

■ For Rear Connecting Studs

Max. applicable crimping terminal: 200mm2 x 1 (w-terminal)

Insulating tube (center pole)

A system studs (Standard) B system studs (Customer-changeable) Crimpint terminal connection (ex. crimping terminal 100mm2 x 2 pcs.)

Right and left poles

Center pole

www.dienhathe.vn

53

Hr.

S-600S/F-600F/L-600E

Min.

Max. value

Magnetic trip range (in 4 steps)

Sec.

Position of setting

Max. interrupting time

Base ambient temperature 40ºC

Compensation rate of rated current (%)

Tripping Time

Min. value

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

■ Drilling Plan

(4) M6 tap holes or ø(4) 7 holes ø(6) 48 holes

ww

w.

(4) M6 tap holes or ø(4) 7 holes

die

194 when the auxilary handle is attached.

For front mounting bolts

■ For front connection

M12 bolt

For rear connecting studs

■ For Rear Connecting Studs

ø13.5 hole

Standard mounting of bar studs are flatwise A system Bar studs are mounted edgewise, If orders as (B system studs)

Pressure-type wire connector connection

204 when the auxilary handle is attached.

54

www.dienhathe.vn

Hr.

Max. interrupting time

Sec.

Tripping Time

Min.

SX600 / FX600

Current (percent rated current)

300A setting 600A setting

yz

Overcurrent Tripping Characteristic Curve

Phase separator

4-M6 screw hole

nh ath

Center poles

e.x

■ Dimensions

Trip button

4-M6 screw hole or ø7 hole

die

■ Drilling Plan

ww

w.

4-M6 screw hole or ø7 hole

ø48 hole

For rear connecting studs

For front mounting bolts

■ Terminal Arrangement

M12 bolt

■ For Rear Connecting Studs ø13.5 hole 4-M6 screw hole

Max. applicable crimping terminal: 200mm2 x 2

A system studs (Standard) B system studs

Crimpint terminal connection (ex. crimping terminal 200mm2 x 2)

www.dienhathe.vn

55

Hr. Min.

Max. value

Magnetic trip range (in 4 steps)

Tripping Time

Min. value

Sec.

Position of setting Max. interrupting time

Base ambient temperature 40ºC Compensation rate of rated current (%)

S-800S / F-800R / F-800RH / L-800E

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

■ Drilling Plan

(4) M6 tap holes or ø(4) 7 holes ø(6) 48 holes

ww

w.

(4) M6 tap holes or ø(4) 7 holes

194 when the auxilary handle is attached.

die

nh ath

e.x

■ Dimensions

For front mounting bolts

■ For front connection

For rear connecting studs

■ For Rear Connecting Studs

ø13.5 hole

M12 bolt

Standard mounting of bar studs are flatwise A system Bar studs are mounted edgewise, If orders as (B system studs)

204 when the auxilary handle is attached.

56

www.dienhathe.vn

Hr.

Max. interrupting time

Sec.

Tripping Time

Min.

SX800 / FX800

Current (percent rated current)

400A setting 800A setting

yz

Overcurrent Tripping Characteristic Curve

Phase separator

nh ath

4-M6 screw hole

e.x

■ Dimensions

Trip button

4-M6 screw hole or ø7 hole

die

■ Drilling Plan

ww

w.

4-M6 screw hole or ø7 hole

ø48 hole

For front mounting bolts

■ Terminal Arrangement

For rear connecting studs

■ For Rear Connecting Studs ø13.5 hole 4-M6 screw hole

M12 bolt

A system studs (Standard) B system studs

www.dienhathe.vn

57

Setting range at short limit

Hr. 1000A setting

500A setting

F-1000C

Tripping Time

Max. interrupting time

Sec.

Max. interrupting time

Sec.

Tripping Time

Min.

Min.

Hr.

F-1000C / F-1200C

Setting range at short limit

Current (A)

1200A setting

F-1200C

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

ww

w.

die

■ Drilling Plan

For front mounting bolts

■ For front connection

For rear connecting studs

■ For Rear Connecting Studs

M12 bolt

58

www.dienhathe.vn

600A setting

Hr.

Hr.

F-1000K / F-1200K

Max. value

Max. value

Min. Tripping Time

Magnetic trip range (in 4 steps)

Min. value

Position of setting

Lo

Hi

F-1000K

Max. interrupting time

Magnetic trip range (in 4 steps)

Position of setting

Sec.

Tripping Time Sec.

Min.

Min. value

Current (percent rated current)

Hi

Lo

Max. interrupting time

F-1200K

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

nh ath

Compensation rate of rated current (%)

e.x

Base ambient temperature 40ºC

Ambient Temperture (ºC)

Temperature Compensation Curve

ww

w.

die

■ Drilling Plan

For front mounting bolts

■ For front connection

For rear connecting studs

■ For Rear Connecting Studs

M12 bolt

www.dienhathe.vn

59

Tripping Time

Min.

Hr.

FX1000 / FX1200

Sec.

Max. interrupting time

FX1000 500A setting FX1200 600A setting

Current (percent rated current)

yz

Overcurrent Tripping Characteristic Curve

4-M8 screw hole

Phase separator ø13.5 hole

Trip button

4-M8 screw hole or ø10 hole

ww

w.

die

4-M8 screw hole or ø10 hole

nh ath

Auxiliary handle

■ Drilling Plan

e.x

■ Dimensions

FX1000 1000A setting FX1200 1200A setting

For front mounting bolts

■ Terminal Arrangement

M12 bolt

For rear connecting studs

■ For Rear Connecting Studs

4-M8 screw hole

Auxiliary handle

ø13.5 hole

A system studs (Standard) B system studs

60

www.dienhathe.vn

Hr. Sec.

Tripping Time

Min.

F-1600CB

Max. interrupting time

Setting range at short limit

1600A setting

800A setting

Current (A)

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

4-M8 tap holes or ø4-10 holes

die

■ Drilling Plan

ww

w.

320 and more

4-M8 tap holes or ø4-10 holes

For front mounting bolts

■ Terminal Arrangement

For rear connecting studs

■ For Rear Connecting Studs ø12 hole

4-Mounting holes for M8 screw

Standard mounting of bar studs are flatwise A system

less than 15 for connecting of conductor M10 x 50 bolt

www.dienhathe.vn

Bar studs are mounted edgewise, If orders as (B system studs)

61

Hr. Tripping Time Sec.

Min.

F-1600B

Magnetic trip range (in 4 steps) Position of setting Lo

Max. interrupting time

Hi

Current (percent rated current)

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

die

■ Drilling Plan

4-M8 tap holes or ø4-10 holes

ww

w.

320 and more

4-M8 tap holes or ø4-10 holes

For front mounting bolts

■ Terminal Arrangement

For rear connecting studs

■ For Rear Connecting Studs ø12 hole

4-Mounting holes for M8 screw

Standard mounting of bar studs are flatwise A system less than 15 for connecting of conductor M10 x 50 bolt

Bar studs are mounted edgewise, If orders as (B system studs)

ø12 hole

62

www.dienhathe.vn

Hr.

F-1600E

[T1] Setting range

[I2] Setting range

Sec.

Tripping Time

Min.

Rated current

[T2] Setting range

[I3] Setting range

Current (percent rated current)

yz

Overcurrent Tripping Characteristic Curve

die w.

■ For Rear Connecting Studs

ww

■ Drilling Plan

nh ath

e.x

■ Dimensions

www.dienhathe.vn

63

DIMENSIONS

OF

4

POLE BREAKERS

yz

F-60R 4 pole

For rear connecting studs

e.x

For front mounting bolts

Drilling plan

die

nh ath

F-100S 4 pole

For rear connecting studs

For front mounting bolts

w. ww

F-100KB 4 pole

Drilling plan

For rear connecting studs

For front mounting bolts

Drilling plan

64

www.dienhathe.vn

yz

F-250FB / F-250KC 4 pole

nh ath

e.x

L-225E 4 pole

For rear connecting studs

Drilling plan

For front mounting bolts

For rear connecting studs

Drilling plan

ww

F-600F / L-600E 4 pole

w.

die

F-400R / L-400E 4 pole

For front mounting bolts

For front mounting bolts

For rear connecting studs Drilling plan

www.dienhathe.vn

65

yz

F-800R / L-800RH 4 pole

For front mounting bolts

For rear connecting studs

e.x

Drilling plan

nh ath

F-1000K, F-1200K 4 pole F-1000C, F-1200C 4 pole

For front mounting bolts

die Auxiliary handle

Trip button

w.

Phase separator ø13.5 hole

ww

F-1600CB 4 pole F-1600B 4 pole 4-M8 screw hole

For rear connecting studs Drilling plan

For front mounting bolts

For rear connecting studs

Drilling plan

66

www.dienhathe.vn

EARTH LEAKAGE BREAKERS AND EARTH LEAKAGE RELAYS This is a combination of a Fuse-Free Breaker and a leakage current detector for preventing fire or electric shock due to deterioration of electric insulation. It will provide perfect protection of a circuit against overload,

■ Principle of operation This device is composed of a zero phase current transformer for detecting leakage current, a control circuit, and a Fuse-Free Breaker with a shunt trip.

nh ath

As shown in Fig. 37, magnetic fluxes cancel out each other, inducing no output voltage in the secondary coil while no leakage is present in the load circuit.

e.x

yz

short-circuit, or earth leakage.

i1 + i2 + i3 = 0

If leakage current (lg) occurs in the load circuit, magnetic flux øg is induced, producing a certain voltage across the secondary coil. i1 + i2 + i3 = ig

die

The induced voltage is supplied to the shunt trip coil of the FuseFree Breaker, through a control circuit composed of diodes and semiconductor control elements, to break the circuit.

Fig. 37 Principle of operation

cLassification and coMposition

R Series

w.

Standard Breaker

High Interrupting Breaker

Earth Leakage Relay Series

ww

E Series

30A – 800A frame

100A – 1200A frame

www.dienhathe.vn



67

R atings Table 19

E

and

specifications

series Type

EB-50E

EB-100E

EX30

EX50

EX50B

EX50C

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

Appearance

Phase- wiring Sysytem

1ø2W

3ø3W 1ø3W 1ø2W

Number of poles

2

3

3

3

3

3

100 – 200

100 – 200

200 – 440

200 – 440

100 – 200

200 – 440

Rated Current (A) (Base ambient temperature 40ºC)

5 10 15 20 30 40 50

60 75 100

5 10 15 20 30

5 10 15 20 30 40 50

Rated Impulse withstand Voltage Uimp (kV)

4

4

6

6

6

6

30 100

30 100 ∙200 ∙500

30 100 ∙200 ∙500

(15) 30 100 (200)

30 100 ∙200 ∙500

0.1

0.1

0.1





(100 ∙200 ∙500 )





(0.3)





(0.1)

0.1

0.1

0.1







Operating time (sec. or less) Limiting non-actuating time (sec. or more)













Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

440V





2.5 / 1

2.5 / 1



10 / 3

415V





2.5 / 1

2.5 / 1



10 / 3

400V





2.5 / 1

2.5 / 1



10 / 3

JIS C 8201-2-2 Ann2

AC

(Icu/Ics)

240V



200V

5/2

100V

96

c

60

d

76

Net Weight (kg)

0.3

Phase Separator for Line Side Test Button Lead Wire

TBL

0.4

130

60

60

76

84

84

84

84

○ ○ ○ ○

○ ○ ○ ○

○ ○ ○ ○

○ ○ ○















○ ○

○ ○

○ ○

○ ○



GKW (STB)



GK∙ GKW (BSD)





STB-2M

STB-2M

STB-2M

STB-2M













































MIW-2E

MIW-2E

MIW-2E

MIW-2E

























LC-03

LC-03

LC-2G

LC-2G

LC-2G

LC-2G





HL-2G

HL-2G

HL-2G

HL-2G

HA





HA-108

HA-108

HA-108

HA-108

HM





HM-S12

HM-S12

HM-S12

HM-S12

TMC

TMC-0G

TMC-0H

TMC-1

TMC-1

TMC-1

TMC-1

Short type





TMC-1S

TMC-1S

TMC-1S

TMC-1S

Long type





TMC-2D

TMC-2D

TMC-2D

TMC-2D

BTC





BTC-1

BTC-1

BTC-1

BTC-1













Automatic Tripping Device

Full Magnetic

Full Magnetic

Full Magnetic

Full Magnetic

Full Magnetic

Full Magnetic

Trip Button













Terminal Cover

Front Type Rear Type

IEC Rail 35 mm

Attention 1. 2. 3. 4. 5. 6. 7. 8.

● : Standard ○ : Option Please use right and left poles in case of using ELBs of 3 poles 200V to 1ø2W 200V wiring sysytem. Please connect neutral line to middle pole of ELBs incase of using ELBs of 3 poles 200V to 1ø3W100 / 200V distribution system. Standard flush mounting base assembly of up to 400AF are GKW and GK is standard in case of 600AF or more. Installation of phase separators is required in case of types marked (*2) IEC rail is standard installation in case of EB-50E and EB-100E, so installation screws and metal fittings are not attached. The accessories marked (*3) can be installed by customers Please state frequency 50 or 60Hz in case of RF-800KN, RF-1000KN, RF-1200KN.

68

● (*2)



ww

Handle Operating Mechanism

130

60

○ ○ ○



LC

130

60



○ ○ ○

STB

HL

130

60



BSD

Lock Cover

97.5

0.7



Handle Lock

75

Front Terminal

TB2

MMK-C



75

0.7



MIW

10 / 3

75

Front Terminal



MMK-S



75

0.7

TB

Motor-operating Mechanism



75

Front Terminal

EAL

Mechanical Interlock

5/2

0.7

Earth Leakage Alarm Sw.

PK

35 / 9 35 / 9

Front Terminal

AL

Plug-in Mounting Base Assembly

— 10 / 3

0.6

AUX

Flush Mounting Base Assembly

5/2 5/2

Front Terminal

Alarm Switch

Rear-connecting Stud

5/2

5/2

Front Terminal

Auxiliary Switch

Terminal Block

Exterior Accessories

75

b

Standard Connection Type

Interior Accessories

5/2 50



5/2

w.

Dimensions (mm)

a

d c

b

a

e.x

Operating time (sec. or less) Rated Sensitivity Current (mA)

Indication of Earth Leakage

Rated Breaking Capacity (kA)

5 10 15 20 30 40 50

(15) 30 (100)

nh ath

Time Delay Type

5 10 15 20 30 40 50

Rated Sensitivity Current (mA)

die

High Speed Type

yz

3

Rated Voltage (AC V)

www.dienhathe.vn

R atings

and

S pecifications

EX100

EX100B

EX225

EXK225

EX400

EX400B

EX600B

EX800B

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3

3

3

3

3

3

3

200 – 440

200 – 440 (100 – 200)

200 – 440 (100 – 200)

200 – 440 (100 – 200)

200 – 440

200 – 440

200 – 440

50 60 75 100

50 60 75 100

125 150 175 200 225

125 150 175 200 225

250 300 350 400

6

6

6

6

8

(15) 30 100 (200)

30 100 ∙200 ∙500

30 100 ∙200 ∙500

30 100 ∙200 ∙500

(30) 100 ∙200 ∙500

yz

3 100 – 200

200 / 225 / 250 300 / 350 / 400 adjustable

300 / 350 / 400 500 / 600 adjustable

400 / 450 / 500 600 / 700 / 800 adjustable

8

8

8

(30) 100 ∙200 ∙500

100 ∙200 ∙500

100 ∙200 ∙500

0.1

0.1

0.1

0.1

0.1

0.1

0.1



(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )



(0.3)

(0.3 0.6 1.2)

(0.3 0.6 1.2)

(0.3 0.6 1.2)

(0.3 0.6 1.2)

(0.3 0.6 1.2)

(0.3 0.6 1.2)



(0.1)

(0.1 0.2 0.5)

(0.1 0.2 0.5)

(0.1 0.2 0.5)

(0.1 0.2 0.5)

(0.1 0.2 0.5)

(0.1 0.2 0.5)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)



10 / 3

15 / 8

15 / 8

36 / 18

36 / 18

36 / 18

36 / 18



10 / 3

15 / 8

15 / 8

36 / 18

36 / 18

36 / 18

36 / 18



10 / 3

15 / 8

15 / 8

36 / 18

36 / 18

36 / 18

36 / 18

35 / 9

35 / 18

35 / 9

35 / 18

10 / 3





75

75

105

130

130

165

60

60

60

84

85

0.9

2.2

Front Terminal

Front Terminal

○ ○ ○ ○

● (*2)

○ ○ ○

○ ○ ○







○ ○

○ ○

○ ○

STB-3K (50A:STB-2M)

STB-3K (50A:STB-2M)























MIW-2E

MIW-2E









LC-2G

LC-2G

35 / 18

50 / 25

50 / 25

50 / 25

50 / 25

35 / 18

50 / 25

50 / 25

50 / 25

50 / 25











105

140

140

210

210

165

257

257

274

274

68

103

103

103

103

93

133

133

141

141

2.2

6.6

6.5

10.6

12.9

Front Terminal

Front Terminal

Front Bar Terminal

Front Bar Terminal

Front Bar Terminal

Front Bar Terminal

● (*2)

● (*2)

● (*2)

● (*2)

● (*2)

● (*2)



○ ○ (*3) ○ (*3)



○ (*3) ○ (*3)

○ ○ ○

○ ○ (*3) ○ (*3)











○ ○

○ ○

○ ○

○ ○

○ ○































die

84 0.8

nh ath

— 10 / 3

e.x

0.1

○ (*3) ○ (*3)







○ (GK)

○ (GK)













MIW-4F

MIW-4L



MIW-5F

MIW-5G

MIW-5G

























LC-4E

LC-2F









ww

w.



HL-2G

HL-2G

HL-4E

HL-2F

HL-5

HL-5

HL-6

HL-6

HA-108

HA-108

HA-207

HA-209

HA-405

HA-406

HA-402

HA-402

HM-S12

HM-S12

HM-S22

HM-S23









TMC-1

TMC-1

TMC-4K

TMC-4J

TMC-5B

TMC-5B

TMC-5D

TMC-5D

TMC-1S

TMC-1S

TMC-4JS

TMC-4JS









TMC-2D

TMC-2D













BTC-1

BTC-1

BTC-4G

BTC-4J

BTC-5B

BTC-5B





















Full Magnetic

Full Magnetic

Thermal-Magnetic

Thermal-Magnetic

Thermal-Magnetic

Electric Relay

Electric Relay

Electric Relay

















9. Applicable voltage range Rated voltage 100 – 200V 440V 200 – 440V

Applicable circuit voltage 100 ∙ 110 ∙ 200 ∙ 220V 400 ∙ 415 ∙ 440V 200 ∙ 220 ∙ 240 380 ∙ 400 ∙ 415 ∙ 440V

Permissible range of voltage 80 – 242V 320 – 484V 160 – 484V

www.dienhathe.vn

69

R

Table 20

series Type

RXK125-S

RXK125-H

RX100

RXK250-S

RXK250-H

RG-225BN RG-225BH

RX400

RX400B

Phase- wiring Sysytem

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø4W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø4W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

Number of poles

3

3

4

3

3

4

3

3

200 – 440

200 – 440 (100 – 200)

200 – 440

250 300 350 400

200 / 225 / 250 300 / 350 / 400 adjustable

8

8

Appearance

Rated Current (A) (Base ambient temperature 40ºC)

Rated Sensitivity Current (mA) Operating time (sec. or less) Rated Sensitivity Current (mA) Operating time (sec. or less) Limiting non-actuating time (sec. or more) Indication of Earth Leakage

JIS C 8201-2-2 Rated Ann2 Breaking (Icu/Ics) Capacity (kA)

8

(0.3 ∙ 0.6 ∙1.2) (0.3 ∙ 0.6 ∙1.2) (0.3 ∙ 0.6 ∙1.2)



(0.3 ∙ 0.6 ∙1.2)

(0.3 ∙ 0.6 ∙1.2)

(0.1 0.2 0.5) (0.1 0.2 0.5) (0.1 0.2 0.5)



(0.1 0.2 0.5)

(0.1 0.2 0.5)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

50 / 25

50 / 25

30 / 15

50 / 25

50 / 25

30 / 15

50 / 25

100 / 50





a

90

90

b

150

150

c

68

68

d

94

94

Net Weight (kg)

2.1

2.1

Standard Connection Type

Front Terminal

Front Terminal ● (*2)



○ ○ (*3) ○ (*3)

Alarm Switch

AL

Auxiliary Switch

AUX

○ (*3) ○ (*3)

Earth Leakage Alarm Sw.

EAL



TB

○ ○ STB-2S (Up to 50A)

Mechanical (button)

Mechanical (button)

50 / 25

42 / 21

50 / 50

50 / 50

50 / 25

42 / 21

50 / 50

50 / 50

50 / 25

30 / 15

50 / 25

42 / 21

50 / 50

50 / 50

85 / 43

50 / 25

100 / 50

85 / 43

100 / 100

100 / 100

85 / 43

50 / 25

100 / 50

85 / 43

100 / 100

100 / 100













120

105

105

185

140

140

150

165

165

345

275

275

103

68

68

103

103

103

123

95

95

133

133

133

2.8

2.0

2.0

9.3

6.6

6.6

Front Terminal

○ ○ ○ ○

die

● (*2) TBL

Front Terminal Front Terminal

Front Terminal

Front Bar Terminal Front Bar Terminal

● (*2)

● (*2)

● (*2)

● (*2)

● (*2)





○ (*3) ○ (*3)

○ ○ ○



○ (*3) ○ (*3)

○ ○ ○

○ (*3) ○ (*3)















○ ○

○ ○

○ ○

○ ○

○ —

○ ○

○ ○

STB-2S (Up to 50A)























○ —

GKW (STB)

○ (Up to 50A) ○ (Up to 50A)

w.

BSD

BSD-3S BSD-3S (60A or more) (60A or more)

GK∙GKW (BSD) ○ (60A or more) ○ (60A or more) PK

















○ (GK)





















Mechanical Interlock

MIW

MIW-3H

MIW-3H

MIW-3F

MIW-4M

MIW-4M

MIW-5DE



MIW-5F

Motor-operating Mechanism

MMK-S

































○ ○

LC-2C

LC-4J

LC-4J







HL

○ ○



HL-4J

HL-4J

HL-5

HL-5

HL-5

HA





HA-106

HA-210

HA-210

HA-405

HA-405

HA-406

MMK-C

Lock Cover

LC

Handle Lock Handle Operating Mechanism Terminal Cover

ww

Exterior Accessories

HM

HM-S13

HM-S13

HM-S11

HM-S25

HM-S25







Front Type

TMC

TMC-2C

TMC-2C

TMC-3C

TMC-4J

TMC-4J

TMC-5B

TMC-5B

TMC-5B

Short type







TMC-4JS

TMC-4JS







Long type

















Rear Type

BTC

BTC-2C

BTC-2C

BTC-3C

BTC-4J

BTC-4J

BTC-5B

BTC-5B

BTC-5B

IEC Rail 35 mm

















Automatic Tripping Device

ThermalMagnetic

ThermalMagnetic

Full Magnetic

ThermalMagnetic

ThermalMagnetic

Thermal-Magnetic

ThermalMagnetic

Electronic Relay

Trip Button

















Attention 1. 2. 3. 4. 5. 6. 7. 8.

● : Standard ○ : Option Please use right and left poles in case of using ELBs of 3 poles 200V to 1ø2W 200V wiring sysytem. Please connect neutral line to middle pole of ELBs incase of using ELBs of 3 poles 200V to 1ø3W100 / 200V distribution system. Standard flush mounting base assembly of up to 400AF are GKW and GK is standard in case of 600AF or more. Installation of phase separators is required in case of types marked (*2) IEC rail is standard installation in case of EB-50E and EB-100E, so installation screws and metal fittings are not attached. The accessories marked (*3) can be installed by customers Please state frequency 50 or 60Hz in case of RF-800KN, RF-1000KN, RF-1200KN.

70

0.1

(0.3 ∙ 0.6 ∙1.2)

30 / 15

STB

0.1

(0.1 0.2 0.5)

30 / 15

Rear-connecting Stud

0.1

(0.3 ∙ 0.6 ∙1.2)

415V

TB2

0.1

(0.1 0.2 0.5)

100V

b

0.1

440V

Phase Separator for Line Side

8

100 ∙200 ∙ 500

(0.3 ∙ 0.6 ∙1.2)

200V

Plug-in Mounting Base Assembly

0.1

30 30 100 ∙200 ∙500 100 ∙200 ∙500

(0.1 0.2 0.5)

50 / 25

Flush Mounting Base Assembly

8

(100 ∙200 ∙500 ) (100 ∙200 ∙500 )

100 / 50

Terminal Block

8

125 150 175 200 225



30 / 15

Test Button Lead Wire

125 150 175 200 225 250

(100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100 ∙200 ∙500 ) (100∙200∙500 )

30 100 ∙200 ∙500

0.1

50 / 25

Dimensions (mm)

125 150 175 200 225 250

30

0.1

240V

d c

8

200 – 440

(30) (30) 100 ∙200 ∙500 100 ∙200 ∙500

30 30 100 ∙200 ∙500 100 ∙200 ∙500

400V

AC

a

Interior Accessories

8

200 – 440

nh ath

Time Delay Type

200 – 440

15 20 30 40 50 16 20 30 40 50 5 10 15 20 30 40 63 75 100 125 63 75 100 125 50 60 75 100

Rated Impulse withstand Voltage Uimp (kV) High Speed Type

200 – 440

yz

200 – 440

e.x

Rated Voltage (AC V)

www.dienhathe.vn

R atings

RG-400BH

RF-600FN

RX800B

RF-800KN

3ø4W

3ø3W 1ø3W 1ø2W

3ø4W

3ø3W 1ø3W 1ø2W

3ø4W

3ø3W 1ø3W 1ø2W

3ø4W

3ø3W 1ø3W 1ø2W

3ø3W 1ø3W 1ø2W

3ø4W

3ø3W 1ø3W 1ø2W

4

3

4

3

4

3

4

3

3

4

3

200 – 440

200 – 440

440 (200)

200 – 440

440 (200)

250 300 350 400

300 / 350 / 400 500 / 600 adjustable

500 600

400 / 450 / 500 600 / 700 / 800 adjustable

8

8

8

8

8

8

100 ∙200 ∙500

50 ∙100 ∙200 500 ∙1000

100 ∙200 ∙500

50 ∙100 ∙200 500 ∙1000

50 ∙100 ∙200 500 ∙1000

0.1

0.1

100 ∙200 ∙500

30

440 (200)

700 800

1000

0.1

0.1



(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(0.3 0.6 1.2)



(0.3 0.6 1.2)

(0.3 1.2)

(0.3 0.6 1.2)

(0.3 1.2)

(0.1 0.2 0.5)



(0.1 0.2 0.5)

(0.1 0.5)

(0.1 0.2 0.5)

(0.1 0.5)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

440 (200)

0.1

RF-1200CBN

440 (200) 600 / 700 / 800 1000 / 1200 adjustable

1200

8

8

8

50 ∙100 ∙200 500 ∙1000

50 ∙100 ∙200 500 ∙1000

50 ∙100 ∙200 500 ∙1000

0.1

0.1

0.1

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(100 ∙200 ∙500 )

(0.3 1.2)

(0.5 1.2)

(0.3 1.2)

(0.5 1.2)

(0.1 0.5)

(0.2 0.5)

(0.1 0.5)

(0.2 0.5)

Mechanical (button)

Mechanical (button)

Mechanical (button)

Mechanical (button)

50 / 50

42 / 21

50 / 50

85 / 22

50 / 50

42 / 21

50 / 50

85 / 22

42 / 21

50 / 50

42 / 21

50 / 50

85 / 22

85 / 22

85 / 22

85 / 22

85 / 22

85 / 43

100 / 100

85 / 43

100 / 100

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

85 / 43

100 / 100

85 / 43

100 / 100

125 / 32

125 / 32

125 / 32

125 / 32

125 / 32

















185

210

280

210

345

274

580

274

103

103

141

103

133

141

179

141

10.6

23.0

12.9

10.2

85 / 22

85 / 22

85 / 22

85 / 22

85 / 22

85 / 22

280

210

280

210

210

— 280

210

800

800

800

800

185

185

185

185

185

225

225

225

225

225

50.0

41.0

60.0

41.0

41.0

800

60.0

41.0

Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal

● (*2)

● (*2)

● (*2)

● (*2)

○ ○ ○





○ (*3) ○ (*3)

○ ○ ○







○ —

○ ○

○ ○

















MIW-5DE

MIW-5G



— — —

● (*2)

● (*2)

● (*2)

● (*2)

○ ○ ○

○ ○ ○

○ ○ (*3) ○ (*3)

○ ○ ○

○ ○ (*3) ○ (*3)













○ ○

○ ○

○ ○

○ ○

○ ○

○ ○



































○ (GK)

○ (GK)



○ (GK)

○ (GK)

○ (GK)

○ (GK)

○ (GK)

















MIW-5G



























ww





● (*2)

die



○ (GK)

○ (*3) ○ (*3)

w.



○ (GK)



85 / 22

85 / 22

nh ath

42 / 21 42 / 21

Front Bar Terminal



























HL-5

HL-6

HL-6

HL-6











HA-405

HA-402

HA-402

HA-402

HA-801

HA-801

HA-801

HA-801

HA-801



















TMC-5B

TMC-5D

TMC-5D

TMC-5D

TMC-6

TMC-6

TMC-6B

TMC-6

TMC-6B



















































— BTC-5B — Thermal-Magnetic —

440 (200)

RF-1200KN

500 / 600 / 700 800 / 900 / 1000 adjustable

(100 ∙200 ∙500 )

Mechanical (button)

RF-1000CBN

e.x

0.1

RF-1000KN

S pecifications

RX600B

yz

RG-400BN

and

















Electronic Relay

ThermalMagnetic

Electronic Relay

ThermalMagnetic

ThermalMagnetic

Electronic Relay

ThermalMagnetic

Electronic Relay



















9. Applicable voltage range Rated voltage 100 – 200V 200V 440V 200 – 440V

Applicable circuit voltage 100 ∙ 110 ∙ 200 ∙ 220V 200 ∙ 220V 400 ∙ 415 ∙ 440V 200 ∙ 220 ∙ 240 380 ∙ 400 ∙ 415 ∙ 440V

Permissible range of voltage 80 – 242V 160 – 220V 320 – 484V 160 – 484V

www.dienhathe.vn

71

c onstRUction The Earth Leakage Circuit Breakers (ELB) consists of circuit breaker unit composed by a switching mechanism, are extinguishers, an over-current tripping device, etc., zero-phase sequence current transformer, amplifier and others for detecting earth leakage current. These components are accommodated in a heat-proof and arc-proof molded case and cover. A typical example of its construction is shown in the diagram below.

Handle

Arc extinguishing device

yz

Earth leakage tripping device

Quick-make, quick-break, trip-free mechanism

e.x

Earth leakage trip indicator

Test button

Over current tripping device

Amplifier

nh ath

Rated sensitivity current selector

Zero-phase sequence current transformer

Operating time selector (Time delay type)

die

Typical construction of Earth leakage breaker for power supply

Rated sensitivity current selector

Connecting terminal

w.

ZCT

Connecting terminal for ZCT

ww

Operating time selector

Connecting terminal for earth leakage relay

Reset button

Earth leakage trip indication

Test button

Typical construction of Earth leakage relays

72

www.dienhathe.vn

Output terminal

Table 21

Applicability of interior accessories

EB-50E EB-100E

EB-50E

Frame

EX30 EX50 EX50B EX50C EX100 EX100B

Poles Accessories

2

EX225 ✶ EXK225 ✶ RXK125-S ✶ RXK125-H ✶ RXK250-S ✶ RXK250-H

3

RG-225B (N) ✶ EX400B ✶ RX400B

✶ EX600B ✶ RX600B ✶ EX800B ✶ RX800B

RF-800KN RF-1000KN RF-1200KN ✶ RF1000CBN ✶ RF1200CBN

RF-600FN

3, 4

3

3, 4

3

3

Alarm Switch

AL

1C

1C

1C

2C

Auxiliary Switch

AUX

1C

1C

1C

2C

Alarm + Auxiliary

AL + AUX



1C

1C

1C

1C

Earth Leakage Alarm Switch

EAL



Alarm + Auxiliary + EAL Switch

AL + AUX + EAL

Test Button Lead Wire

TBL





Appearance

Time Delay Type

R-NZB

R-NZBT

ww

Rated Voltage (AC V) Frequency (Hz)

Rated Sensitivity Current (mA)

50 / 100 / 200 / 500 / 1000 (1) (30)

Operating Time (sec.)

0.1 or less

Alarm Contact a

b

Dimensions (mm)

d c

2C

1C

1C

1C

2C

2C

2C

2C

Equipped normaly

Equipped normaly

1C

1C

2C

2C

Equipped normaly

Equipped normaly

AL

Standard type Automatic Reset Type R-NZBK





EAL

AUX

Latched Type R-NZBL

100, 200, 240, 380, 415 50, 60 100 / 200 / 500 / 50 / 100 / 200 / 1000 / 2000(1) 500 / 1000 (1) (30) 0.3 0.1 or less (0.2 / 0.5 / 2 / 4 (1)) 0.3 1c + 1a

a

TBL

Relay: Automatic Reset Lamp: Latched R-NZBR

100 / 200 / 500 / 1000 / 2000(1) 0.3 (0.2 / 0.5 / 2 / 4 (1))

80

b

80

c

115

Weight (kg) Notes:

2C



High Speed Type

w.

Type-Form

2C

yz



die

Function

2C



Handle of Breaker

Earth Leakage Relays

2C

e.x



Remarks: (1) Handle of breaker (2) 2C: 1C is also available

Table 22

2C

nh ath



2C

0.45

(1) Interchangeable by manual operation. (2) Rating with ( ) are manufactured by customer’s order. (3) Rated Voltage Applicable Circuit Voltage Remarks 100V 200V 240V 380V 415V

100 ∙ 110V 200 ∙ 220V 230 ∙ 240V 380V 400 ∙ 415 ∙ 440 ∙ 460V (60Hz)

Interchangealbe by tap changing

www.dienhathe.vn

73

Contact Specifications Load

Resistive Load cosø = 1

Inductive Load cosø = 0.3, L / R = 7ms

Rated Thermal Current (A)

Rated Current (A)

Table 24

AC 120V

3

2

AC 240V

3

1.5

AC 415V

1

0.5

DC 24V

3

1.5

DC 100V

0.2

0.2

Zero-phase-sequence Current Transformer Maximum Available Wire Size

Aperture Diameter

Type

3

Vinyl-insulated 600V Wire (IV)

Polyethylene-Insulated 600V Wire (CV)

2-wire

3-wire

4-wire

2-wire

3-wire

ø15

14mm2 (88A)

8mm2 (61A)

8mm2 (61A)

2mm2 (33A)

ZR-30B

ø30

60mm2 (217A)

50mm2 (190A)

38mm2 (162A)

38mm2 (190A)

ZR-58B

ø58

250mm2 (556A)

200mm2 (469A)

150mm2 (395A)

ZR-65

ø65

325mm2 (650A)

250mm2 (556A)

200mm2 (469A)

ZR-80

ø80

500mm2 (842A)

500mm2 (842A)

325mm2 (650A)

ZR-120

Table 25

ø100

500mm x 4 (1,684A) 400mm x 6 (1,490A)

ø120

Z-400B

Z-600B

Number of Poles

3

Continuous Thermal Current (A)

4 400

Frequency (Hz) Rated withstand Current (kA)

A

220

100mm2 (365A)

200mm2 (560A)

150mm2 (480A)

400mm2 (870A)

325mm2 (760A)

250mm2 (655A)

600mm (1,140A)

2

400mm2 (870A)

2

600mm2 (1,140A)

600mm (1,140A)

2

1000mm (1,600A)

800mm (1,370A)

3

Z-1000B

4

3

800

Z-1200B

4

3

1000

Z-2000B

4

3

1200

4 2000

600 50, 60 150 (peak value)

Refer to Earth Leakage Relays Ditto

315

220

315

240

320

240

320

240

320

310

380

348

348

348

380

380

380

380

380

380

300

300

400

460

460

480

480

480

480

480

480

600

600

B

348

B1

400

C

187

214

187

214

214

239

214

239

214

239

242

284

11

15

11.2

16

12.3

17

12.3

17

13

18

30

42

ww

b b1

4

w.

Operating Time (sec.)

74

150mm2 (480A)

250mm2 (655A)

100 (peak value)

Rated Sensitivity Current

Weight (kg)

3

600

Rated Voltage (AC V)

Dimensions (mm)

200mm2 (560A)

Z-800B

die

Appearance

c

500mm (842A) 2

ZCT with Primary Conductors Type

14mm2 (105A)

2

350mm x 9 (1,950A) 400mm x 8 (1,490A)



a

2

2



22mm2 (135A)

nh ath

ZR-100

2

4-wire

2mm2 (33A)

e.x

ZR-15

2

yz

Table 23

www.dienhathe.vn

e aRtH L eaKage R eLaYs

w.

die

nh ath

e.x

yz

of

ww

a ppLication

www.dienhathe.vn

75

Hr.

diMensions

Tripping Time

Min.

EB-50E

Max.

Base ambient temperature 40ºC

Current (percent rated current)

yz

Tripping Time (%)

Sec.

Min.

Ambient Temperture (ºC)

e.x

Overcurrent Tripping Characteristic Curve ■ Dimensions

2-M4 mounting hole

2-M4 mounting hole

M5 screw

nh ath

Mounting fixture

Test button Earthleakage trip indicator

Earthleakage trip indicator

2-M4 screw hole or ø5 hole

2-M4 screw hole or ø5 hole

Direct-connected bus drilling

2 pole

ww

w.

■ Drilling Plan

die

Test button

Temperature Compensation Curve

1mm clearance on each side of handle

3 pole

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 14mm2

Applicable wire conductor ø1.6 – 22mm2

M5 screw

Bus or pressure-type wire connector connection

76

Wire connection

www.dienhathe.vn

Hr.

Max. value for 31A or more

Min.

EX30 / EX50 / EX50B Tripping Time

Max. value for 30A or less

Min. value

Tripping Time (%)

Sec.

Base ambient temperature 40ºC

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

e.x

2-mounting holes for M4 screw Rated sensitivity current selector (if provided)

nh ath

Earthleakage trip indicator

■ Drilling Plan

w.

2-M4 tap holes or ø5 holes

Direct-connected bus drilling

ww

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

ø5.5 holes

die

Test button

Temperature Compensation Curve

Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 14mm2 Applicable wire conductor ø1.6 – 22mm2

M5 screw

www.dienhathe.vn

77

Hr.

Max. value for 31A or more

Min.

EX50C Tripping Time

Max. value for 30A or less

Min. value

Tripping Time (%)

Sec.

Base ambient temperature 40ºC

Current (percent rated current)

Ambient Temperture (ºC)

■ Dimensions 2-mounting holes for M4 screw

e.x

Phase separator

Rated sensitivity current selector (if provided)

nh ath

Earth leakage indicator

ww

w.

2-M4 tap holes or ø5 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 14mm2

M5 screw

78

Direct-connected bus drilling

die

Test button

■ Drilling Plan

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

Applicable wire conductor ø1.6 – 22mm2

www.dienhathe.vn

Hr.

EB-100E Tripping Time

Min.

Max.

Base ambient temperature 40ºC

Sec.

Tripping Time (%)

Min.

Current (percent rated current)

yz

Overcurrent Tripping Characteristic Curve

2-mounting hole

nh ath

M8 screw

Test button

ø5.5 holes

Direct-connected bus drilling

ww

w.

2-M4 screw hole or ø5 hole

Temperature Compensation Curve

die

Earthleakage trip indicator

■ Drilling Plan

e.x

■ Dimensions Mounting fixture

Ambient Temperture (ºC)

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection Max. applicable pressure-type wire connector: 38mm2

M8 screw

www.dienhathe.vn

79

Hr.

EX100 Tripping Time

Min.

Max. value

Base ambient temperature 40ºC

Sec.

Tripping Time (%)

Min. value

Current (percent rated current)

Ambient Temperture (ºC)

■ Dimensions

e.x

Mounting hole for M4 screw

nh ath

Earth leakage indicator

Test button

ww

w.

2-M4 tap holes or ø5 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Max. applicable pressure-type wire connector: 38mm2 M8 screw

Direct-connected bus drilling

die

■ Drilling Plan

80

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

Frontplate cutout

■ Internal Diagram Connection

Applicable wire conductor ø1.6 – 22mm2

www.dienhathe.vn

Hr.

EX100B Tripping Time

Min.

Max. value

Base ambient temperature 40ºC

Sec.

Tripping Time (%)

Min. value

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

e.x

Mounting hole for M4 screw

nh ath

Earthleakage trip indicator

■ Drilling Plan

w.

2-M4 tap holes or ø5 holes

ww

1mm clearance on each side of handle

For front mounting bolts

Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 38mm2 M8 screw

Direct-connected bus drilling

die

Test button

■ Terminal Arrangement

Temperature Compensation Curve

Applicable wire conductor ø1.6 – 22mm2

www.dienhathe.vn

81

Hr.

Hr.

RXK125-S / RXK125-H

Min.

Current (percent rated current)

Overcurrent Tripping Characteristic Curve (15-30A)

Overcurrent Tripping Characteristic Curve (31-125A)

e.x

Phase insulator (Removable) 2-M4 mounting holes

Test button

nh ath

Rated sensitivity current selector (if provided)

Operating time selector (Time delay type only)

Trip button

Direct-connected bus drilling

die

■ Drilling Plan

ww

w.

2-M4 screw holes or ø5 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 60mm2 (22mm2 for 50A or less)

9.5

24

17

M8 screw (M6 screw for 50A or less)

Bus or pressure wire conductor connection (

): dimensions only for 50A or less

Applicable wire conductor ø1.6 – 22mm2

Wire connection (15 to 50A)

82

Max. interrupting time

Current (percent rated current)

■ Dimensions

Earth leakage trip indicator

Min. value Sec.

Min. value

Max. interrupting time

Max. value of 31 to 50A

yz

Sec.

Tripping Time

Max. value

Tripping Time

Min.

Max. value of 51 to 125A

www.dienhathe.vn

Hr.

EX225 Tripping Time

Min.

Max. value

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Sec.

Min. value

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

e.x

Mounting hole for M4 screw

Phase separator Earthleakage indicator

nh ath

Rated sensitivity current selector (if provided)

Test button

Direct-connected bus drilling

die

■ Drilling Plan

Temperature Compensation Curve

ww

w.

4 (or 2)-M4 tap holes or ø5 holes

For front mounting bolts

■ Terminal Arrangement

1mm clearance on each side of handle Frontplate cutout

■ Internal Diagram Connection

Maximum applicable pressure -type wire connector = 60mm2 Special pressure type wire connector is attached for 175 – 225A as shown on the right table

Rated current (A) Applicable wire size of pressuretype wire connector (mm2) 175 – 225 Pressure-type wire connector 80, 100, 125 (mm)

Pressure-type wire connector directly connected

www.dienhathe.vn

83

Hr.

EXK225 Tripping Time

Min.

Max. value

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Sec.

Min. value

Current (percent rated current)

Ambient Temperture (ºC)

e.x

■ Dimensions Phase separator

Trip button

Test button Operating time selector Earthleakage trip indicator

■ Drilling Plan

ww

w.

2-M4 screw hole or ø5 hole

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Direct-connected bus drilling

die

2-M4 mounting hole

nh ath

Rated sensitivity current selector (if provided)

Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 150mm2

M8 screw

Pressure-type wire connector directly connected

84

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

www.dienhathe.vn

Hr.

RXK250-S / RXK250-H

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Min. value Sec.

Tripping Time

Min.

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

e.x

Mounting hole for M4 screw

Earthleakage trip indicator

nh ath

Rated sensitivity current selector (if provided) Operating time selector (Time delay type only) Test button

Direct-connected bus drilling

die

■ Drilling Plan

Temperature Compensation Curve

ww

w.

4-M4 tap holes or ø5 holes

For front mounting bolts

■ Terminal Arrangement Maximum applicable pressure t-ype wire connector = 60mm2 Special pressure type wire connector is attached for 175 – 225A as shown on the right table

1mm clearance on each side of handle Frontplate cutout

■ Internal Diagram Connection

Rated current (A) Applicable wire size of pressuretype wire connector (mm2) 175 – 225 Pressure-type wire connector 80, 100, 125 (mm)

Pressure type wire connector directly connected

www.dienhathe.vn

85

Hr.

EX400 / RX400

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Min. value

Sec.

Tripping Time

Min.

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

Phase separator

Earthleakage indicator Operating time selector (Time delay type only) Test button

die

■ Drilling Plan

nh ath

Rated sensitivity current selector (if provided)

e.x

■ Dimensions Mounting hole for M4 screw

ww

w.

4-M4 tap holes or ø5 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M10 bolt

86

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

www.dienhathe.vn

Max. interrupting time

Sec.

Tripping Time

Min.

Hr.

EX400B / RX400B

Current (percent rated current)

200A setting 400A setting

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

e.x

Phase separator

Phase separator

4-M6 mounting hole

4-M6 mounting hole

Rated sensitivity current selector Operating time selector Earth leakage indicator Test button

Operating time selector Earth leakage indicator Test button

Rated current selector Trip button

Rated current selector Trip button

die

■ Drilling Plan

nh ath

Rated sensitivity current selector

w.

4-M6 screw hole or ø7 hole

ww

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

M10 bolt

www.dienhathe.vn

87

Hr.

Max. interrupting time

Sec.

Tripping Time

Min.

EX600B / RX600B

Current (percent rated current)

300A setting 600A setting

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions 4-M6 mounting hole

e.x

Phase separator

Test button

nh ath

Rated sensitivity current selector

Operating time selector Earth leakage indicator

Rated current selector

■ Drilling Plan

w.

4-M6 screw hole or ø7 hole

die

Trip button

ww

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

M12 bolt

88

www.dienhathe.vn

Hr.

Max. interrupting time

Sec.

Tripping Time

Min.

EX800B / RX800B

Current (percent rated current)

400A setting 800A setting

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions Phase separator

e.x

4-M6 mounting hole

Test button

nh ath

Rated sensitivity current selector

Operating time selector Earth leakage indicator

Rated current selector

4-M6 screw hole or ø7 hole

w.

■ Drilling Plan

die

Trip button

ww

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

M12 bolt

www.dienhathe.vn

89

Adjustable magnetic trip range (in 4 steps)

Hr.

Base ambient temperature 40ºC

Position of setting Max. interrupting time

Compensation rate of rated current (%)

Min. value

Sec.

Tripping Time

Min.

RF-1000KN

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

die

■ Drilling Plan

ww

w.

4-M10 tap holes or ø11 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M12 bolt

90

www.dienhathe.vn

Hr.

Max. interrupting time

Sec.

Tripping Time

Min.

RF-1000CBN

1000A setting (time highly type) 500A setting (time highly type)

Current (percent rated current)

500A setting (time delay type) 1000A setting (time delay type)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions M10 mounting hole

ø13.5 holes

e.x

Phase separator

Auxiliary handle

nh ath

Trip button Rated current selector

Sealed cover

Rated sensitivity current selector

Test button

die

■ Drilling Plan

Earth leakage indicator and reset button

ww

w.

4-M10 screw hole or ø11 hole

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M12 bolt

www.dienhathe.vn

91

Adjustable magnetic trip range (in 4 steps)

Hr.

Base ambient temperature 40ºC

Position of setting Max. interrupting time

Compensation rate of rated current (%)

Min. value

Sec.

Tripping Time

Min.

RF-1200KN

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

die

■ Drilling Plan

ww

w.

4-M10 tap holes or ø11 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M12 bolt

92

www.dienhathe.vn

Hr.

Max. interrupting time

Sec.

Tripping Time

Min.

RF-1200CBN

1200A setting (time highly type) 600A setting (time highly type)

Current (percent rated current)

600A setting (time delay type) 1200A setting (time delay type)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions M10 mounting hole

ø13.5 holes

e.x

Phase separator

Auxiliary handle

nh ath

Trip button Rated current selector

Sealed cover

Rated sensitivity current selector

Test button

die

■ Drilling Plan

Earth leakage indicator and reset button

ww

w.

4-M10 screw hole or ø11 hole

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M12 bolt

www.dienhathe.vn

93

Hr.

Max. value for 31 to 100A Max. value for 30A or less Base ambient temperature 40ºC

Min. value for 31 to 100A Min. value for 30A or less

Tripping Time (%)

Sec.

Tripping Time

Min.

RX100 4P

Current (percent rated current)

Ambient Temperture (ºC)

■ Dimensions

e.x

Mounting hole for M4 screw

Phase separator

Rated sensitivity current selector (if provided)

nh ath

Test button

Earth leakage trip indicator

ww

w.

4-M4 tap holes or ø5 holes

Center of handle

For front mounting bolts

Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 38mm2 (22mm2 for 50A or less)

M8 screw (M6 screw for 50A or less)

94

Applicable wire conductor ø1.6 – 22mm2

www.dienhathe.vn

ø8.5 hole (ø6.5 hole for 50A or less)

Direct-connected bus drilling

die

■ Drilling Plan

■ Terminal Arrangement

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

Hr.

Max. value

Tripping Time

Min.

Base ambient temperature 40ºC

Sec.

Min. value

Max. interrupting time

Compensation rate of rated current (%)

RG-225BH 4P RG-225BN 4P

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

■ Dimensions

e.x

Phase separator 4-Mounting hole for M6 screw Earth leakage trip indicator

nh ath

Test button

Rated sensitivity current selector

ø5.5 holes

Direct-connected bus drilling

die

■ Drilling Plan

Temperature Compensation Curve

ww

w.

4-M6 tap holes or ø7 holes

For front mounting bolts

■ Terminal Arrangement

1mm clearance on each side of handle Frontplate cutout

■ Internal Diagram Connection

Max. applicable pressure-type wire connector: 100mm2

M10

Bus or pressure-type wire connector connection

www.dienhathe.vn

95

Hr.

RG-400BN 4P RG-400BH 4P

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Min. value Sec.

Tripping Time

Min.

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

■ Dimensions

e.x

Phase separator Mounting hole for M6 screw

S.N pole

Test button

R.T pole

nh ath

Earth leakage trip indicator

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

Rated sensitivity current selector

ø11 holes

die

■ Drilling Plan

ww

w.

4-M6 tap holes or ø4-7 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M10 bolt

96

www.dienhathe.vn

Hr.

RF-600FN 4P

Adjustable magnetic trip range (in 4 steps) Position of setting

Max. interrupting time

Base ambient temperature 40ºC Compensation rate of rated current (%)

Min. value

Sec.

Tripping Time

Min.

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve ■ Dimensions

Trip button Reset buton and earth leakage trip indicator

nh ath

ø13.5 holes

e.x

Phase separator 4-mounting holes for M8 screw

Temperature Compensation Curve

Rated sensitivity current selector

Test button

die

■ Drilling Plan

ww

w.

4-M8 tap holes or ø9 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M12 bolt

www.dienhathe.vn

97

Adjustable magnetic trip range (in 4 steps)

Hr.

Min. value

Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Position of setting Sec.

Tripping Time

Min.

RF-800KN 4P

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

Temperature Compensation Curve

yz

Overcurrent Tripping Characteristic Curve

nh ath

e.x

■ Dimensions

die

■ Drilling Plan

ww

w.

4-M10 tap holes or ø4-11 holes

1mm clearance on each side of handle

For front mounting bolts

■ Terminal Arrangement

Frontplate cutout

■ Internal Diagram Connection

M12 bolt

98

www.dienhathe.vn

Hr.

Min. value

Adjustable magnetic trip range (in 4 steps) Base ambient temperature 40ºC

Max. interrupting time

Compensation rate of rated current (%)

Position of setting Sec.

Tripping Time

Min.

RF-1000KN 4P RF-1200KN 4P

Max. value

Current (percent rated current)

Ambient Temperture (ºC)

yz

Overcurrent Tripping Characteristic Curve

t15

68.5

nh ath

e.x

■ Dimensions

Temperature Compensation Curve

die

■ Drilling Plan

ww

w.

4-M10 tap holes or ø4-11 holes

1mm clearance on each side of handle Frontplate cutout

For front mounting bolts

■ Terminal Arrangement

■ Internal Diagram Connection

M12 bolt

www.dienhathe.vn

99

R-NZB

■ Dimensions

Mounting holes

Rated sensitivity current selector

Terminal screw for M3.5 Test button

■ Internal Diagram Connection

e.x

■ Drilling Plan

nh ath

2-M4 tap holes or ø2-5 holes

■ Dimensions

Mounting holes

Rated sensitivity current selector

Operating time selector

die

R-NZBT

Reset button

yz

Indication lamp

Terminal screw for M3.5

Test button

Reset button

ww

w.

Indication lamp

■ Internal Diagram Connection

■ Drilling Plan

2-M4 tap holes or ø2-5 holes

100

www.dienhathe.vn

R-NZBK

■ Dimensions

Mounting holes

Rated sensitivity current selector Operating time selector

Test button

yz

Terminal screw for M3.5 Indication lamp

■ Internal Diagram Connection

e.x

■ Drilling Plan

die

Mounting holes

Rated sensitivity current selector

Terminal screw for M3.5

Indication lamp Reset button

w.

Test button

ww

R-NZBL

■ Dimensions

nh ath

2-M4 tap holes or ø2-5 holes

■ Internal Diagram Connection

■ Drilling Plan

2-M4 tap holes or ø2-5 holes

www.dienhathe.vn

101

R-NZBR

■ Dimensions

Mounting holes

Rated sensitivity current selector Operating time selector

Terminal screw for M3.5 Test button

Reset button

yz

Indication lamp

■ Internal Diagram Connection

e.x

■ Drilling Plan

ww

w.

die

nh ath

2-M4 tap holes or ø2-5 holes

102

www.dienhathe.vn

Z-400B

■ Dimensions

■ Drilling Plan

Terminal screw for M3.5

ø13.5 holes

4-M6 tap holes or ø4-8 holes 3 pole

3 pole

■ Terminal Arrangement

4 pole

Z-600B

■ Dimensions

M12 bolt

e.x

yz

Terminal screw for M3.5

ø13.5 holes

4-M6 tap holes or ø4-8 holes 4 pole

■ Drilling Plan

nh ath

Terminal screw for M3.5

ø13.5 holes 3 pole

4-M6 tap holes or ø4-8 holes 4 pole

■ Terminal Arrangement

die

Terminal screw for M3.5

4-M6 tap holes or ø4-8 holes 3 pole

M12 bolt

ø13.5 holes

■ Dimensions

ww

Z-800B

w.

4 pole

■ Drilling Plan

Terminal screw for M3.5

ø13.5 holes 3 pole

3 pole

Terminal screw for M3.5

4-M8 tap holes or ø4-10 holes

4 pole

4-M8 tap holes or ø4-10 holes

■ Terminal Arrangement

M12 bolt

ø13.5 holes

4 pole

www.dienhathe.vn

103

Z-1000B

■ Dimensions

■ Drilling Plan

Terminal screw for M3.5

ø13.5 holes 3 pole

3 pole

4-M8 tap holes or ø4-10 holes

4 pole

4-M8 tap holes or ø4-10 holes

■ Terminal Arrangement

yz

Terminal screw for M3.5

M12 bolt

e.x

ø13.5 holes

4 pole

■ Drilling Plan

Terminal screw for M3.5

ø13.5 holes 3 pole

nh ath

Z-1200B

■ Dimensions

3 pole

4-M8 tap holes or ø4-10 holes

4 pole

4-M8 tap holes or ø4-10 holes

■ Terminal Arrangement

M12 bolt

die

Terminal screw for M3.5

ø13.5 holes

■ Dimensions

ww

Z-2000B

w.

4 pole

■ Drilling Plan

Terminal screw for M3.5

ø4-11 holes

3 pole

3 pole Terminal screw for M3.5

4-M8 tap holes or ø4-12 holes

4 pole

■ Terminal Arrangement

M10 bolt

ø11 holes

4 pole

104

www.dienhathe.vn

4-M8 tap holes or ø4-12 holes

yz

ZR-15 — 120

■ Dimensions

Surface K

Mounting holes

Mounting holes

e.x

2-M4 mounting holes

ø15 holes

nh ath

Surface L

Output terminal (M3.5)

ø30 holes

Mounting holes

Surface K

Mounting holes

4-øH holes

ww

Surface L

ZR-30B

w.

ZR-15

die

Outlet terminal wire 0.5mm2 length 500mm

ho l øD

ø58 holes

Output terminal (M3.5)

es

Output terminal (M3.5)

ZR-58B

ZR-65 — 120 Type

A

B

C

D

E

ZR-65

145

170

79

Ø65

75

80 × 60

Ø6

6

1.6

ZR-80

172

198

89

Ø80

90

100 × 65

Ø6

6

2.0

ZR-100

185

222

90

Ø100

100

110 × 65

Ø8

8

2.5

ZR-120

226

264

95

Ø120

120

140 × 70

Ø9.5

9.5

3.0

www.dienhathe.vn

F×G

H

J

(kg)

105

FOR

WELDERS

Tripping Time (sec.)

Max. value

Sec.

Tripping Time

Min.

Hr.

E ARTH L EAKAGE BREAKERS

Setting time (sec.)

Max. value

Min. value

Continuous Tripping Instantaneous Current (A) Current Tripping Current (A)

Overcurrent Tripping Characteristic Curve

■ Ratings and Specifications Type

RXW225

Number of Poles

Earth Leakage Tripping Characteristic Curve (at 0.3 sec.)

RGW-400B

2

Rated Voltage (AC V)

nh ath

200, 415

Rated Sensitivity Current (mA)

100 ∙ 200 ∙ 500*

Operating Time (sec.)

**0.3 ∙ 0.6 ∙ 1.2*

Rated Current (kA)

(0.1 ∙ 0.2)*

225

Instantaneous Tripping Current (kA)

400

3—4

AC200V

3.6 — 4.4

85

AC415V

42

3±1

Setting Current (A)

Continuous Current Protection

Earth Leakage Current (Percent Rated Sensitivity Current)

e.x

RXW225

Interrupting Capacity (kA) sym.

yz

Min. value

Setting Time (sec.)

**0.3 ∙ 0.6 ∙ 1.2(3)*

Release Time (sec.)

0.1

For pressure-type wire connector terminal

Front bar terminal

Net Weight (kg)

7.4

8.3

die

Terminal

w.

Note: * Interchangeable by manual operation. ** Earth leakage tripping time and continuous current tripping time are interlocked.

■ Selection

Rated Current of ELCB (A)

Setting Current of Instantaneous Tripping Current (A)

111

225

1200

50

106

225

1200

75

219

400

2250

100

330

400

3500

35

111

225

600

50

106

225

600

200

415

(

ww

Specifications of Welder Rated Voltage (AC V)

Rated Capacity (kVA)

Maximum Input (typ.)(kVA)

35

75

219

225

1200

100

330

225

1700

125

(395)

400

2250

150

(475)

400

2500

200

(630)

400

3500

): for reference value

106

www.dienhathe.vn

RXW225

■ Dimensions

4-M4 mounting hole

Earth leakage indicator

M8 screw

Indication lamp

Test button

Rated sensitivity current selector

yz

Operation time selector

■ Drilling Plan

■ Dimensions

Insulting barrier easy installation ø11 holes 4-mounting hole for M6 screw

die

RGW-400B

nh ath

e.x

4-M4 mounting holes or ø5 holes

w.

Continuous currrnt and earth leakage indicator

ww

Rated operation time selector

Test button

Rated sensitivity current selector

■ Drilling Plan M6 tap holes or ø7 holes

www.dienhathe.vn

107

MINIATURE CIRCUIT BREAKERS MCB is applicable to electric circuit with rated voltage 230/400V, 240/415V AC, frequency 50/60Hz and rated current is up to 63A. The product provides against overload and short circuit and equipments in

BTK63 series

Alarm switch (for BK63)

Auxiliary switch

TRIPPING CHARACTERISTICS

die

nh ath

BK63 series

e.x

MCB is also used as non-frequent changeover of electric circuit.

yz

household and commercial installations.

COLORED HANDLES

w.

n Type B Instant tripping characteristics : 3–5In Application : computers and electronic equipments

Easy to distinguish the rated current of the MCB by means of colored handle.

1A

Black

2A

Pink

3A

Pink

4A

Brown

6A

Green

10A

Red

16A

Grey

20A

Blue

25A

Yellow

32A

Purple

n CE marking

40A

Black

n CB Certificate

50A

White

63A

Cupper-colored

ww

n Type C I nstant tripping characteristics : 5–10In

Application : general load such as bulbs , motors

n Type D

Instant tripping characteristics : 10–20In Application : high current surge device such as transformers, motors with heavy load

APPROVAL

108

www.dienhathe.vn

SPECIFICATIONS

Type

BK63

BTK63 Overload and short circuit

Rated current

1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A

Characteristics

B, C, D curve

Number of poles

1P, 1P+N, 2P, 3P, 3P+N, 4P 2, 3, 4P

6kA at 230/400VAC

6kA at 400VAC

Standards

2, 3, 4P

10kA at 240/415VAC

10kA at 415VAC

IEC60898

Approval

SEMKO CB scheme

KEMA CB scheme

Thermal magnetic release

nh ath

Type of trip Electrical endurance

6,000 operations

Installation

8,000 operations

35mm DIN rail

Width

17.8mm per pole

Lug type (Cable up to 25mm2)

Type of terminal

1changeover contact 6A at 230VAC,3A at 415VAC(AX) 6A at 230VAC,3A at 415VAC(AL) 2A at 48VAC,1A at 125VAC

die

Alarm switch (Optional)

1P

e.x

Breaking capacity

1P

yz

Protection

Not applicable

Lug terminal Cable capacity 2.5mm2

Dimension

(mm)

(mm)

ww

w.

9mm wide

www.dienhathe.vn

109

C HARACTERISTIC

C OMPENSATION

CURVE AND

CURVE

n Characteristic curve For type BK63, BTK63

n Compensation table

ww

w.

die

nh ath

e.x

yz

Operating curves

n Compensation curve

[Temperature copensation table](IEC60898-1) In(A)

1 1.05 1.02 1.0 0.98 0.95 0.93 0.9 0.89 0.85 2 2.03 2.04 2.0 1.96 1.92 1.88 1.84 1.8 1.74 3 3.18 3.09 3.0 2.91 2.82 2.7 2.61 2.49 2.37 4 4.24 4.12 4.0 3.88 3.75 3.64 3.52 3.36 3.24 6 5.24 6.12 6.0 5.88 5.76 5.64 5.52 5.4 5.3 10 10.6 10.3 10.0 9.7 9.3 9.0 8.6 8.2 7.8 16 16.8 16.5 16.0 15.5 15.2 14.7 14.2 13.8 13.3 20 21.0 20.6 20.0 19.4 19.0 18.4 17.8 17.4 16.8 25 26.2 25.7 25.0 24.2 23.7 23.0 22.2 21.5 20.7 32 33.5 32.9 32.0 31.4 30.4 29.8 28.4 28.2 27.5 40 42.0 41.2 40.0 38.8 38.0 36.8 35.6 34.4 33.2 50 52.5 51.5 50.0 48.5 47.4 45.5 44.0 42.5 40.5 63 66.2 64.9 63.0 61.0 58.0 56.7 54.2 51.7 49.2 [1:113% In 12:145% In accordng to IEC60898-1]

110

www.dienhathe.vn

RESIDUAL CURRENT CIRCUIT BREAKERS RCCB is applicable to electric circuits with rated voltage 240/415VAC, frequency 50/60Hz and rated current up to63A. The RCCBs provides indirect protection to the operator’s body under such condition that the exposed live parts should be connected to a proper earthing pole. The RCCB also provides protection against the fire danger caused by earth fault

e.x

yz

current due to function failure of over current protection device.

w.

FEATURES

die

nh ath

RK63 series

ww

n RCCBs with rated sensitivity up to 30mA can be used as supplementary protecting device in case other protecting device fails its protection against electric shock.

APPROVAL n CE marking n CB Certificate

n RCCBs designed for household installation and other similar application, is for non-professional operation, and no maintenance is required. n RCCBs provides no protection against electric shock resulted from direct contacts of both protected lines, or leakage current between these two lines. n Particular devices such as surge protective devices, surge arresters etc are recommended to installation at upstream line to RCCBs as precaution against potential surge voltage and current occurring at its power input side.

COLORED HANDLES n Black only.

n Satisfying conditions and applications as mentioned above, RCCBs with ON-OFF indicating device is considered suitable for isolation function.

www.dienhathe.vn

111

SPECIFICATIONS

RK63

Protection

Ground fault

Rated current

25, 32, 40, 63A

Operating I∆n

30, 100, 300mA (non-adjustable)

Non operating I∆n

0.5I∆n

Number of poles

2, 4 pole

Rated voltage

240VAC (2P), 240/415VAC(4P)

Residual current off time

≤0.1 sec.

Standards

IEC61008

Approval

SEMKO CB scheme

Type of trip of grand fault

Electro-magnetic (No over current relay)

e.x

nh ath

Conditional short circuit capacity (Inc) Rated making capacity (Im)

6kA

500A for In=25,32,40A 630A for In=63A

Electrical endurance

6,000 times

Installation

35mm DIN rail

Lug type (Cable up to 35mm2)

112

(mm)

w. ww

Dimension

17.8mm per pole

die

Width Type of terminal

yz

Type

4P

www.dienhathe.vn

2P

min.

sALes LoT

n MCBs Type

Min. sales lot (pcs.) BTK63 1P

120

BK63 2P

BTK63 2P

60

BK63 3P

BTK63 3P

40

BK63 4P

BTK63 4P

30

n RCCBs Type RK63 2P

Min. sales lot (pcs.) 60 30

ww

w.

die

RK63 4P

nh ath

e.x

yz

BK63 1P

www.dienhathe.vn

113

AIR CIRCUIT BREAKERS oRDeRinG ACB & Accessories

3P / 4P Standard D type RST (N)

AKN

08 830AF

10 13 16 AKS 20

1000AF 1250AF 1600AF 2000AF

20 2000AF

4P Reverse W phase type NRST

3P / 4P Standard D type RST (N)

AKH AKS

40 4000AF

50 5000AF

40 4000AF

AKH AKS 50 5000AF 63 6300AF

114

3P (D)

4

3

4P Reverse phase type NRST

4P (D, W)

06 08 10 13 16 20 25 32 40

630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A

3P (E)

4

4P (E, X)

3P/4P Standard D type RST(N)

3

3P (F)

40 4000A

4P Reverse W phase type NRST

4

4P (F, Y)

50 5000A

3

3P (G)

ww

AKS

W

w.

25 2500AF 32 3200AF 40 4000AF

3

00 02 04 06 04 06 08 10 13 16 20

Rated current (CT Spec.) Without OCR & CT 200A 400A 630A 400A 630A 800A 1000A 1250A 1600A 2000A

nh ath

06 630AF

AKH

No. of pole

die

AKH AKS AKN

Frame size & phase array

e.x

Ampere frmae - -

Type

yz

AKH

D

3P/4P Standard type RST(N)

4P Reverse W phase type NRST

40 4000A 50 5000A

4

4P (G, Z)

www.dienhathe.vn

63 6300A

Connections Draw-out type

J

Manual connection

A

Automatic connection

Fixed type H Horizontal type V Vertical type Mixed type M Line: Horizontal Load: Vertical Mixed type N Line: Vertical Load: Horizontal P Front type

D0 D1 D2 D3 D4 D5 D6 D7

Without Shunt coil AC / DC 100 – 130V AC / DC 200 – 250V DC 125V DC 24 – 30V DC 48 – 60V AC 380 – 480V AC 48V

Closing coil rated voltage

AL A2 A3 A4 A5 A6 A7 A8 C S B M D K K2 K3 R T H 1)

AX AC BX BC HX HC CC JC

yz

Standard OFF-Charge 3a3b Standard ON-Charge 3a3b Standard OFF-Charge 5a5b Standard ON-Charge 5a5b High capacity OFF-Charge 5a5b High capacity ON-Charge 5a5b Standard ON-Charge 6a6b High capacity ON-Charge 6a6b

die

Without Closing coil AC / DC 100 – 130V AC / DC 200 – 250V DC 125V DC 24 – 30V DC 48 – 60V AC 380 – 480V AC 48V

Closing coil rated voltage

w.

D0 D1 D2 D3 D4 D5 D6 D7

Trip relay

e.x

Without Motor AC / DC 100 – 130V AC / DC 200 – 250V DC 125V DC 24 – 30V DC 48 – 60V AC 380 – 415V AC 440 – 480V AC 48V

AL1 + MRB AL1 + AL2 + MRB AL1 + MRB + RES (AC / DC 100 – 130V) AL1 + MRB + RES (AC / DC 200 – 250V) AL1 + MRB + Auto reset AL1 + AL2 + MRB + Auto reset AL1 + MRB + RES (AC / DC 100 – 130V) + Auto reset AL1 + MRB + RES (AC / DC 200 – 250V) + Auto reset C CS2 B MI DI or MOC K1 K2 K3 RCS TM SHT2

ww

MA M1 M2 M3 M4 M5 M6 M7 M8

Shunt coil rated voltage

nh ath

Motor rated voltage

UVT coil rated voltage U0 U1 U2 U3 U4 U5 U6 U7

Without UVT coil AC / DC 100 – 130V AC / DC 200 – 250V DC 125V DC 24 – 30V DC 48 – 60V AC 380 – 480V AC 48V

*UVT Delay module is available over AC / DC 48V

Accessories Trip alarm contact 1a + Manual reset button Trip alarm contact 2a + Manual reset button Trip alarm contact 1a + Manual reset button + Remote reset switch Trip alarm contact 1a + Manual reset button + Remote reset switch AL + Auto reset type A2+ Auto reset type A3 + Auto reset type A4 + Auto reset type Counter Charge switch communication ON / OFF button lock Mechanical Interlock Door Interlock or Mechanical Operated Cell Switch Key Lock Key Interlock set Key Lock double Ready to close switch Temperature Alarm Double Shut Coil

Note) 1. UVT and SHT2 aare alternative. 2. Other accessories should be ordered seperately.

www.dienhathe.vn

115

oRDeRinG Cradle

No. of pole

H Horizontal type V Vertical type P Front type Mixed type M Line: Horizontal Load: Vertical

3P 4P

Mixed type N Line: Vertical Load: Horizontal

Terminal connections

J

Manual connection

A

Automatic connection

w. ww 116

Safety shutter

E

Without safety shutter

e.x

3 4

Connections

nh ath

Rated current & frmae H16D AKH-06 – 16D H20D AKH-20D H32E AKH-20 – 32E H40E AKH-40E H50G AKH-40 – 50G H63G AKH-63G N16D AKN-06 – 16D S20D AKS-20D S32E AKS-20 – 32E S40E AKS-40E S50F AKS-40 – 50F S50G AKS-40 – 50G S63G AKS-63G

die

ACB cradle

yz

AL

www.dienhathe.vn

F

With safety shutter

Arc cover N

Without Arc cover

S

With Arc cover

oRDeRinG Trip relay

Trip relay type

0 Without trip relay

Without trip relay

N N Normal

G 0

Without comm.

*LSIG configuration as standard - with LED indicators - without output contacts *Ground fault system by bector sum

G Z E C K X

G Earth leakage Earth leakage (extemal CT, fault current ≤ 30A) Earth leakage (extemal CT, fault current > 30A) Earth leakage + Comm. Earth leakage (extemal CT, fault current ≤ 30A) + Comm. Earth leakage (extemal CT, fault current > 30A) + Comm.

nh ath

A A Ammeter

e.x

0

Communication & protection

yz

N

Control voltage & frequency

0

Without trip relay

0 5

0 Self-Power, 60Hz Self-Power, 50Hz

0 1 2 5 6 7

0 Self-Power, 60Hz AC / DC 100 – 250V, 60Hz DC 24 – 60V, 60Hz Self-Power, 50Hz AC / DC 100 – 250V, 50Hz DC 24 – 60V, 50Hz

1 2 6 7

1 AC / DC 100 – 250V, 60Hz DC 24 – 60V, 60Hz AC / DC 100 – 250V, 50Hz DC 24 – 60V, 50Hz

1 2 6 7

1 AC / DC 100 – 250V, 60Hz DC 24 – 60V, 60Hz AC / DC 100 – 250V, 50Hz DC 24 – 60V, 50Hz

C K X A

G Earth leakage + Comm. Earth leakage (extemal CT, fault current ≤ 30A) + Comm. Earth leakage (extemal CT, fault current > 30A) + Comm. Pre-Trip Alarm + Comm.

w.

P P Power meter

die

*LSIG configuration as standard *Ground fault system G, C: 4pole unit - fault current over 20% of rated currenty by vector sum 3pole unit - phase unbalanced current over 20% of rated current Z, K: external CT - out ZCT applied E, X: external CT - private ZCT applied *Comm. works under control power *LSIG output contact works under control power (LED indicators works without control power)

S

ww

*LSIG configuration as standard *Ground fault system C: vector sum K: external CT - out ZCT applied X: external CT - private ZCT applied *Comm. works under control power *Applicable to generator protection purpose *Voltage module required for P and S types. (supplied separately) *Ground fault function unavailable at A (Pre-Trip Alarm + Comm.)

S Supreme meter

C K X A

C Earth leakage + Comm. Earth leakage (extemal CT, fault current ≤ 30A) + Comm. Earth leakage (extemal CT, fault current > 30A) + Comm. Pre-Trip Alarm + Comm.

*LSIG configuration as standard *Ground fault system C: vector sum K: external CT - out ZCT applied X: external CT - private ZCT applied *Comm. works under control power *Applicable to generator protection purpose *Voltage module required for P and S types. (supplied separately) *Ground fault function unavailable at A (Pre-Trip Alarm + Comm.) Note) The function like Metering, Communication, ZSI, Remote Reset and DO control are not available only under Self-Power condition.

www.dienhathe.vn

117

R ATinGs

(AF)

Rated current (A)

(in max)

Setting current (A)* Rated current of neutral pole (A)

Control trip relay (... x in max)

AKH-06D 630 200 400 630

at 40ºC

400

Rated service breaking capacity (kA) (Ics) Rated making capacity (kA peak) AC 50 / 60Hz (Icm) Rated shot-time withstand current (kA)

(Icw)

Operating time (ms)

w.

Life cycle (time)

ww

Connections**

Weight (kg) (3P / 4P)

Draw-out type

Fixed type External dimensions (mm) (H x W x D)

220V / 230V / 380V / 415V 460V / 480V / 500V JISC 8201-2-1 550V / 600V / 690V ...% x Icu 220V / 230V / 380V / 415V IEC 60947-2 460V / 480V / 500V JISC 8201-2-1 550V / 600V / 690V 1 sec 2 sec 3 sec Maximum total breaking time Maximum closing time Mechanical Without maintenance With maintenance Electrical Without maintenance With maintenance Horizontal connection Draw-out / Fixed Vertical connection Front connection Mixed connection Main body Motor charging type (With cradle) Manual charging type Cradle only Motor charging type Manual charging type Draw-out 3P type 4P Fixed type 3P 4P IEC 60947-2

die

(Icu)

Trip relay Certificate & Approval *Refer to trip relay specification. **●: Standard, ○: Option

118

400 630 800

nh ath

(Ui) (Ue) (Uimp)

AKH-10D 1000

AKH-13D 1250

AKH-16D 1600

AKH-20D 2000

1000

1250

1600

2000

1600

2000

(0.4 – 1.0) x in max

630 Rated insulation voltage (V) Rated operating voltage (V) Rated impulse withstand voltage (kV) Frequency (Hz) Number of poles (P) Rated breaking capacity (kA sym) AC 50 / 60Hz

AKH-08D 800 400 630 800

e.x

Type Ampere frame

yz

AKH series

www.dienhathe.vn

1000

1250

1,000 690 12 50 / 60 3, 4 85 85 65 100% 187 187 143 65 60 50 40 80 20,000 30,000 5,000 10,000

● ○ ○ ○ 63 / 74 61 / 72 29 / 32 34 / 44 32 / 42 430 x 334 x 375 430 x 419 x 375 300 x 300 x 295 300 x 385 x 295 N, A, P, S type KEMA

● 70 / 85 68 / 83 33 / 40 38 / 47 36 / 45

AKH-10E 1000

AKH-13E 1250

AKH-16E 1600

AKH-20E 2000

AKH-25E 2500

AKH-32E 3200

AKH-40E 4000

630

800

1000

1250

1600

2000

2500

3200

4000

(0.4 – 1.0) x In max 1250

1600

2000

3200

4000

die

1,000 690 12 50 / 60 3, 4 100 100 85 100% 220 220 187 85 75 65 40 80 15,000 20,000 5,000 10,000

2500

nh ath

1000

w.

800

● ○ ○ ○ 87 / 103 85 / 101 44 / 55 44 / 55 42 / 53 430 x 412 x 375 430 x 527 x 375 300 x 378 x 295 300 x 493 x 295 N, A, P, S type KEMA

ww

630

yz

AKH-08E 800

e.x

AKH-06E 630

○ ● 104 / 147 102 / 145 58 / 70 63 / 100 61 / 98

www.dienhathe.vn

AKH-40G 4000

AKH-50G 5000

AKH-63G 6300

4000

5000

6300

(0.4 – 1.0) x In max 4000

5000 1,000 690 12 50 / 60 3, 4 150 150 100 100% 330 330 220 100 100 100 40 80 10,000 15,000 2,000 5,000 ○ ● 181 / 223 179 / 221 97 / 117 98 / 123 96 / 121 460 x 785 x 375 460 x 1,015 x 375 300 x 751 x 295 300 x 981 x 295 N, A, P, S type KEMA

6300

186 / 230 184 / 228 102 / 124 103 / 130 101 / 128

119

R ATinGs

(AF)

Rated current (A)

(in max)

Setting current (A)* Rated current of neutral pole (A)

Control trip relay (... x in max)

AKN-06D 630 200 400 630

at 40ºC

400 630

(Icu)

Rated service breaking capacity (kA) (Ics) Rated making capacity (kA peak) AC 50 / 60Hz (Icm) Rated shot-time withstand current (kA)

(Icw)

Operating time (ms)

ww

Connections**

Weight (kg) (3P / 4P)

Draw-out type

Fixed type External dimensions (mm) (H x W x D)

220V / 230V / 380V / 415V 460V / 480V / 500V JISC 8201-2-1 550V / 600V / 690V ...% x Icu 220V / 230V / 380V / 415V IEC 60947-2 460V / 480V / 500V JISC 8201-2-1 550V / 600V / 690V 1 sec 2 sec 3 sec Maximum total breaking time Maximum closing time Mechanical Without maintenance With maintenance Electrical Without maintenance With maintenance Horizontal connection Draw-out / Fixed Vertical connection Front connection Mixed connection Main body Motor charging type (With cradle) Manual charging type Cradle only Motor charging type Manual charging type Draw-out 3P type 4P Fixed type 3P 4P IEC 60947-2

w.

Life cycle (time)

nh ath

(Ui) (Ue) (Uimp)

die

Rated insulation voltage (V) Rated operating voltage (V) Rated impulse withstand voltage (kV) Frequency (Hz) Number of poles (P) Rated breaking capacity (kA sym) AC 50 / 60Hz

Trip relay Certificate & Approval

AKN-08D AKN-10D AKN-13D 800 1000 1250 400 630 1000 1250 800 (0.4 – 1.0) x in max 400 630 1000 1250 800 1,000 690 12 50 / 60 3, 4 65 65 50 100% 143 143 105 50 42 36 40 80 20,000 30,000 5,000 10,000 ● ○ ○ ○ 63 / 74 61 / 72 29 / 32 34 / 44 32 / 42 430 x 334 x 375 430 x 419 x 375 300 x 300 x 295 300 x 385 x 295 N, A, P type KEMA

e.x

Type Ampere frame

*Refer to trip relay specification. **●: Standard, ○: Option

120

yz

AKN AKS series

www.dienhathe.vn

AKN-16D 1600

AKS-20D 2000

1600

2000

1600

2000

70 70 65 100% 154 154 143 65 55 50

● 70 / 85 68 / 83 33 / 40 38 / 47 36 / 45

AKS-32E 3200

AKS-40E 4000

4000

AKS-50F 5000

2500

3200

4000

4000

5000

(0.4 – 1.0) x In max

● ○ ○ ○ 87 / 103 85 / 101 44 / 50 44 / 55 42 / 53 430 x 412 x 375 430 x 527 x 375 300 x 378 x 295 300 x 493 x 295 N, A, P type KEMA

4000

5000

1,000 690 12 50 / 60 3, 4 100 100 85 100% 220 220 187 85 75 65 40 80 10,000 15,000 2,000 5,000 ○ ● 145 / 173 143 / 171 78 / 90 76 / 94 74 / 92 460 x 629 x 375 460 x 799 x 375 300 x 597 x 295 300 x 767 x 295 N, A, P type KEMA

nh ath

1,000 690 12 50 / 60 3, 4 85 85 85 100% 187 187 187 85 75 65 40 80 15,000 20,000 5,000 10,000

4000

die

3200

w.

2500

AKS-40G 4000

AKS-50G 5000

AKS-63G 6300

4000

5000

6300

(0.4 – 1.0) x In max

○ ● 104 / 147 102 / 145 58 / 70 63 / 100 61 / 98

ww

630, 800 1000, 1250 1600, 2000

yz

AKS-25E 2500

e.x

AKS-20E 2000 630, 800 1000, 1250 1600, 2000

www.dienhathe.vn

(0.4 – 1.0) x In max 4000

5000 1,000 690 12 50 / 60 3, 4 120 120 100 100% 264 264 220 100 90 85 40 80 10,000 15,000 2,000 5,000 ○ ● 181 / 223 179 / 221 97 / 117 98 / 123 96 / 121 460 x 785 x 375 460 x 1,015 x 375 300 x 751 x 295 300 x 981 x 295 N, A, P type KEMA

6300

186 / 230 184 / 228 102 / 124 103 / 130 101 / 128

121

Dimensions Fixed type 2000AF 630 – 1600A: AKH / AKN / AKS-06 – 16D

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

Door Frame: DF (AKH / AKN / AKS-D / E)

Note) The dimensions are for drawout type.

122

www.dienhathe.vn

die

ww

w.

Front connection type

nh ath

e.x

yz

Horizontal type

www.dienhathe.vn

123

Dimensions

Draw-out type 2000AF 630 – 1600A: AKH / AKN / AKS-06 – 16D

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

124

www.dienhathe.vn

die

ww

w.

Front connection type

nh ath

e.x

yz

Horizontal type

www.dienhathe.vn

125

Dimensions

Fixed type 2000AF 2000A: AKH / AKS-20D

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

126

www.dienhathe.vn

Draw-out type 2000AF 2000A: AKH / AKS-20D

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

www.dienhathe.vn

127

Dimensions

Fixed type 4000AF 2000 – 3200A: AKH / AKN / AKS-20 – 32E

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

128

www.dienhathe.vn

nh ath

e.x

yz

Horizontal type

ww

w.

die

Front connection type

www.dienhathe.vn

129

Dimensions

Draw-out type 4000AF 2000 – 3200A: AKH / AKN / AKS-20 – 32E

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

130

www.dienhathe.vn

nh ath

e.x

yz

Horizontal type

ww

w.

die

Front connection type

www.dienhathe.vn

131

Dimensions

Fixed type 4000AF 4000A: AKH / AKS-40E

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

132

www.dienhathe.vn

ww

w.

die

nh ath

e.x

yz

Horizontal type

www.dienhathe.vn

133

Dimensions

Draw-out type 4000AF 4000A: AKH / AKS-40E

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

134

www.dienhathe.vn

ww

w.

die

nh ath

e.x

yz

Horizontal type

www.dienhathe.vn

135

Dimensions

Fixed type 5000AF 4000 – 5000A: AKS-40 – 50F

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

136

www.dienhathe.vn

w.

die

18

nh ath

e.x

yz

Horizontal type

ww

Door Frame: DF (AKH-G, AKS-F )

Note) The dimensions are for drawout type.

www.dienhathe.vn

137

Dimensions

Draw-out type 5000AF 4000 – 5000A: AKS-40 – 50F

nh ath

e.x

yz

Front view

ww

w.

die

Vertical type

138

www.dienhathe.vn

ww

w.

die

nh ath

e.x

yz

Horizontal type

www.dienhathe.vn

139

Dimensions

Fixed type 6300AF 4000 – 6300A: AKH / AKS-40 – 50G

nh ath

e.x

yz

Front view

4000A – 5000A

die 6300A

18

4000A – 5000A

ww

w.

Vertical type

6300A

140

www.dienhathe.vn

yz

Horizontal type

nh ath

e.x

4000A – 5000A

ww

w.

die

6300A

www.dienhathe.vn

141

Dimensions

Draw-out type 6300AF 4000 – 6300A: AKH / AKS-40 – 50G

nh ath

e.x

yz

Front view

4000A – 5000A

4000A – 5000A

142

die ww

w.

Vertical type

6300A

6300A

www.dienhathe.vn

yz

Horizontal type

nh ath

e.x

4000A – 5000A

ww

w.

die

6300A

www.dienhathe.vn

143

ww

w.

die

nh ath

e.x

yz

memo

144

www.dienhathe.vn

Catalog Hitachi_mcb-mccb hitachi.pdf

4th Floor, North Tower. World Finance Centre, Harbour City. Canton Road, Tsim Sha Tsui, Kowloon. Hong Kong. TEL:<852>2735-9218. FAX:<852>2375-3192.

46MB Sizes 1 Downloads 186 Views

Recommend Documents

Catalog ...
Catalog-16_Page_Channel_Think_Range_Winter_OneBook_LowRes_UK.pdf. Catalog-16_Page_Channel_Think_Range_Winter_OneBook_LowRes_UK.pdf.

Datasheet catalog
Dec 6, 1990 - For the DC characteristics see “74HC/HCT/HCU/HCMOS Logic Family Specifications”. Output capability: bus driver. ICC category: MSI. AC CHARACTERISTICS FOR 74HC. GND = 0 V; tr = tf = 6 ns; CL = 50 pF. SYMBOL. PARAMETER. Tamb (°C). UN

Catalog CS_ACE2_MCCB.pdf
... very fast clearance of short. circuit current. ... Prospective. current peak. Actual. current ... Short Circuit protection Magnetic protection. (A). Tripping current Ii (A) ...

2015/2016 Choice Catalog
Century Fox Film Corporation and Bluebush. Productions, LLC. All rights reserved. 28957. High Polish Chrome. Laser Engrave/Auto Engrave. $33.95 ...

Catalog CS_SwitchDisconnectors.pdf
Available in 3 Pole as well as 4 Pole, interiors as. well as in ... current carrying surfaces. It again .... Displaying Catalog CS_SwitchDisconnectors.pdf. Page 1 of ...

Catalog
SESAME STICKS 23. SHAVING CREAM 51 ... w/Randita's (credit: Adam. Milliron). TOP R: swiss chard from. the garden (credit: Terra. Ferderber. MIDDLE: Our ...

catalog korad.pdf
Page 2 of 28. 2. Certificate Reg. No. 04 100 930041. Certificate Reg. No. 44 104 060736. 094 0002646. ÊÎÌÏÀÍÈß. U. S. STEEL KOÅ ICE, s.r.o. - ÏÐÎÈÇÂÎÄÈÒÅËÜ ...

catalog-safetronics.pdf
Page 2 of 20. bezpečnosÅ¥ou vyÅ¡Å¡ou s trezory. Trezory. zbrane na Skrine. spisy na Skrine. 13/NTR TREZORY NÁBYTKOVÉ. (TimeLock® (SOPHIA zámkom ...

Catalog
18: Studio Visit: SEO. 17: Terry Haggerty: Angle of Response / Kuttner Siebert Gallery, Berlin. 14: Interview with Dan Perjovschi at Fumetto Festival Lucerne.

catalog parang.pdf
Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. catalog parang.pdf. catalog parang.pdf. Open. Extract. Open with.

Catalog
10: Urs Fischer: Service à la Française (2009) / Luma Westbau / Pool etc. ...... 10: Claes Oldenburg & Coosje van Bruggen: The European Desktop / Ivorypress ...

Auction catalog - NYSAuctions
Title. Otsego County Tax Foreclosure Real Estate Auction. Description. Auction: Wednesday, August 16th 11AM. Registration at 9AM Location: Holiday Inn ...

IEEE Catalog Number
2011 International Conference for Internet Technology and Secured Transactions. IEEE Catalog Number: ISBN: Technical Inquiries: Professor Charles A ...

Catalog CS_Switch_Disconnector_Fuse_Units.pdf
ISO 9001 certified manufacturing facilities assure quality & .... limited by the fuse link. With rated ... Displaying Catalog CS_Switch_Disconnector_Fuse_Units.pdf.

Catalog AVFF2017_byStudents.pdf
Contact: Tom Mo, Discipline Farm, Auroville, Tamil Nadu – 605101. Phone: 0091-8940566639. Email: tommo(at)defracted.com. DotA 2 Tribute. 2017, Music Video, India, 3 min, English. A fire-spinning performance set to the iconic symphonic music. from t

2015/2016 Choice Catalog
All FENDER guitars and basses, amplifiers, logos, and trade dress, including the .... over the depletion of our natural resources. Both the attractive gift box and the cardboard insert are made from renewable materials and are 100% recyclable.

Catalog
18: Studio Visit: SEO. 17: Terry Haggerty: Angle ...... 19: Interview with Vera Cortês / Vera Cortês Art Agency / ARCO 2008 Madrid, Spain. 18: Dan Perjovschi: Stu ...

Training Catalog
course covers the fundamental concepts of fluid flow in porous media, including an ... teach students the impact of these factors on waterflood performance.

Catalog CS_2Pole-Contactor.pdf
International Business Division: Tel. ... low voltage pick-up, to suite rugged Indian field conditions ensuring long trouble free service, conforming to IS 13947-4-1. ... Building Automation ... Power Rating at 240VAC (AC3) KW/HP 3.8/5 4.8/6.

UI2120G Series Catalog
Obtain motion in minutes: The UI2120G Intelligent Driver combines a high output driver with an easy to use controller/pulse generator. • Consolidates step motor systems from three to two components. • Easy Operation. • Maximum Travel Distance â

Fall Activities Catalog -
Kick-off Tailgate Party . .... Social Conference – Plays primarily Thursday nights with foam ..... subsidized parties, all equipment, and CHASE Kickball t-shirts.

dometic-catalog-vinotecas.pdf
dometic-catalog-vinotecas.pdf. dometic-catalog-vinotecas.pdf. Open. Extract. Open with. Sign In. Main menu. Displaying dometic-catalog-vinotecas.pdf.

Parts Catalog NSR.pdf
Page 4 of 64. Parts Catalog NSR.pdf. Parts Catalog NSR.pdf. Open. Extract. Open with. Sign In. Main menu. Displaying Parts Catalog NSR.pdf. Page 1 of 64.

catalog MCCB, ELCB.pdf
There was a problem previewing this document. Retrying... Download. Connect more apps... Try one of the apps below to open or edit this item. catalog MCCB ...Missing: